WO2008007586A1 - Dispositif de commande de conditionnement d'air - Google Patents
Dispositif de commande de conditionnement d'air Download PDFInfo
- Publication number
- WO2008007586A1 WO2008007586A1 PCT/JP2007/063339 JP2007063339W WO2008007586A1 WO 2008007586 A1 WO2008007586 A1 WO 2008007586A1 JP 2007063339 W JP2007063339 W JP 2007063339W WO 2008007586 A1 WO2008007586 A1 WO 2008007586A1
- Authority
- WO
- WIPO (PCT)
- Prior art keywords
- air conditioner
- control
- compressor
- control device
- mode
- Prior art date
Links
Classifications
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F25—REFRIGERATION OR COOLING; COMBINED HEATING AND REFRIGERATION SYSTEMS; HEAT PUMP SYSTEMS; MANUFACTURE OR STORAGE OF ICE; LIQUEFACTION SOLIDIFICATION OF GASES
- F25B—REFRIGERATION MACHINES, PLANTS OR SYSTEMS; COMBINED HEATING AND REFRIGERATION SYSTEMS; HEAT PUMP SYSTEMS
- F25B49/00—Arrangement or mounting of control or safety devices
- F25B49/005—Arrangement or mounting of control or safety devices of safety devices
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/30—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/30—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring
- F24F11/32—Responding to malfunctions or emergencies
- F24F11/38—Failure diagnosis
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/62—Control or safety arrangements characterised by the type of control or by internal processing, e.g. using fuzzy logic, adaptive control or estimation of values
- F24F11/63—Electronic processing
- F24F11/64—Electronic processing using pre-stored data
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F25—REFRIGERATION OR COOLING; COMBINED HEATING AND REFRIGERATION SYSTEMS; HEAT PUMP SYSTEMS; MANUFACTURE OR STORAGE OF ICE; LIQUEFACTION SOLIDIFICATION OF GASES
- F25B—REFRIGERATION MACHINES, PLANTS OR SYSTEMS; COMBINED HEATING AND REFRIGERATION SYSTEMS; HEAT PUMP SYSTEMS
- F25B13/00—Compression machines, plants or systems, with reversible cycle
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/30—Control or safety arrangements for purposes related to the operation of the system, e.g. for safety or monitoring
- F24F11/32—Responding to malfunctions or emergencies
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F24—HEATING; RANGES; VENTILATING
- F24F—AIR-CONDITIONING; AIR-HUMIDIFICATION; VENTILATION; USE OF AIR CURRENTS FOR SCREENING
- F24F11/00—Control or safety arrangements
- F24F11/50—Control or safety arrangements characterised by user interfaces or communication
- F24F11/52—Indication arrangements, e.g. displays
-
- F—MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
- F25—REFRIGERATION OR COOLING; COMBINED HEATING AND REFRIGERATION SYSTEMS; HEAT PUMP SYSTEMS; MANUFACTURE OR STORAGE OF ICE; LIQUEFACTION SOLIDIFICATION OF GASES
- F25B—REFRIGERATION MACHINES, PLANTS OR SYSTEMS; COMBINED HEATING AND REFRIGERATION SYSTEMS; HEAT PUMP SYSTEMS
- F25B2313/00—Compression machines, plants or systems with reversible cycle not otherwise provided for
- F25B2313/027—Compression machines, plants or systems with reversible cycle not otherwise provided for characterised by the reversing means
- F25B2313/02741—Compression machines, plants or systems with reversible cycle not otherwise provided for characterised by the reversing means using one four-way valve
Definitions
- the present invention relates to an air conditioner control device.
- Patent Document 1 Japanese Unexamined Patent Application Publication No. 2004-156829
- Patent Document 1 makes it easy to extract a plurality of abnormal factors and has a certain effect. However, it is still difficult to narrow down the factors among multiple abnormal factors.
- An object of the present invention is to provide an air conditioning control device capable of easily narrowing down abnormal factors in preparation for an abnormality of an air conditioner.
- An air conditioning control device includes a microcomputer and a memory.
- the microcomputer executes an inspection operation mode in which the air conditioner is operated in the inspection process at the manufacturing site and a normal operation mode in which the air conditioner is operated at the installation site, and the operation state of the air conditioner satisfies a predetermined condition. If not, it is determined that there is an abnormality and the air conditioner is abnormally stopped.
- the memory stores predetermined information according to instructions from the microcomputer. Then, when the air conditioner is abnormally stopped, the microcomputer stores the predetermined operation information acquired until the air conditioner is abnormally stopped and the operation mode that is executed when the air conditioner abnormality occurs in the memory.
- An air conditioning control device is the air conditioning control device according to the first invention, and the normal operation mode is composed of a plurality of control modes.
- the microcomputer stores the control mode in memory when the air conditioner malfunctions!
- an abnormality that can only occur in the control mode is specified by identifying the control mode.
- the analysis target power of abnormal factors that cannot occur in the control mode is also excluded. For this reason, it becomes easy to narrow down abnormal factors.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein a plurality of control modes include a control during stop for controlling the air conditioner when the compressor is stopped. Mode is included.
- the air conditioner has a refrigerant circuit including a compressor.
- This air-conditioning control device makes it easy to narrow down the cause of an error when an error occurs during control during stoppage.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein a plurality of control modes eliminates the pressure difference between the high pressure side and the low pressure side before starting the compressor. It includes a pre-starting equalization control mode.
- the air conditioner has a refrigerant circuit including a compressor.
- This air-conditioning control device makes it easy to narrow down the cause of an abnormality that occurs during pressure equalization control before startup.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein the plurality of control modes include a start control mode for starting the compressor.
- the air conditioner has a refrigerant circuit including a compressor.
- This air-conditioning control device makes it easy to narrow down the cause of an abnormality that occurs during start-up control.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein the plurality of control modes include a test operation control mode for performing a test operation after installing the air conditioner.
- This air-conditioning control device makes it easy to narrow down the cause of an abnormality for an abnormality that occurred during trial operation control.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, comprising a plurality of The control mode includes a steady control mode in which the air conditioner is operated normally after the compressor is started.
- the air conditioner has a refrigerant circuit including a compressor. This air-conditioning control device makes it easy to narrow down the cause of an abnormality that occurs during steady-state control.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein, in a plurality of control modes, an oil return for forcibly recovering the refrigeration oil accumulated in the refrigerant circuit to the compressor. Control mode is included.
- the air conditioner has a refrigerant circuit including a compressor. In this air conditioning control device, abnormalities that cannot occur with respect to abnormalities that occur during oil return control are excluded from the analysis target of abnormal factors. Therefore, it becomes easy to narrow down abnormal factors.
- An air conditioning control device is the air conditioning control device according to the second invention, wherein in a plurality of control modes, the liquid refrigerant in the refrigerant circuit is stored in a predetermined container when the operation of the air conditioner is stopped. A down control mode is included.
- the air conditioner has a refrigerant circuit including a compressor.
- abnormalities that do not occur with respect to the abnormalities that occurred during the pump down control are excluded from the analysis target of the abnormal factors, so that it is easy to narrow down the abnormal factors.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein the plurality of control modes include a defrost control mode in which defrosting is performed during frost formation during heating operation of the air conditioner. It is included.
- abnormalities that cannot occur in contrast to abnormalities that occurred during defrost control are excluded from the analysis target of abnormal factors, making it easier to narrow down abnormal factors.
- An air conditioning control device is the air conditioning control device according to the second aspect of the present invention, wherein the plurality of control modes includes a defrost that performs control after completion of defrosting during the heating operation of the air conditioner.
- a post-control mode is included.
- An air conditioning control device is the air conditioning control device according to the first aspect of the present invention, wherein the microcomputer transmits and receives signals between the outdoor side of the air conditioner and the indoor side of the air conditioner. Switch between the operation mode for inspection and the normal operation mode based on the transmitted source information that proves the identity of the indoor side.
- the power of the abnormality that occurred during the inspection becomes clear, such as whether the abnormality occurred during normal operation, or the like. This makes it easier to narrow down abnormal factors.
- an abnormality that can occur only in the control mode is specified by determining the control mode.
- abnormalities that do not occur in the control mode are excluded from the analysis target power of the abnormal factors. This makes it easier to narrow down abnormal factors.
- abnormalities that cannot occur with respect to abnormalities that occur during predetermined control are excluded from the analysis target of abnormal factors, making it easy to narrow down abnormal factors. Become.
- FIG. 1 is a block diagram of an air conditioner.
- FIG. 2 Configuration diagram of the operation mode of the air conditioner.
- FIG. 3 is a flowchart of operation mode selection control.
- FIG. 4 is a flowchart of abnormality confirmation control for a low pressure abnormality.
- FIG. 5 is a flowchart of abnormality confirmation control for a low pressure abnormality.
- FIG. 1 is a block diagram of the air conditioner.
- the air conditioner 1 is a multi-type air conditioner for buildings, and a plurality of air conditioner indoor units 3 are connected in parallel to one or a plurality of air conditioner outdoor units 2 so that refrigerant can flow.
- Compressor 111 four-way switching valve 112, outdoor heat exchanger 113, outdoor expansion valve 114, indoor expansion valve 115, indoor heat exchanger 116, gas shut-off valve 118, liquid shut-off valve 119, etc.
- Circuit 10 is formed.
- the control device 4 includes a microcomputer 5 and a memory 6.
- the microcomputer 5 transmits and receives signals between the air conditioner outdoor unit 2 and the air conditioner indoor unit 3 via the internal / external transmission line 50 (hereinafter referred to as internal and external). This is called transmission, and the necessary information is stored in the memory 6. ⁇ Operation mode>
- Fig. 2 is a block diagram of the operation mode of the air conditioner.
- the operation mode 701 of the air conditioner 1 is classified into an operation mode for inspection and a normal operation mode.
- the operation mode for inspection is a mode operated in the inspection process at the manufacturing site, and is hereinafter referred to as inspection operation mode 801.
- the normal operation mode is a mode that is normally operated at the installation site, and is hereinafter referred to as a normal operation mode 9001.
- the microcomputer 5 performs internal / external transmission between the air conditioning outdoor unit 2 and the air conditioning indoor unit 3 via the internal / external transmission line 50.
- an inspection facility (not shown) is connected to the internal / external transmission line 50 instead of the air conditioning indoor unit 3, so that the microcomputer 5 is based on the transmission source information transmitted from the inspection facility. Recognizing that the inspection equipment is connected, the operation mode 701 is switched to the inspection operation mode 801.
- the microcomputer 5 stores in the memory 6 that the operation mode 701 at the time of occurrence of the abnormality is the inspection operation mode 801. Later, when analyzing the cause of the abnormality, the power of the abnormality that occurred during the inspection process at the manufacturing site or the abnormality that occurred at the installation site will be revealed, and the analysis work will be easier. In particular, if an abnormality occurs in the inspection process, it is easy to perform a reproduction experiment and narrow down the cause of the abnormality.
- the normal operation mode 901 includes a plurality of control modes 91 1 to 921.
- the stop control mode 911 is control executed while the compressor 111 is stopped.
- the pre-starting pressure equalization control mode 912 is a control for improving the startability by canceling the pressure difference between the high pressure side and the low pressure side before starting the compressor 111.
- the start control mode 913 is control for starting the compressor 111.
- the test operation control mode 914 is a control for confirming the operation after the air conditioner 1 is installed.
- the steady control mode 915 is control for operating the air conditioner 1 in a steady state.
- the oil return control mode 916 is control for forcibly recovering the refrigeration oil retained in the refrigerant circuit 10 to the compressor 111 after performing a cooling operation or a heating operation for a certain period of time.
- the pump down control mode 917 is a control for storing the liquid refrigerant in the container when the operation is stopped to keep the gas refrigerant on the low pressure side of the compressor 111 dry, and prevents liquid back when the compressor 111 is restarted.
- Control mode 918 during stop before restart is control when compressor 111 is stopped in a standby state.
- the pre-defrost control mode 919 is control before the defrost (defrost) control mode 920 is performed, and the post-defrost control 921 is control performed after the defrost control mode 920 ends.
- the defrost control is a control for defrosting the outdoor heat exchanger 113 that is frosted during the heating operation of the air conditioner 1.
- FIG. 3 is a flowchart of the operation mode selection control.
- Microcomputer 5 starts internal / external transmission in step S1.
- the equipment connected to the internal / external transmission line 50 is usually the air-conditioning indoor unit 3, but inspection equipment is connected in the inspection process at the manufacturing site. Therefore, when the internal / external transmission is started, the transmission source information for notifying the identity of the device connected to the internal / external transmission line 50 is transmitted.
- step S2 it is determined whether or not the transmission source information is an inspection facility.
- step S2 If it is determined in step S2 that it is an inspection facility, the process proceeds to step S3, and the inspection operation mode 801 is selected as the operation mode 701. On the other hand, if it is determined No in step S2, the air conditioner indoor unit 3 is connected, so the process proceeds to step S4, and the normal operation mode 901 is selected as the operation mode 701.
- step S5 the microcomputer 5 determines whether there is an abnormality. If an error occurs, in step S6, obtain operation information such as the operation mode that was being executed when the error occurred and the details of the error. In step S7, the operation mode and operation information acquired in step S6 are stored in the memory 6.
- the microcomputer 5 is designed to prevent the compressor 111 from becoming seized due to an internal temperature rise due to an abnormal drop in pressure on the low pressure side due to factors such as forgetting to open the closing valves 118 and 119 and excessive gas shortage. Control is performed to abnormally stop the compressor 111 when the pressure is low, and this is called abnormality confirmation control for low pressure abnormality. On the other hand, in order to prevent an abnormal stop due to a transient decrease in low-pressure side pressure, the compressor 111 is forcibly stopped before an abnormality occurs to determine whether or not it is a transient failure. Low-pressure standby control is also performed, and the number of low-pressure standbys is counted by a low-pressure standby counter (not shown). When the low-pressure standby reaches a predetermined number of times, a low-pressure abnormality occurs. There are multiple conditions for low-pressure standby. Here, only a part is cited.
- step S21 determines whether or not the compressor 111 is operating in step S21.
- step S22 determines whether or not the defrost is OFF.
- the defrost OFF means that the defrost control mode 920 is OFF.
- step S22 If it is determined in step S22 that the defrost is OFF, the process proceeds to step S23, and it is determined whether or not the force has passed 10 minutes or more after the defrost is completed. If it is determined in step S23 that 10 minutes or more have elapsed, the process proceeds to step S24 to determine whether the oil return is OFF.
- the oil return OFF means that the oil return control mode 916 is OFF.
- step S24 If it is determined in step S24 that the oil return is OFF, the process proceeds to step S25, and it is determined whether the pump down operation is OFF.
- Pump-down operation OFF means that pump-down control mode 917 is OFF!
- step S25 If it is determined in step S25 that the pump down operation is OFF, the process proceeds to step S26, and it is determined whether or not the low pressure side pressure Pe is less than 1.2 kgZcm 2 continuously for 10 minutes or more.
- step S26 If it is determined in step S26 that the continuous operation continues for 10 minutes or more, the process proceeds to step S27 to determine whether or not the test run is OFF. Note that the trial run OFF is the trial run control mode. 914 is OFF.
- step S27 If it is determined in step S27 that the test run is OFF, the process proceeds to step S28, and it is determined whether or not the Pe standby counter is 10 times or more.
- step S28 If it is determined in step S28 that the number is 10 times or more, the process proceeds to step S29 to determine that the low pressure is abnormal and output a confirmation signal ON. Even if it is determined in step S27 that the test operation is being performed, the process proceeds to step S29, where the low pressure abnormality is confirmed and a confirmation signal ON is output.
- step S30 determines in step S30 whether the start control is OFF.
- the start control OFF means that the start control mode 913 is OFF.
- step S30 If it is determined in step S30 that the start control is OFF, the process proceeds to step S31, and it is determined whether or not the force has passed for 5 minutes or more after the start control ends. If it is determined in step S31 that 5 minutes or more have elapsed, the process proceeds to step S33 to forcibly stop the compressor 111 and perform low-pressure standby.
- step S30 If it is determined in step S30 that the activation control is not OFF, the process proceeds to step S32, and it is determined whether or not the activation Pe standby counter is 9 or less. If it is determined in step S32 that the number is 9 or less, the process proceeds to step S33 to forcibly stop the compressor 111 and perform low pressure standby. If it is determined in step S32 that it is not 9 or less, the process proceeds to step S29, where it is determined that the low pressure is abnormal, and a confirmation signal ON is output.
- the above is the flow of the abnormality confirmation control of the low pressure abnormality.
- the microcomputer 5 When the microcomputer 5 outputs the abnormality confirmation signal ON, the microcomputer 5 obtains operation information such as the operation mode executed at the time of the abnormality and the abnormality content. Store in memory 6.
- the abnormality confirmation control for low pressure abnormality there are three scenes where the abnormality is confirmed.
- the first scene of error determination is when all the judgments in steps 21 to S28 are Yes.
- the memory 6 stores a steady control mode 915 as an operation mode. Then, it can be seen that this low-pressure abnormality occurred during execution of the steady control mode 915, and it is determined that the abnormality factor is excessive gas shortage.
- Steps S22, S23, S24, S25 so that the force is divided, defrost ⁇ ⁇ 1 ”control mode, 920 It can be seen that the low pressure abnormality is not determined while the post-defrost control mode 921, the oil return control mode 916, and the pump down control mode 917 are being executed. Therefore, if the air conditioner 1 stops abnormally and the details of the abnormality are unknown, reading the operation mode at the time of occurrence of the abnormality from the memory 6 can grasp the abnormality that could not occur in that operation mode, In fact, it is easy to narrow down the cause of an abnormality by excluding the ability to analyze the cause of an abnormality.
- the second scene of the abnormality confirmation is a case where it is determined in step S27 that the trial run is not OFF (trial run control mode 914 is being executed).
- the air conditioner 1 is abnormally stopped due to a low pressure abnormality and the operation mode at the time of occurrence of the abnormality is the trial operation control mode 914, it may be determined that the abnormality factor is forgetting to open the closing valves 118 and 119. .
- the third scene of failure confirmation is when the startup Pe counter becomes 10 or more when the startup control is not OFF (when startup control mode 913 is running).
- the air conditioner 1 is abnormally stopped due to a low pressure abnormality and the operation mode at the time of occurrence of the abnormality is the start control mode 913, it is determined that the low pressure standby is frequently performed (10 times). It's okay.
- HPS is an abbreviation for the high-pressure side pressure switch 71 (see FIG. 1) provided on the discharge side of the compressor 111.
- the air conditioner 1 in order to prevent damage to the equipment due to excessive high pressure rise, if the HPS operates, the air conditioner 1 is abnormally stopped as a high pressure abnormality.
- the high-pressure abnormality is an abnormality that occurs during the operation of the compressor 111.
- the compressor 111 may stop abnormally in the stopped control mode 911 and the HPS may be activated. It is logically not possible for the compressor 111 to rise at a high pressure while the compressor 111 is stopped. Therefore, in this embodiment, the operation mode at the time of HPS operation is stored in the memory 6 to facilitate the determination of HPS failure. That is, if the operation mode at the time of HPS operation is the stop control mode 911, the HPS is defective.
- smoothing capacitor abnormality As an example.
- smooth The capacitor is an electrolytic capacitor (not shown) that is connected in parallel to a DC circuit that converts the output of the AC power source into a DC output, and is provided in the control device 4.
- the abnormality is detected by monitoring the voltage across the terminals of the smoothing capacitor.
- smoothing capacitor abnormalities when the terminals are short-circuited and when the terminals are overvoltaged. The possibility of a ground fault in the compressor 111 is high.
- a short-circuit between terminals of the smoothing capacitor is detected before the compressor 111 is started, and an overvoltage of the smoothing capacitor is detected in the start-up control mode 913 in which the compressor 111 is started.
- the operation mode is stored in the memory 6. That is, if the smoothing capacitor abnormality occurs before the compressor 111 starts, it is a short circuit between terminals, and if it occurs in the start control mode 913, it is caused by an overvoltage between terminals due to the ground fault of the compressor 111. You may judge that there is.
- LPS is an abbreviation for the low pressure side pressure switch 72 (see FIG. 1) provided on the suction side of the compressor 111.
- LPS failure has two phenomena: one is a contact open side failure that occurs when the LPS internal contact is open, and the other is a contact closure that occurs when the LPS internal contact is closed. The side is bad. For this reason, LPS failure alone does not distinguish between contact opening failure and contact closing failure.
- the control device 4 includes a microcomputer 5 and a memory 6.
- Microcomputer 5 is air conditioner 1 manufacturing site Executes the inspection operation mode 801 that operates in the inspection process and the normal operation mode 901 that operates the air conditioner 1 at the installation site, and it is determined as abnormal when the operation state of the air conditioner 1 does not satisfy the predetermined condition. Stop the air conditioner 1 abnormally. Then, when the air conditioner 1 is abnormally stopped, the microcomputer 5 obtains the predetermined operation information acquired until the air conditioner 1 is abnormally stopped, and the operation mode executed when the abnormality of the air conditioner 1 occurs. Is stored in memory 6.
- the force that is an abnormality that occurred during the inspection makes the background at the time of occurrence of the abnormality clear, and makes it easy to narrow down the cause of the abnormality.
- the normal operation mode 901 includes a plurality of control modes 911 to 921.
- the control mode 911 to 921 executed when the abnormality of the air conditioner 1 occurs is stored in the memory 6.
- the analysis target power of abnormalities that cannot occur in the control modes 911 to 921 is also excluded. For this reason, it becomes easy to narrow down abnormal factors.
- the operation of the HPS in the control mode 911 during the stop can be determined to be an HPS failure.
- the LPS failure in the pre-startup pressure equalization control mode 912 can be determined as a LPS contact open side failure.
- the abnormality factor of the electrolytic capacitor terminal voltage in the startup control mode 913 is a ground fault.
- the low pressure abnormality in the trial operation control mode 914 can be determined that the cause of the abnormality is forgetting to open the closing valves 118 and 119.
- the low pressure abnormality in the steady control mode 915 can be determined that the abnormality factor is excessive gas shortage.
- the microcomputer 5 causes the internal / external transmission between the air conditioner outdoor unit 2 of the air conditioner 1 and the air conditioner indoor unit 3 of the air conditioner 1, and the transmission source information transmitted from the air conditioner indoor unit 3 side.
- the air conditioning indoor unit 3 or the inspection equipment is connected to the internal / external transmission line 50 based on
- the operation mode 701 is switched to the inspection operation mode 801, and when the air conditioning indoor unit 3 is connected, the operation mode 701 is changed to the normal operation mode 901. Switch.
- an abnormality in the inspection operation mode 801 it can be reproduced in the inspection process, and it becomes easy to narrow down the cause of the abnormality.
- the present invention is useful for an air conditioning control device because it makes it easy to narrow down abnormal factors when an abnormality occurs in an air conditioner.
Landscapes
- Engineering & Computer Science (AREA)
- Mechanical Engineering (AREA)
- General Engineering & Computer Science (AREA)
- Chemical & Material Sciences (AREA)
- Combustion & Propulsion (AREA)
- Physics & Mathematics (AREA)
- Thermal Sciences (AREA)
- Signal Processing (AREA)
- Fuzzy Systems (AREA)
- Mathematical Physics (AREA)
- Health & Medical Sciences (AREA)
- Biomedical Technology (AREA)
- Air Conditioning Control Device (AREA)
Description
Claims
Priority Applications (4)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
CN2007800257625A CN101490478B (zh) | 2006-07-10 | 2007-07-04 | 空调控制装置 |
AU2007273696A AU2007273696B8 (en) | 2006-07-10 | 2007-07-04 | Air conditioner control device |
US12/306,757 US8033125B2 (en) | 2006-07-10 | 2007-07-04 | Air conditioner control device |
EP07768109.6A EP2042817B1 (en) | 2006-07-10 | 2007-07-04 | Air conditioning control device |
Applications Claiming Priority (2)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
JP2006188964A JP4567637B2 (ja) | 2006-07-10 | 2006-07-10 | 空調制御装置 |
JP2006-188964 | 2006-07-10 |
Publications (1)
Publication Number | Publication Date |
---|---|
WO2008007586A1 true WO2008007586A1 (fr) | 2008-01-17 |
Family
ID=38923148
Family Applications (1)
Application Number | Title | Priority Date | Filing Date |
---|---|---|---|
PCT/JP2007/063339 WO2008007586A1 (fr) | 2006-07-10 | 2007-07-04 | Dispositif de commande de conditionnement d'air |
Country Status (6)
Country | Link |
---|---|
US (1) | US8033125B2 (ja) |
EP (1) | EP2042817B1 (ja) |
JP (1) | JP4567637B2 (ja) |
CN (1) | CN101490478B (ja) |
AU (1) | AU2007273696B8 (ja) |
WO (1) | WO2008007586A1 (ja) |
Cited By (3)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
JP2011191023A (ja) * | 2010-03-16 | 2011-09-29 | Panasonic Corp | 空気調和機 |
EP2239518A3 (en) * | 2009-03-09 | 2014-01-15 | Mitsubishi Electric Corporation | Air-conditioning apparatus |
WO2019082407A1 (ja) * | 2017-10-26 | 2019-05-02 | 株式会社日立産機システム | 異常検出システムおよび異常検出方法 |
Families Citing this family (14)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR101800887B1 (ko) * | 2010-12-16 | 2017-11-23 | 엘지전자 주식회사 | 네트워크 시스템 |
KR101712213B1 (ko) * | 2011-04-22 | 2017-03-03 | 엘지전자 주식회사 | 멀티형 공기조화기 및 그의 제어방법 |
JP5879950B2 (ja) * | 2011-11-21 | 2016-03-08 | ダイキン工業株式会社 | 空気調和機の制御基板 |
KR101955977B1 (ko) * | 2012-01-30 | 2019-03-08 | 엘지전자 주식회사 | 압축기 제어 장치와 방법, 및 이를 포함한 냉장고 |
JP5413480B2 (ja) * | 2012-04-09 | 2014-02-12 | ダイキン工業株式会社 | 空気調和装置 |
AT513855B1 (de) * | 2013-08-29 | 2014-08-15 | Vossloh Kiepe Ges M B H | Verfahren zum Steuern einer Klimaanlage |
JP5693704B2 (ja) * | 2013-12-26 | 2015-04-01 | 三菱電機株式会社 | 空気調和機 |
JP6201872B2 (ja) * | 2014-04-16 | 2017-09-27 | 三菱電機株式会社 | 空気調和機 |
JP6028817B2 (ja) * | 2015-01-30 | 2016-11-24 | ダイキン工業株式会社 | 空気調和装置 |
FR3039636B1 (fr) * | 2015-07-31 | 2017-08-11 | Financiere Oppenot | Installation de climatisation |
CN106247530B (zh) * | 2016-07-29 | 2019-05-21 | 海信(山东)空调有限公司 | 多管制变频一拖多空调自检方法 |
CN107939649B (zh) * | 2017-11-10 | 2019-07-26 | 广东美的暖通设备有限公司 | 多联机系统及其压缩机油量调节方法和调节装置 |
CN110017580B (zh) * | 2019-04-17 | 2021-05-14 | 宁波奥克斯电气股份有限公司 | 风机盘管与冷热源设备模式互锁控制方法、装置及空调器 |
JP2021020572A (ja) * | 2019-07-29 | 2021-02-18 | サンデン・オートモーティブクライメイトシステム株式会社 | 車両用空気調和装置 |
Citations (12)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
JPS55134256A (en) * | 1979-04-03 | 1980-10-18 | Daikin Ind Ltd | Multiichamber air conditioner |
JPS6050351A (ja) * | 1983-08-30 | 1985-03-20 | ダイキン工業株式会社 | 冷凍装置 |
JPH0452466A (ja) * | 1990-06-18 | 1992-02-20 | Daikin Ind Ltd | 冷凍装置及び冷凍装置の運転制御装置 |
JPH0883386A (ja) * | 1994-09-14 | 1996-03-26 | Fenwall Controls Of Japan Ltd | 空調設備制御装置及びアナログ感知器 |
JPH10141743A (ja) * | 1996-10-26 | 1998-05-29 | Samsung Electron Co Ltd | 空気調和機の運転制御装置およびその方法 |
JPH11132578A (ja) * | 1997-10-28 | 1999-05-21 | Matsushita Electric Ind Co Ltd | 冷凍サイクル装置 |
JP2000220833A (ja) * | 1999-01-27 | 2000-08-08 | Matsushita Electric Ind Co Ltd | ガス調理器 |
JP2001004217A (ja) * | 1999-06-24 | 2001-01-12 | Harman Co Ltd | 温度検出式の制御装置 |
JP2001108288A (ja) * | 1999-10-04 | 2001-04-20 | Matsushita Seiko Co Ltd | 換気装置 |
JP2002115920A (ja) * | 2000-10-10 | 2002-04-19 | Daikin Ind Ltd | 冷凍装置 |
JP2004156829A (ja) | 2002-11-06 | 2004-06-03 | Daikin Ind Ltd | 空気調和機 |
JP2004301436A (ja) * | 2003-03-31 | 2004-10-28 | Mitsubishi Electric Corp | 空調機器および空調機管理システム |
Family Cites Families (7)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
JPH05196329A (ja) | 1992-01-16 | 1993-08-06 | Daikin Ind Ltd | 冷凍装置の運転制御装置 |
JPH06221734A (ja) | 1993-01-27 | 1994-08-12 | Sanyo Electric Co Ltd | 空気調和機 |
JP3757504B2 (ja) * | 1996-12-12 | 2006-03-22 | 三菱電機株式会社 | 冷却装置の遠隔監視システム |
JP2002320284A (ja) | 2001-04-24 | 2002-10-31 | Sanyo Electric Co Ltd | 遠隔監視装置及び遠隔監視システム |
JP4179025B2 (ja) * | 2003-04-10 | 2008-11-12 | 三菱電機株式会社 | 電気機器の制御装置 |
JP4052466B2 (ja) * | 2003-09-16 | 2008-02-27 | 日鐵住金建材株式会社 | 補強型先行手摺枠 |
KR100664056B1 (ko) * | 2004-10-26 | 2007-01-03 | 엘지전자 주식회사 | 멀티형 공기조화기의 고장유무 판별장치 및 방법 |
-
2006
- 2006-07-10 JP JP2006188964A patent/JP4567637B2/ja not_active Expired - Fee Related
-
2007
- 2007-07-04 WO PCT/JP2007/063339 patent/WO2008007586A1/ja active Application Filing
- 2007-07-04 US US12/306,757 patent/US8033125B2/en not_active Expired - Fee Related
- 2007-07-04 CN CN2007800257625A patent/CN101490478B/zh not_active Expired - Fee Related
- 2007-07-04 AU AU2007273696A patent/AU2007273696B8/en not_active Ceased
- 2007-07-04 EP EP07768109.6A patent/EP2042817B1/en not_active Not-in-force
Patent Citations (12)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
JPS55134256A (en) * | 1979-04-03 | 1980-10-18 | Daikin Ind Ltd | Multiichamber air conditioner |
JPS6050351A (ja) * | 1983-08-30 | 1985-03-20 | ダイキン工業株式会社 | 冷凍装置 |
JPH0452466A (ja) * | 1990-06-18 | 1992-02-20 | Daikin Ind Ltd | 冷凍装置及び冷凍装置の運転制御装置 |
JPH0883386A (ja) * | 1994-09-14 | 1996-03-26 | Fenwall Controls Of Japan Ltd | 空調設備制御装置及びアナログ感知器 |
JPH10141743A (ja) * | 1996-10-26 | 1998-05-29 | Samsung Electron Co Ltd | 空気調和機の運転制御装置およびその方法 |
JPH11132578A (ja) * | 1997-10-28 | 1999-05-21 | Matsushita Electric Ind Co Ltd | 冷凍サイクル装置 |
JP2000220833A (ja) * | 1999-01-27 | 2000-08-08 | Matsushita Electric Ind Co Ltd | ガス調理器 |
JP2001004217A (ja) * | 1999-06-24 | 2001-01-12 | Harman Co Ltd | 温度検出式の制御装置 |
JP2001108288A (ja) * | 1999-10-04 | 2001-04-20 | Matsushita Seiko Co Ltd | 換気装置 |
JP2002115920A (ja) * | 2000-10-10 | 2002-04-19 | Daikin Ind Ltd | 冷凍装置 |
JP2004156829A (ja) | 2002-11-06 | 2004-06-03 | Daikin Ind Ltd | 空気調和機 |
JP2004301436A (ja) * | 2003-03-31 | 2004-10-28 | Mitsubishi Electric Corp | 空調機器および空調機管理システム |
Non-Patent Citations (1)
Title |
---|
See also references of EP2042817A4 |
Cited By (4)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
EP2239518A3 (en) * | 2009-03-09 | 2014-01-15 | Mitsubishi Electric Corporation | Air-conditioning apparatus |
JP2011191023A (ja) * | 2010-03-16 | 2011-09-29 | Panasonic Corp | 空気調和機 |
WO2019082407A1 (ja) * | 2017-10-26 | 2019-05-02 | 株式会社日立産機システム | 異常検出システムおよび異常検出方法 |
JP2019079356A (ja) * | 2017-10-26 | 2019-05-23 | 株式会社日立産機システム | 異常検出システムおよび異常検出方法 |
Also Published As
Publication number | Publication date |
---|---|
AU2007273696B8 (en) | 2010-07-29 |
EP2042817A1 (en) | 2009-04-01 |
JP4567637B2 (ja) | 2010-10-20 |
AU2007273696A1 (en) | 2008-01-17 |
EP2042817A4 (en) | 2013-04-24 |
US8033125B2 (en) | 2011-10-11 |
CN101490478A (zh) | 2009-07-22 |
AU2007273696B2 (en) | 2010-07-15 |
EP2042817B1 (en) | 2018-02-21 |
JP2008014609A (ja) | 2008-01-24 |
CN101490478B (zh) | 2012-04-18 |
US20090320507A1 (en) | 2009-12-31 |
Similar Documents
Publication | Publication Date | Title |
---|---|---|
JP4567637B2 (ja) | 空調制御装置 | |
JP5976333B2 (ja) | 空気調和装置及び空気調和装置の四方弁制御方法 | |
JP6403887B2 (ja) | 冷凍サイクル装置、遠隔監視システム、遠隔監視装置および異常判定方法 | |
CN109282424B (zh) | 空调器控制方法、空调器控制装置 | |
WO2012077398A1 (ja) | 空気調和機 | |
CN103017295A (zh) | 多联机空调的制冷转制热模式启动方法 | |
JP2014088965A (ja) | 給湯機 | |
CN107560101A (zh) | 一种空调电子膨胀阀的故障检测方法 | |
WO2006009141A1 (ja) | 空気調和装置 | |
CN112303851B (zh) | 用于空调的控制方法及使用其的空调 | |
JP5217531B2 (ja) | 空気調和装置及びその制御方法 | |
JP2008185321A (ja) | 空気調和機 | |
CN115789963A (zh) | 热泵热水机组及其漏水检测方法和检测装置 | |
CN111023440B (zh) | 一种空调低压传感器故障的检测方法、装置及空调器 | |
KR100814956B1 (ko) | 멀티에어컨 및 그의 압축기 제어방법 | |
JP2005249293A (ja) | ヒートポンプ式給湯機の制御装置 | |
JPH0634224A (ja) | 暖冷房機 | |
CN110553344B (zh) | 多联机及其室内机的节流元器件故障判定方法 | |
KR100677282B1 (ko) | 공기조화기의 실외기 제어방법 및 제어장치 | |
CN102384615A (zh) | 容量控制型螺旋式冷冻装置的运转控制方法 | |
WO2008007595A1 (fr) | Dispositif de commande | |
CN117345897A (zh) | 一种两联供四通阀换向异常控制方法 | |
CN115235039A (zh) | 一种四通阀控制方法、装置及存储介质 | |
JPH05223360A (ja) | 空気調和機 | |
KR0172089B1 (ko) | 냉장고 부하구동용 릴레이 접점 불량시의 응급조치방법 |
Legal Events
Date | Code | Title | Description |
---|---|---|---|
WWE | Wipo information: entry into national phase |
Ref document number: 200780025762.5 Country of ref document: CN |
|
121 | Ep: the epo has been informed by wipo that ep was designated in this application |
Ref document number: 07768109 Country of ref document: EP Kind code of ref document: A1 |
|
WWE | Wipo information: entry into national phase |
Ref document number: 12306757 Country of ref document: US |
|
NENP | Non-entry into the national phase |
Ref country code: DE |
|
WWE | Wipo information: entry into national phase |
Ref document number: 2007768109 Country of ref document: EP |
|
WWE | Wipo information: entry into national phase |
Ref document number: 2007273696 Country of ref document: AU |
|
NENP | Non-entry into the national phase |
Ref country code: RU |
|
ENP | Entry into the national phase |
Ref document number: 2007273696 Country of ref document: AU Date of ref document: 20070704 Kind code of ref document: A |