SPEC 49406317 SpecificationSheet
SPEC 49406317 SpecificationSheet
SPEC 49406317 SpecificationSheet
Original Instructions
Topic Page
Summary of Changes 2
Product Line Overview 3
Bulletin 140MP Motor Protection Circuit Breakers 4
Product Overview 4
Group Installation with MPCBs 4
Catalog Number Explanation 5
Product Selection 6
Accessories 7
Specifications 11
MPCB Specifications 11
Application Ratings 12
Accessory Specifications 16
Wiring Diagrams 18
Approximate Dimensions 19
Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors 21
Product Overview 21
Application Diagrams 22
Catalog Number Explanation 24
Product Selection 25
Selection Using Current and Hp/kW Ratings 25
Selection Using Application Ratings 28
Accessories 33
Specifications 40
Approximate Dimensions 52
140MT-C, 140MT-D Devices and Accessories 52
140M-F Devices and Accessories 55
Additional Resources 57
Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Technical Data
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect
all changes.
Topic Page
Updated Cat. No. Explanation for Bulletin 140MT devices 24
Updated Hp ratings for 140MT-C3E-B16, 140MT-D9E-B16, 140MT-D9E-C10, 140MT-D9E-C25, 140MT-D9V-C10, and 140MT-D9V-C25 devices 25
Updated High Inrush Hp ratings for 140MT-D9T-B16, 140MT-D9T-C10, and 140MT-D9T-C25 devices 26
Updated Hp ratings for 140MT-D9N-B16, 140MT-D9N-C10, and 140MT-D9N-C25 devices 27
Updated current ratings for connecting modules 38
Updated connecting module descriptions; added connecting modules for joining 140MT-C and 140MT-D MPCBs to 100S-E08…E38 safety 38
contactors with QJ coils
Removed “Pending” from Bulletin 140MT cULus Listing, UL 60947 application ratings, and Type 2 coordination ratings 40, 43, 44, 45
Product Overview
Bulletin 140MP Motor Protection Circuit Breakers (MPCBs) or Motor Protective Switching Devices (MPSDs) are UL
Listed as Manual Motor Controllers (with approvals for Suitable as Motor Disconnect and Suitable for use in Group
Installation).
Group motor installations eliminate the need for individual branch short circuit protective devices for each motor
circuit, reducing panel space, installation & wiring time, and costs. There is only one Branch Circuit Protective
Device (BCPD) for the "Group".
According to UL 60947-4-1, CSA C22.2 No.60947-4-1, these devices may provide the following control and protection functions.
• Disconnect for Motor Branch Circuit
• Manual Switching (Motor control means)
• Overload Protection (Thermal Protection)
These devices meet requirement of Motor Protective Switching Devices (MPSD) according to IEC 60947-4-1 and Circuit Beaker according to
IEC 60947-2 standard for application outside of North America. These devices provide the following functions.
• Disconnect for Motor Branch Circuit
• Short-circuit Protection (Magnetic Protection)
• Overload Protection (Thermal Protection)
• Manual Switching (Motor control means)
140MP devices provide Trip Class 10A overload protection and phase loss sensitivity protection. These are suitable for single- and three-
phase application.
Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and
other loads to be connected to the same branch-circuit…” The most restrictive part of the conditions specified for Group Installation is the
requirement for the protection of the conductors for each motor circuit.
Figure 1 shows an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”.
Bulletin 140MP Motor Protection Circuit Breakers are UL/CSA Listed for Group Installation: conductors from the BCPD to each motor
must be a minimum of 1/3 the ampacity of the Branch Circuit conductors.
Group Installation
Single motor taps must be 1/3
the ampacity of the branch
circuit conductors Branch Circuit
Conductors
a b c d e
Interrupting Rating/
Bulletin Number Frame Size Function Current Range
Breaking Capacity
Code Description Code Description Code Description Code Description Code Description
140MP Motor Protection A Frame A 3 Normal break Adjustable Thermal/ A 0.10 (example: A16 = 0.16 A)
140MP E
Circuit Breaker Fixed Magnetic MPCB B 1.0 (example: B16 = 1.6 A)
C 10 (example: C16 = 16 A)
Product Selection
Table 1 - Bulletin 140MP MPCB Selection Using Current and Hp/kW Ratings
Max. Short Circuit
Rated Motor Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Current Magnetic
Current (Ie) Adjustment 400V 480V Cat. No.
Trip
[A] Range [A] Current [A] (I ) (group motor) 200V 230V 460V 575V 230V 400/415V 500V 690V
cu
0.16 0.10…0.16 2 100 30 — — — — — 0.02 0.06 0.06 140MP-A3E-A16
0.25 0.16…0.25 3.1 100 30 — — — — — 0.04 0.09 0.09 140MP-A3E-A25
0.4 0.25…0.40 5 100 30 — — — 0.25 0.06 0.09 0.12 0.18 140MP-A3E-A40
0.63 0.40…0.63 7.9 100 30 — — 0.25 0.33 0.09 0.18 0.18 0.25 140MP-A3E-A63
1 0.63…1.0 12.5 100 30 — — 0.5 0.75 0.18 0.25 0.37 0.55 140MP-A3E-B10
1.6 1.0…1.6 20 100 30 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140MP-A3E-B16
2.5 1.6…2.5 31.3 75 30 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140MP-A3E-B25
4 2.5…4.0 50 75 18 1 1 3 3 0.75 1.5 2.2 3 140MP-A3E-B40
6.3 4.0…6.3 78.8 50 18 1.5 2 5 5 1.5 2.2 3 4 140MP-A3E-B63
10 6.3…10 150 50 18 3 3 7.5 10 2.2 4 6.3 7.5 140MP-A3E-C10
12 8.0…12 180 50 18 3 3 7.5 10 3 5.5 6.3 7.5 140MP-A3E-C12
16 10…16 240 15 18 5 5 10 15 4 7.5 10 13 140MP-A3E-C16
20 16…20 300 15 18 5 7.5 15 20 5.5 10 11 17 140MP-A3E-C20
25 20…25 375 15 18 7.5 7.5 20 20 5.5 11 15 22 140MP-A3E-C25
32 25…32 480 15 18 7.5 10 25 30 7.5 15 20 25 140MP-A3E-C32
(1) Horsepower/kW ratings shown are for reference. The final selection of the MPCB/MPSD depends on the actual motor full load current.
Accessories
Table 3 - Auxiliary Contacts
Auxiliary Contacts Pkg.
Description Connection Diagram Cat. No.
N.O N.C Qty.
13 21
1 1 14 22
140MP-A-AFA11
1 0 140MP-A-AFA10
Front-mounted Auxiliary Contact
• No additional space required 10
• 1 and 2-pole 21
0 1 22
140MP-A-AFA01
I >>
2 0 140MP-A-AFA20
1 1 140MP-A-ASA11
Lead Contacts 33 41
34 42 140MP-A-ASA20L
2 0
57 65
1 1 140MP-A-ASAR11
I>>
58 68
• Use compact bus bars with 54 mm
(2.13 in.) spacing
55 65
0 2 140MP-A-ASAR02
I >>
56 66
Screw Adapter
• For screw arrangement of a motor protection circuit breaker
140MP 10 140MP-A-N45
• Hat (DIN) Rail 35 x 7.5 mm (1.4 x 0.3 in.)
• 44 mm (1.7 in.) length
Enclosure
• Up to three padlocks in OFF position 140MP 1
• Protection Class: IP65; UL/CSA Type 12 Black handle 140MP-A-ENN65
Red/Yellow 140MP-A-DCY65
Door Coupling Handle
• Up to three padlocks in OFF position
• Defeatable 140MP 1
• Type 1/3R/12
• IP64
Black 140MP-A-DC65
Coupler
• Coded - Positioning of ON indication Driver with screw 140MP-A-DNC
dependent from mounting orientation of the
140MP 140MP 1
• Uncoded - Positioning of ON indication
Driver without
independent from mounting orientation of 140MP-A-DNUC
coding, with screw
the 140MP
Specifications
MPCB Specifications
Table 9 - General Ratings
Attribute Value
IEC IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
Standards compliance
cULus UL 60947-1, UL 60947-4-1, CSA C22.2, No. 60947-4-1
Global RINA (Marine)
Certifications
Regional CCC, KC, EAC, CE, IEC, cULus, CB Scheme
Rated operating voltage Ue 690V AC
Maximum operating voltage (UL) 600V
Rated Frequency 50/60 Hz
Trip Class 10A
Mechanical 100.000 Cycles
Number of operations
Electrical 100,000 Cycles (0.1…16 A); 50,000 Cycles (20…32 A)
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 690V
Pollution Degree 3
Phase loss sensitivity Yes
Disconnect function per IEC/EN 60947-2 Yes
Resistance to shock per IEC 60068-2-27 25 G/11 ms
Resistance to vibrations per IEC 60068-2-6 5 G /3 … 150 Hz
Mounting DIN Rail (EN 60715)
Group mounting (side by side) up to 40 °C (104 °F)
Minimum distance to other Horizontal 0 mm (0 in.)
units same type Vertical 150 mm (5.9 in.)
Horizontal, up to 400V 0 mm (0 in.)
Minimum distance to Horizontal, up to 690V > 1.5 mm (0.06 in.)
electrical conductive board
Vertical 75 mm (2.96 in.)
Housing IP20
Degree of Protection
Main Terminals IP10
@230V, 400V, 440V, 500V, and 690V See Table 2
Short-circuit ratings @480V and 600V—for motor disconnect
See Table 14
@480V and 600V—for group motor installation
IEC 60947-2 (Circuit breaker) A
Utilization Category
IEC 60947-4-1 (Motor Starter) AC-3
Type of terminals
Application Ratings
Table 14 lists specific application ratings for MPCBs.
Table 14 - UL/CSA Listed Application Ratings, Motor Protection Circuit Breaker Only
UL 60947-4-1 — Manual Motor Controller
Max. Short Circuit Current [kA]
Cat. No. Branch Circuit Protection Motor Disconnect Group Installation
Max. Size per NEC/CEC [A]
480V 600V 480V 600V
140MP-A3E-A16 175 30 5 30 5
140MP-A3E-A25 175 30 5 30 5
140MP-A3E-A40 175 30 5 30 5
140MP-A3E-A63 175 30 5 30 5
140MP-A3E-B10 175 30 5 30 5
140MP-A3E-B16 175 30 5 30 5
140MP-A3E-B25 175 30 5 30 5
140MP-A3E-B40 175 18 5 18 5
140MP-A3E-B63 175 18 5 18 5
140MP-A3E-C10 175 18 5 18 5
140MP-A3E-C12 175 18 5 18 5
140MP-A3E-C16 175 18 5 18 5
140MP-A3E-C20 400 18 5 18 5
140MP-A3E-C25 400 18 5 18 5
140MP-A3E-C32 400 18 5 18 5
Table 15 through Table 20 lists specific application ratings for MPCBs in combination with Bulletin 100-K, 100-C, and 100-E contactors.
Type 1 Coordination—Specified 100-K contactors are suitable for motor group applications when they are used on the load side of the
140MP-A3E Manual Motor Controllers that are specified in Table 15.
Table 15 - Type 1 Application Ratings, 140MP to 100-K Miniature IEC Contactors
SCCR
Manual Motor Controller Contactor (1) Maximum Fuse or Circuit Breaker
480V AC [kA] 600V AC [kA] sized per NEC [A]
140MP-A3E-A16 30 5 175
140MP-A3E-A25 30 5 175
140MP-A3E-A40 30 5 175
140MP-A3E-A63 100-K05 30 5 175
140MP-A3E-B10 100-K09 30 5 175
140MP-A3E-B16 100-K12 30 5 175
140MP-A3E-B25 30 5 175
140MP-A3E-B40 18 — 175
140MP-A3E-B63 18 — 175
100-K09
140MP-A3E-C10 18 — 175
100-K12
140MP-A3E-C12 18 — 175
100-K12
140MP-A3E-C16 18 — 175
(1) May be used with 140MP-A-PEK12 connecting module between 140MP-A3E manual motor controller and 100-K contactor.
Type 1 Coordination—Specified 100-C contactors (without R suffix) are suitable for motor group applications when they are used on the load
side of the specified Manual Motor Controllers.
Table 16 - Type 1 Application Ratings, 140MP to 100-C IEC Contactors
SCCR
Manual Motor Controller Contactor (1) Maximum Fuse or Circuit
480V AC [kA] 600V AC [kA] Breaker sized per NEC [A]
140MP-A3E-A16 30 5 175
140MP-A3E-A25 30 5 175
140MP-A3E-A40 30 5 175
140MP-A3E-A63 30 5 175
100-C09
140MP-A3E-B10 100-C12 30 5 175
140MP-A3E-B16 100-C16 30 5 175
100-C23
140MP-A3E-B25 30 5 175
140MP-A3E-B40 18 5 175
140MP-A3E-B63 18 5 175
140MP-A3E-C10 18 5 175
100-C12
140MP-A3E-C12 100-C16 18 5 175
100-C23
140MP-A3E-C16 (2) 100-C16, 100-C23 18 5 175
100-C23
140MP-A3E-C20 100-C30 18 5 400
100-C37
140MP-A3E-C25 (3) 100-C23 18 — 400
140MP-A3E-C25 (3) 100-C30, 100-C37 18 5 400
140MP-A3E-C32 (4) 100-C30, 100-C37 18 5 400
(1) 140MP-A-PEC23 connection modules may be used with 100-C09…-C23 up to 24 A.
(2) Limited to 15.5 FLA maximum when used in a 365 x 235 x 140 mm (14.4 x 9.3 x 5.5 in.) (200%) or larger enclosure. Limited to 14.5 FLA maximum when used in 115 x 290 x 180 mm
(4.5 x 11.4 x 7.1 in.) (150%) minimum sized enclosure.
(3) Minimum enclosure size is 170 x 670 x 235 mm (6.7 x 26.4 x 9.3 in.) (250%) at full load current. If end use current is 22.5 FLA or less, may be used in an enclosure as small as
115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%).
(4) May be used at 30.8 FLA maximum when used ambient temperature of 40 °C (104 °F) maximum. May be used up to 29 FLA when used in a 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%)
minimum size enclosure.
Table 17 - Type 2 Coordination Ratings per IEC 60947-4-1, 140MP to 100-C IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, IEC 60947-4-1
Cat. No. 400/415V
Max. Short Circuit Current [kA] For Use With Contactor Cat. No.
140MP-A3E-A16 50 100-C09
140MP-A3E-A25 50 100-C09
140MP-A3E-A40 50 100-C09
140MP-A3E-A63 50 100-C09
140MP-A3E-B10 50 100-C09
140MP-A3E-B16 50 100-C09
140MP-A3E-B25 50 100-C09
140MP-A3E-B40 50 100-C09
140MP-A3E-B63 50 100-C09
140MP-A3E-C10 50 100-C09
140MP-A3E-C12 25 100-C12
140MP-A3E-C16 10 100-C23
140MP-A3E-C20 10 100-C30
140MP-A3E-C25 10 100-C30
140MP-A3E-C32 10 100-C30
Table 18 - Type 2 Coordination Ratings per IEC 60947-4-1, 140MP to 100-E IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, IEC 60947-4-1
Cat. No. 400V
Max. Short Circuit Current [kA] Minimum Contactor Size
140MP-A3E-A16 50 100-E09
140MP-A3E-A25 50 100-E09
140MP-A3E-A40 50 100-E09
140MP-A3E-A63 50 100-E09
140MP-A3E-B10 50 100-E09
140MP-A3E-B16 50 100-E09
140MP-A3E-B25 50 100-E09
140MP-A3E-B40 50 100-E26
140MP-A3E-B63 50 100-E26
140MP-A3E-C10 50 100-E26
140MP-A3E-C12 25 100-E26
140MP-A3E-C16 16 100-E26
140MP-A3E-C20 10 100-E30
140MP-A3E-C25 10 100-E30
140MP-A3E-C32 10 100-E38
Table 19 - Type 2 Coordination Ratings per UL 60947-4-1, 140MP to 100-C IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, UL 60947-4-1
Max. Fuse or Circuit Breaker Size
Cat. No. Contactor (1) 480V 600V per NEC [A]
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]
140MP-A3E-A16 30 5 175
140MP-A3E-A25 30 5 175
100-C09
140MP-A3E-A40 100-C12 30 5 175
140MP-A3E-A63 100-C16 30 5 175
100-C23
140MP-A3E-B10 30 5 175
140MP-A3E-B16 30 5 175
100-C12
140MP-A3E-B25 100-C16 30 5 175
100-C23
100-C16
140MP-A3E-B40 18 5 175
100-C23
140MP-A3E-B63 100-C23 18 5 175
140MP-A3E-C10 18 5 175
140MP-A3E-C12 18 5 175
140MP-A3E-C16 (2) 100-C30 18 5 175
140MP-A3E-C20 100-C37 18 5 400
140MP-A3E-C25 (3) 18 5 400
140MP-A3E-C32 (4) 18 5 400
(1) 140MP-A-PEC23 connection modules may be used with 100-C09…-C23 up to 24 A.
(2) Limited to 15.5 FLA maximum when used in a 365 x 235 x 140 mm (14.4 x 9.3 x 5.5 in.) (200%) or larger enclosure.
Limited to 14.5 FLA maximum when used in 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%) minimum sized enclosure.
(3) Minimum enclosure size is 170 x 670 x 235 mm (6.7 x 26.4 x 9.3 in.) (250%) at full load current.
If end use current is 22.5 FLA or less, may be used in an enclosure as small as 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%).
(4) May be used at 30.8 FLA maximum when used ambient temperature of 40 °C (104 °F) maximum.
May be used up to 29 FLA when used in a 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%) minimum size enclosure.
Table 20 - Type 2 Coordination Ratings per UL 60947-4-1, 140MP to 100-E IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, UL 60947-4-1
Max. Fuse or Circuit 480V 600V
Cat. No. Breaker per NEC Max. Short-circuit Current Minimum Contactor Size Max. Short-circuit Current Minimum Contactor Size
[kA] [kA]
140MP-A3E-A16 175 30 100-E09 5 100-E09
140MP-A3E-A25 175 30 100-E09 5 100-E09
140MP-A3E-A40 175 30 100-E09 5 100-E09
140MP-A3E-A63 175 30 100-E09 5 100-E09
140MP-A3E-B10 175 30 100-E09 5 100-E09
140MP-A3E-B16 175 30 100-E09 5 100-E09
140MP-A3E-B25 175 30 100-E16 5 100-E16
140MP-A3E-B40 175 18 100-E26 5 100-E16
140MP-A3E-B63 175 18 100-E26 5 100-E26
140MP-A3E-C10 175 18 100-E26 5 100-E30
140MP-A3E-C12 175 18 100-E26 5 100-E30
140MP-A3E-C16 175 18 100-E26 5 100-E40
140MP-A3E-C20 400 18 100-E26 5 100-E40
140MP-A3E-C25 400 18 100-E30 5 100-E40
140MP-A3E-C32 400 18 100-E38 5 100-E40
Accessory Specifications
Table 21 - Auxiliary Contact, Signaling Contact, and Short-circuit Signaling Contact Specifications
Side-mounted Auxiliary, Signaling,
Attribute Front-mounted Auxiliary Contacts
and Short-circuit Signaling Contacts
IEC IEC/EN 60947–1, IEC/EN 60947-5-1 IEC/EN 60947–1, IEC/EN 60947-5-1
Standards compliance
UL/cULus UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1 UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1
Rated operating voltage Ue 690V AC/600V DC 250V AC/250V DC
Conventional free-air thermal current Ith 6A 5A
Rated Frequency 50/60 Hz 50/60 Hz
Rated impulse withstand voltage Uimp 6 kV 6 kV
Rated insulation voltage Ui 690V AC 250V AC
Pollution Degree 3 3
Operation -25 … +60 °C (-13…+140 °F) -25 … +60 °C (-13…+140 °F)
Ambient air temperature
Storage -50 … +80 °C (-58…+176 °F) -50 … +80 °C (-58…+176 °F)
Resistance to shock per IEC 60068-2-27 25 G/11 ms 25 G/11 ms
Resistance to vibrations per IEC 60068-2-6 5 G/3 … 150 Hz 5 G/3 … 150 Hz
24V, 120V 6A 3A
Rated operational current Ie 240V 4A 1.5 A
AC-15 per IEC/EN 60947-5-1 for
utilization category 400V 3A —
440V, 690V 1A —
24V 2A 1A
Rated operational current IeDC- 125V 0.55 A 0.27 A
13 per IEC/EN 60947-5-1 for
utilization category 250V 0.27 A 0.11 A
440V, 600V 0.15 A —
Minimum switching capacity 17V DC/5 mA 17V DC/5 mA
Short-circuit protective device (N.O, N.C) 10 A Type gG 10 A Type gG
Duty time 100% 100%
Mounting Right side Front
Mechanical
Number of operations 50,000 cycles 50,000 cycles
Electrical
Contact utilization characteristics according to UL/CSA
Rated operating voltage Ue per UL/CSA 600V AC/600V DC 250V AC/250V DC
Pilot duty B600, Q600 B300, R300
AC thermal rated current 5A 5A
making 3600 3600 VA
AC maximum volt-ampere
breaking 360 360 VA
DC thermal rated current 2.5 A 2.5 A
making
DC maximum volt-ampere 69 VA 28 VA
breaking
Connecting characteristics Table 24 Table 24
Wiring Diagrams
Figure 2 illustrates basic wiring for the 140MP MPCB and accessories.
C1 21 31 41 55 65 Right-side-mounted Trip
Signaling Contact
140MP-A-ASAR…
C2 22 32 42 56 66
D1 13 23 33 43 57 67
Undervoltage Release
140MP-A-UX… U<
D2 1 L1 3 L2 5 L3
14 24 34 44 58 68
13 21 33 41 57 65
14 22 34 42 58 66
Approximate Dimensions
Dimensions are in millimeters (inches) and are not intended for manufacturing purposes.
90°
122
(4.8)
110
(4.33)
17.5 (0.69)
122
(4.8)
110
(4.33)
1.65 37.0
(0.1) (1.46)
90
(3.54) 57.7
45.0 (2.27)
27.4 (1.77)
(1.08)
14 (0.55) 14 (0.55)
45 (1.77)
70 (2.76)
75
(2.95)
1.65
(0.1) 37.0
(1.46)
45.0 57.25
26.93 (1.77) (2.27)
(1.06) 96.8
(3.81)
14 (0.55) 14 (0.55)
45 (1.77)
Product Overview
Bulletin 140MT Motor Protection Circuit Breakers (MPCBs) or Motor Protective
Switching Devices (MPSDs) are UL Listed as Manual, Self-Protected Combination Motor
Controllers (Type E) and Manual Motor Controllers (with approvals for Suitable as Motor
Disconnect and Suitable for use in Group Installation).
According to UL 60947-4-1, CSA C22.2 No.60947-4-1, these devices may provide the following control and protection functions.
• Disconnect for motor branch circuit
• Short-circuit Protection (magnetic protection)
• Overload protection (thermal protection)
• Manual switching (motor control means)
Group motor installations eliminate the need for individual branch short-circuit protective devices for each motor circuit, reducing panel
space, installation and wiring time, and costs. There is only one Branch Circuit Protective Device (BCPD) for the "Group". Bulletin 140MT
devices are also UL Listed for Tap Conductor protection in group installations, which helps reduce conductor sizing.
According to UL 60947-4-1, CSA C22.2 No.60947-4-1, these devices these devices certified for group motor installation may provide the
following control and protection functions.
• Disconnect for motor branch circuit
• Overload protection (thermal protection)
• Manual switching (motor control means)
Bulletin 140MT devices meet requirement of Motor Protective Switching Devices (MPSD) according to IEC 60947-4-1 and Circuit Beaker
according to IEC 60947-2 standard for application outside of North America. These devices provide the following functions.
• Disconnect for motor branch circuit
• Short-circuit Protection (magnetic protection)
• Overload protection (thermal protection)
• Manual switching (motor control means)
Bulletin 140MT devices provide Trip Class 10 overload protection and phase loss sensitivity protection. These are suitable for single- and
three- phase applications.
Cat. No. 140MT-D9V devices can also be applied at the output of a variable frequency drive (VFD) in multi-motor applications.
Application Diagrams
Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and
other loads to be connected to the same branch-circuit…”. The most restrictive part of the conditions specified for Group Installation is the
requirement for the protection of the conductors for each motor circuit. In the U.S. NEC for 2002, a new rule for the conductor sizing was
added for devices that are listed and marked “Suitable for use as Tap Conductor Protection”.
Figure 8 shows an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”.
Bulletin 140MT Motor Protection Circuit Breakers UL/CSA Listed for Group Installation: conductors from the BCPD to each motor must be a
minimum of 1/3 the ampacity of the Branch Circuit conductors.
Bulletin 140MT Motor Protection Circuit Breakers UL/CSA Listed for Tap conductor Protection in Group Installations: conductors from the
BCPD to manual motor controller listed as “…Tap Conductor Protection…” must be minimum of 1/10 the rating or setting of the BCPD.
Conductors from the controller to the motor must be 125% of the motor FLA.
Fuses or
Circuit Breaker
Tap Conductor Protection in Group
Group Installation Installation:
Single motor taps must Conductors from BCPD to manual motor
be 1/3 the ampacity of controller listed as “…Tap Conductor
the branch circuit Branch Circuit Protection…” must be minimum of 1/10 the
conductors Conductors rating or setting of the BCPD
Bulletin 140MT Motor Protection Circuit Breakers (MPCBs) are UL/CSA Listed as Type E Manual Self-Protected Combination Motor Controllers
or UL/CSA Listed as Circuit Breakers. These UL/CSA Listings allow the Bulletin 140MT MPCBs to provide the branch-circuit, short-circuit
protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the
protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream
protective device. Figure 9 shows an example that illustrates installations involving multiple motors, each with its own branch-circuit
protection (BCPD).
a b c d e
Current Rating/ Interrupting Rating/
Bulletin Number Function Current Range
Frame Size Breaking Capacity
Code Description Code Description Code Description Code Description Code Description
140MT Motor Protective C 32 A, Frame C 3 Normal break Adjustable Thermal/Fixed A 0.10 (example: A16 = 0.16 A)
140MT Switching E Magnetic (14 x In) MPCB
Device (Thermal) D 40 A, Frame D 9 High break B 1.0 (example: B16 = 1.6 A)
N Fixed Magnetic (14 x In) MCP C 10 (example: C16 = 16 A)
Adjustable Thermal/Fixed
T Magnetic (18…22 x In) MPCB
Fixed Magnetic (application at
V output of VFD multi-motor)
F-Frame Devices
140M - F 8 E - C10
a b c d e
a b c d e
Current Rating/ Interrupting Rating/
Bulletin Number Function Current Range
Frame Size Breaking Capacity
Code Description Code Description Code Description Code Description Code Description
140M Motor Protection F 45 A, Frame F 8 High break Adjustable Thermal/Fixed C 10 (example: C16 = 16 A)
140M E Magnetic (14 x In) MPCB
Circuit Breaker)
N Fixed Magnetic (14 x In) MCP
Adjustable Thermal/Fixed
T Magnetic (18…22 x In) MPCB
Product Selection
Selection Using Current and Hp/kW Ratings
Table 27 - Motor Protective Switching Devices
Max Short-circuit
Rated Motor Current Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Adjustment Magnetic Trip Cat. No.
Current (Ie) [A] Range [A] Current [A] 400V 480V
(Icu) (group motor) 200V 230V 460V 575V 230V 400/415V 500V 690V
Motor Circuit Protectors (Cat. No. 140MT-D9N, 140M-F8N) do not provide thermal protection for themselves nor for downstream
components. You must install a separate protective device against thermal overload, such as an overload relay as part of a
starter combination. In applications that use these devices as the short-circuit protection device of heavy-duty starting motors,
the rated operational current Ie of the devices must be over-sized using the factors in Table 30.
Table 31 - UL/CSA Listed Application Ratings, Motor Protective Switching Devices (Continued)
UL 60947-4-1 Self-Protected (Type E)
UL 60947-4-1 — Manual Motor Controller Combination Motor Controller
Max. Fuse or Max Short-circuit Current [kA] Cat. No.
Circuit Max Short-circuit Current [kA]
Group Motor Installation Motor Disconnect Tap Conductor Protection
Breaker per
NEC [A] 480V 600V 480V 600V 480Y/277V(1) 600Y/347V(1) 480Y/277V(1) 600Y/347V(1)
450 30 — 30 — 30 — 30 — 140MT-D9V-C40(2)
D-Frame, Adjustable Thermal/Fixed Magnetic (18…22 x In)
450 65 50 65 50 65 50 65 50 140MT-D9T-A16
450 65 50 65 50 65 50 65 50 140MT-D9T-A25
450 65 50 65 50 65 50 65 50 140MT-D9T-A40
450 65 50 65 50 65 50 65 50 140MT-D9T-A63
450 65 50 65 50 65 50 65 50 140MT-D9T-B10
450 65 50 65 50 65 50 65 50 140MT-D9T-B16
450 65 30 65 30 65 30 65 30 140MT-D9T-B25
450 65 30 65 30 65 30 65 30 140MT-D9T-B40
450 65 30 65 30 65 30 65 30 140MT-D9T-B63
450 65 30 65 30 65 30 65 30 140MT-D9T-C10
450 65 30 65 30 65 30 65 — 140MT-D9T-C16
450 65 30 65 30 65 — 65 — 140MT-D9T-C20
450 50 30 50 18 50 — 50 — 140MT-D9T-C25
F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)
600 65 30 65 30 65 30 65 30 140M-F8E-C10
600 65 30 65 30 65 30 65 30 140M-F8E-C16
600 65 30 65 30 65 30 65 30 140M-F8E-C20
600 65 30 65 30 65 30 65 30 140M-F8E-C25
600 65 30 65 30 65 30 65 30 140M-F8E-C32
600 65 18 65 18 65 — 65 — 140M-F8E-C45
F-Frame, Adjustable Thermal/Fixed Magnetic (16…22 x In)
600 65 30 65 30 65 30 65 30 140M-F8T-C25
600 65 18 65 18 65 18 65 18 140M-F8T-C32
(1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.
(2) Suitable for continuous operation at 90% current rating at 480V only if used in a minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).
Accessories
Table 34 - Auxiliary Contacts
Operator Position(1)
OFF ON Tripped Term. Contact Connection
Description For Use With Cat. No.
No. Description Diagram(2)
140MT-C, D
140UT-D 140MT-C-AFA10
O X O 13-14 N.O. Aux
140M-F 140M-C-AFA10
140M/MT Operator
O O X 27-28 18 28
(short-circuit)
N.O. Trip
O O X 57-58 (short-circuit
57 67
and overload) 140M-C-ASAR10M10
I>>
N.O. Trip
O O X 67-68 58 68
(short-circuit)
N.O. Trip
O O X 57-58 (short-circuit
Right-Side Mounted Trip and overload) 57 65
140M-C-ASAR10M01
Contact I>>
N.C. Trip
• 2-pole X X O 65-66 (short-circuit)
58 66
O O X 67-68 56 68
• A right-side mounted (short-circuit)
auxiliary contact may be N.C. Trip
tandem mounted on top of X X O 55-56 (short-circuit
this trip contact and overload) 55 65
140M-C-ASAR01M01
I >>
N.C. Trip
X X O 65-66 56 66
(short-circuit)
N.O. Trip
O O X 77-78 (short-circuit) 77 65
140M-C-ASAM11
N.C. Trip I >>
X X O 65-66 (short-circuit) 78 66
140M/MT Operator
140M/MT Operator
140M/MT Operator
140MT-C, D 140MT-C-CA
Anti-Tamper Shield
• Provides protection against inadvertent adjustment of the current setting
• Must be ordered in multiples of 10 (10 pieces/package)
140M-F 140M-C-CA
Blue 140MT-C-KB
Lockable Twist Knob
Black 140MT-C, D 140MT-C-KN
• For one padlock 4…6 mm (3/16 in.) diameter shackle 140UT- D
• Can be locked in OFF position Red/Yellow 140MT-C-KRY
Black 140M-C-KN1
Lockable Twist Knob
• For one padlock 5 mm (3/16 in.) diameter shackle 140M-F
• Can be locked in OFF position Red/Yellow 140M-C-KRY1
140MT-C-KB
Locking Tag 140MT-C-KN 140MT-C-M3
• Padlock attachment to the lockable handles 140MT-C-KRY
• Up to three padlocks 4…8 mm (5/16 in.) diameter shackle 140M-C-KN1 140M-C-M3
140M- C-KRY1
140MT-SB, 140MT-S1
140MT-SY
12 in. (30.48 cm)
140M-SB, 140M-S1
Extension Shaft 140M-SY
• Cut to required length for mounting depth (front of DIN Rail to front of enclosure
door) 140MT-SB, 140MT-S2
140MT-SY
21 in. (53.34 cm)
140M-SB, 140M-S2
140M-SY
Coupler
140M-F 140M-C-DNC
• Included with Cat. Nos. 140M-C-DN66 and 140M-C-DRY66
140MT-C, D
Screw Adapter 140UT- D 140MT-C-N45
• For screw arrangement of a motor protection circuit breaker
• Must be ordered in multiples of 10 (10 pieces/pkg) 140M-F 140M-C-N45
140MT-C, -D 140MT-C-WSN
Terminal Cover
• For covering of unused compact bus bar terminals IP2X finger protection
• Must be ordered in multiples of 10
• 10 pieces/pkg
140M-F 140M-F-WS
Specifications
Table 41 - General Data
Attribute 140MT-C 140MT-D 140M-F
IEC IEC/EN 60947–2, IEC/EN 60947-4-1
Standards compliance
cULus UL 60947-4-1, CSA C22.2, No. 60947-4-1
Certifications Regional CCC, EAC, CE, cULus Listed, IEC, CB Scheme cULus Listed, CCC, EAC, CE
IEC [V] 690
Rated Insulation Voltage Ui
UL/CSA [V] 600
Pollution degree 3
Rated Impulse Withstand Main circuits Uimp/Overvoltage Category 6 kV/III, 8 kV (Disconnect)
Voltage Uimp
Auxiliary circuits Uimp /Overvoltage Category 6 kV/III
Rated Frequency [Hz] 45-65
IEC 60947-2 (Circuit breaker) A
Utilization Category
IEC 60947-4-1 (Motor starter) AC-3
Mechanical [operations] 100,000 30,000
Life Span
Electrical (Ie max.) [operations] 100,000 30,000
Switching Frequency [operations/hour] max. 25
Storage [ °C ( °F)] -40…+85 (-40…185)
Ambient Temperature
Operation [ °C ( °F)] -25…+70 (-13…158)
Climatic resistance Operating Humidity/Moisture heat (60068-2-3) 5…95% Non-condensing
Site Altitude [m] to 2000 N.N. (6561 ft)
Protection Class IP2X from all directions
ON 15 G/11 ms
Resistance to Shock, Transport (60068-2-27)
OFF 30 G/11 ms
Resistance to Vibration, Operation (60068-2-6) 5G
up to 40 °C (104 °F) ambient temperature [A] 0.1…32 0.63…40 6.3…45
Rated Thermal Current Ith
up to 60 °C (140 °F) ambient temperature [A] 0.1…32 0.63…40 6.3…45
Rated Supply Current Ie [A] 0.1…32 0.63…40 6.3…45
40 °C (104 °F) [A] no reduction
Dependence on 50 °C (122 °F) [A] no reduction
Temperature 60 °C (140 °F) [A] no reduction
70 °C (158 °F) [A] 15% current reduction of the upper rated current Ie
IEC 60947-4-1 Motor protection
Overload Protection Characteristics (except Cat. Nos. 140MT-D9N, 140M-F9N)
Ambient Temperature Compensation [ °C ( °F)] -25…+60 (-13…+140)
Phase-loss Protection Differential release
Trip class 10 (except Cat. Nos. 140MT-D9N, 140M-F8N) fixed setting
Magnetic Release fixed setting
for E, N Version [A] 14 x Ie max.(1) 13 x Ie max
Release current (±20%) for E, N Version C36, C40 [A] 12 x Ie max.(1) —
for T Version [A] 18…22 x Ie max.(2)
Total Power loss Pv Circuit Breaker at rated load/ [W] 4…11 4…14 7…22
operating temp.
Main Disconnect Switch Application Yes, with accessories
140MT-D…C36, -C40: Suitable for continuous operation at 90% current rating at 480V only if used in a
minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).
Application Conditions For utilization outside North America, assemblies (of products) shall comply to the IEC 61439-1 requirements
140M and 140MT manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive
or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments.
(1) Ie max. = maximum values of setting ranges fixed magnetic setting for 140MT-D9V; see ratings.
(2) Ie max. = maximum values of setting ranges; see ratings.
Type of terminals
Screw Clamp up to 16 A, M4 Screw Clamp greater than 16 A, M4
Connection Screw Pozidriv No.2/Blade No.3 Pozidriv No.2/Blade No.3 Pozidriv No.2/Blade No.3
2 2
1 1…6 mm 1.5…10 mm 2.5…25 mm2
Solid or stranded 1…2.5 mm2 1.5…4 mm2
2 2.5…25 mm2
2.5…6 mm2 4…10 mm2
1 1…6 mm2 1.5…10 mm2 2.5…25 mm2
Flexible with
ferrule (end sleeve) 1…2.5 mm2 1.5…4 mm2
2 2.5…25 mm2
2.5…4 mm2 4…10 mm2
Wiring
1 1.5…6 mm2 2.5…10 mm2 16…25 mm2
Finely stranded 1.5…4 mm2 2.5…6 mm2
2 16…25 mm2
2.5…6 mm2 4…10 mm2
Cross section per 1 No. 14…10 AWG No. 14…8 AWG No.14…8
UL/CSA solid, No. 14…10 AWG
stranded 2 No. 14…10 AWG No.14…8
No. 12…8 AWG
Stripping length 10 mm (0.39 in.) 10 mm (0.39 in.) 10 mm (0.39 in.)
Tightening torques [N•m]/[lb•in] 2…2.5/18…22 2…2.5/18…22 3…3.5/27…30
Combination Ratings
Table 45 - UL 60947 Application Ratings, MCPs with Bulletin 100-C IEC Contactors
UL 60947-4-1 Manual Motor Controller
Group Motor Installation Motor Disconnect
Cat. No. Max. Fuse or Circuit Minimum Contactor Max Short-circuit Current [kA] Max Short-circuit Current [kA]
Breaker per NEC [A] Size
480V 600V 480V 600V
D-Frame, Motor Circuit Protectors, Fixed Magnetic (14 x In)
140MT-D9N-A16 450 100-C09 65 50 65 50
140MT-D9N-A25 450 100-C09 65 50 65 50
140MT-D9N-A40 450 100-C09 65 50 65 50
140MT-D9N-A63 450 100-C09 65 50 65 50
140MT-D9N-B10 450 100-C09 65 50 65 50
140MT-D9N-B16 450 100-C09 65 50 65 50
140MT-D9N-B25 450 100-C09 65 30 65 30
140MT-D9N-B40 450 100-C09 65 30 65 30
140MT-D9N-B63 450 100-C09 65 30 65 30
140MT-D9N-C10 450 100-C09 65 30 65 30
140MT-D9N-C16 450 100-C12 65 30 65 30
140MT-D9N-C20 450 100-C23 65 30 65 30
140MT-D9N-C25 450 100-C23 50 30 50 30
140MT-D9N-C29 450 100-C30 50 30 50 30
140MT-D9N-C32 450 100-C37 50 30 30 18
140MT-D9N-C36 450 100-C37 30 30 30 18
140MT-D9N-C40 450 100-C37 30 30 30 18
F-Frame, Motor Circuit Protectors, Fixed Magnetic (13 x In)
140M-F8N-C25 600 100-C23 65 30 65 30
140M-F8N-C32 600 100-C30 65 30 65 30
140M-F8N-C45 600 100-C37 65 18 65 18
Table 46 - Type 2 Coordination Ratings, MPSDs with Bulletin 100-C IEC Contactors
Cat. No. 400V 480V 600V
Standard Motor High Inrush Motor Circuit Max Short-circuit Minimum Max Short-circuit Minimum Max Short-circuit Minimum
Protection Motor Protection Protection Current [kA] Contactor Size Current [kA] Contactor Size Current [kA] Contactor Size
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-C3E-A16 — — 100 100-C09 — — — —
140MT-C3E-A25 — — 100 100-C09 — — — —
140MT-C3E-A40 — — 100 100-C09 — — — —
140MT-C3E-A63 — — 100 100-C09 — — — —
140MT-C3E-B10 — — 100 100-C09 — — — —
140MT-C3E-B16 — — 100 100-C09 — — — —
140MT-C3E-B25 — — 65 100-C23 — — — —
140MT-C3E-B40 — — 65 100-C23 — — — —
140MT-C3E-B63 — — 65 100-C23 — — — —
140MT-C3E-C10 — — 65 100-C23 — — — —
140MT-C3E-C16 — — 50 100-C30 — — — —
140MT-C3E-C20 — — 50 100-C30 — — — —
140MT-C3E-C25 — — 15 100-C30 — — — —
140MT-C3E-C29 — — 15 100-C30 — — — —
140MT-C3E-C32 — — 15 100-C30 — — — —
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-D9E-A63 — — 100 100-C09 — — — —
140MT-D9E-B10 140MT-D9T-A63 140MT-D9N-B10 100 100-C09 — — — —
140MT-D9E-B16 140MT-D9T-B10 140MT-D9N-B16 100 100-C09 — — — —
140MT-D9E-B25 140MT-D9T-B16 140MT-D9N-B25 100 100-C09 — — — —
140MT-D9E-B40 140MT-D9T-B25 140MT-D9N-B40 65 100-C09 — — — —
140MT-D9E-B63 140MT-D9T-B40 140MT-D9N-B63 65 100-C09 — — — —
140MT-D9E-C10 140MT-D9T-B63 140MT-D9N-C10 65 100-C09 — — — —
140MT-D9E-C16 140MT-D9T-C10 140MT-D9N-C16 65 100-C23 — — — —
140MT-D9E-C20 140MT-D9T-C16 140MT-D9N-C20 65 100-C23 — — — —
140MT-D9E-C25 140MT-D9T-C20 140MT-D9N-C25 65 100-C23 — — — —
140MT-D9E-C29 140MT-D9T-C25 140MT-D9N-C29 65 100-C30 — — — —
140MT-D9E-C32 140MT-D9T-C29 140MT-D9N-C32 65 100-C30/C37 — — — —
140MT-D9E-C36 140MT-D9T-C32 — 65 100-C30/C37 — — — —
140MT-D9E-C40 140MT-D9T-C36 140MT-D9N-C40 65 100-C30/C37 — — — —
F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)
140M-F8E-C10 — — 100 100-C09 65 100-C09 30 100-C30
140M-F8E-C16 — — 100 100-C12 65 100-C12 30 100-C30
140M-F8E-C20 — — 100 100-C23 65 100-C23 30 100-C30
140M-F8E-C25 — 140M-F8N-C25 100 100-C30 65 100-C30 30 100-C30
140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 100 100-C30 65 100-C30 30 100-C30
140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 100 100-C37 65 100-C37 10 100-C37
Accessory Specifications
Table 48 - Auxiliary Contact Specifications—For 140MT-C… and 140MT-D… Devices
Front-mounted Auxiliary Contacts Right Side-mounted Auxiliary Contacts
Attribute Cat. Nos. 140MT-C-AFA, -AFAR/ -AFAR10M10 Cat. No. 140MT-C-ASA
at 40 °C (104 °F) ambient temperature [A] 5 10
Rated Thermal Current Ith
at 60 °C (140 °F) ambient temperature [A] 4 6
Back-up Fuses gG, gL [A] 10 10
General Use current [A] 5 10
IEC [V] 250 690
Rated insulation voltage Ui
UL/CSA [V] 240 600
AC B300 A600
Contact rating code designation (UL/CSA)
DC R300 Q600
24V [A] 4 6
120V [A] 3 5
AC-15 240V [A] 1.5 3
415V [A] — 2
690V [A] — 1
Rated Supply Current Ie
24V [A] 1.2 2
125V [A] 0.22 0.55
DC-13 250V [A] 0.11 0.27
400V [A] — 0.15
500V [A] — 0.13
Type of Terminals
Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3
Flexible with insulated ferrule 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.5…2.5 mm2/No. 18…14 AWG
Flexible 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Stranded per UL/CSA 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Solid 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.5…2.5 mm2/No. 18…14 AWG
Conductor steps Max 2 conductor steps allowed Max 2 conductor steps allowed
Tightening torque 1…1.2 N•m/8.9…10.6 lb•in 1…1.2 N•m/8.9…10.6 lb•in1…1.2
Type of Terminals
Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3
1 conductor 0.5…1.5 mm2 0.5…2.5 mm2
Flexible with insulated ferrule
2 conductors 0.75…1.5 mm2 0.75…2.5 mm2
Stranded per UL/CSA 1 or 2 conductors 0.75…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Solid 1 or 2 conductors 0.75…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Tightening torque 1.2…1.5 N•m/10.6…13 lb•in 1.2…1.5 N•m/10.6…13 lb•in
Table 50 - Undervoltage and Shunt Trip Specifications—For 140MT-C… and 140MT-D… Devices
Undervoltage Trip for Left-side Mounting Shunt Trip for Left-side Mounting
Attribute Cat. No. 140MT-C-UX Cat. No. 140MT-C-SN
Pick-up [V] 0.85…1.1 x Us 0.7…1.1 x Us
Actuating Voltage
Drop-out [V] 0.7…0.35 x Us 0.7…1.1 x Us
50 Hz [V AC] 24 —
140MT-C-UXK
60 Hz [V AC] 28 —
50 Hz [V AC] 110 —
140MT-C-UXD
60 Hz [V AC] 120 —
50 Hz [V AC] 220…230 —
140MT-C-UXF
60 Hz [V AC] — —
50 Hz [V AC] — —
140MT-C-UXA
60 Hz [V AC] 240…260 —
50 Hz [V AC] 380…400 —
140MT-C-UXN
60 Hz [V AC] 440…460 —
50 Hz [V AC] 415 —
140MT-C-UXB
60 Hz [V AC] 480 —
50 Hz [V AC] — 24
140MT-C-SNK
60 Hz [V AC] — 24…28
Rated AC Control Voltage 50 Hz [V AC] — 110
140MT-C-SND
60 Hz [V AC] — 120
50 Hz [V AC] — 220…230
140MT-C-SNF
60 Hz [V AC] — —
50 Hz [V AC] — —
140MT-C-SNA
60 Hz [V AC] — 240…260
50 Hz [V AC] — 240
140MT-C-SNT
60 Hz [V AC] — 277
50 Hz [V AC] — 380…400
140MT-C-SNN
60 Hz [V AC] — 440…460
50 Hz [V AC] — 415
140MT-C-SNB
60 Hz [V AC] — 480
On-time Continuous duty Continuous duty
Pick-up [VA/W] 8.5/8 8.5/8
Coil consumption
Hold-in [VA/W] 4/2 4/2
140MT-C-SNZJ [V DC] — 24
Rated DC Control Voltage On-time Max 5 s
Coil consumption Pick-up [W] 50
Type of Terminals
Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3
Flexible with insulated ferrule 1 or 2 conductors 0.5…2.5 mm2/ No. 18…14 AWG 0.5…2.5 mm2/ No. 18…14 AWG
Flexible 1 or 2 conductors 0.75…2.5 mm2/ No. 18…14 AWG 0.75…2.5 mm2/ No. 18…14 AWG
Stranded per UL/CSA 1 or 2 conductors 0.75…2.5 mm2/ No. 18…14 AWG 0.75…2.5 mm2/ No. 18…14 AWG
Solid 1 or 2 conductors 0.5…2.5 mm2/ No. 18…14 AWG 0.5…2.5 mm2/ No. 18…14 AWG
Conductor steps Max 2 conductor steps allowed Max 2 conductor steps allowed
Tightening torque 1…1.2 N•m/8.9…10.6 lb•in 1…1.2 N•m/8.9…10.6 lb•in1…1.2
Type of Terminals
Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3
1 conductor 0.5…2.5 mm2 0.5…2.5 mm2
Flexible with insulated ferrule
2 conductors 0.75…2.5 mm2 0.75…2.5 mm2
Stranded per UL/CSA 1 or 2 conductors 0.75…2.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Solid 1 or 2 conductors 0.75…2.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Tightening torque 1.2…1.5 N•m/10.6…13.3 lb•in 1.2…1.5 N•m/10.6…13.3 lb•in
Stranded per UL/CSA 1 conductor 2.5…25 mm2/No. 14…4 AWG 4…50 mm2/No. 12…1/0 MCM — —
Solid 1 conductor 2.5…25 mm2/No. 14…4 AWG 2.5…50 mm2/No. 12…1/0 MCM — —
for use with for use with 4…25 mm2/ for use with
Stranded per UL/CSA 1 conductor 4…25 mm2 140MT-C-W No. 10…4 AWG 140MT-C-W 140M-F-W
No. 10…4 AWG
for use with for use with 2.5…25 mm2/ for use with
Solid 1 conductor 2.5…25 mm2 140MT-C-W No. 14…4 AWG 140MT-C-W 140M-F-W
No. 14…4 AWG
Tightening torque 3…3.5 N•m 2…2.5 N•m 27…31 lb•in 18…22 lb•in 5…6 N•m/45…54 lb•in
Time-Current Characteristic
Figure 10 - Motor Protection Circuit Breakers Time-Current Characteristic
10 000
1h
1 000
100
1
10
0.1
2
0.01
0.001
0.8 1 2 4 6 10 20 40 60 100
Multiple of set current Ie
140MT-C, -D, 140M-F Motor Protection Circuit Breakers (for 140MT-D9V, see ratings)
The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC 60947-4-1. If a different value is prescribed
(for example, reduced Ie for cooling medium having a temperature higher than 40 °C (104 °F) or a place of installation higher than 2000 m
(6561 ft) above sea level), the setting current is equal to the reduced rated current Ie of the motor.
Approximate Dimensions
Dimensions are in millimeters (inches) and are not intended for manufacturing purposes.
90° 90°
120°
46.8
(1.83)
45
96.3 (1.77)
5.8 (3.79)
(0.23)
48.15
(1.9)
X2
Z
Y 24.8 Y 49 (1.93)
(0.98)
69 (2.71) 7.5
18 45 9 (0.3)
(0.71) (1.77) (0.35)
(1)
4.5
(0.18)
36.8 44.8
96.3 100 (1.45 (1.76)
(3.8) (3.94) 57.9
(2) (2.28)
23
(0.91)
6.9
(0.27) (3) (4)
2.7
14.4 14.4 (0.11)
(0.57) (0.57) 4.8
44.7 (1.76) (0.19)
(1)
4.5
(0.18) 36.8 44.8
96.3 100 (1.45 (1.76)
(3.8) (3.94) 57.9
(2) 22.9 (2.28)
(0.9)
6.9
(0.27) (3) (4)
4.75
(0.19)
14.4 14.4 8.7
(0.57) (0.57) (0.34)
44.9 (1.77)
11.4
(0.4)
44.25
(1.7)
44.8
(1.8)
30.55
(1.2)
17.3
(0.7)
35.8 (1.4)
Figure 17 - 140MT-C and 140MT-D with Cat. No. 140MT-C-TE Type E Adapter
45
(1.77)
140MT-C: 52.1 (2.05)
43.1 140MT-D: 58.1 (2.29)
(1.70)
19
(0.78)
67
(2.64)
45
(1.77)
45
(1.77)
30 (1) 30°
(1-3/16)
90° 90°
120°
(1)
30
(1-3/16)
Note Information
1 Minimum distance to grounded parts or walls
4.5 55.7
(0.18) (2.19) (1)
91 92 45
(3.58) (3.62) 111.4 (1.77)
(4.39)
55.7
(2.19)
12
(0.47)
2.4 4.5
62 (0.09) (0.18) 91 (3)
(2.44) (3.58)
54 92 (3)
18 9 (3.62)
(0.71) (2.12)
(0.35)
102
(4.01) 8
(0.31)
110
(4.33)
Note Information
1 Mounting on 35 mm DIN Rail
2 Undervoltage/shunt trip
3 Auxiliary contact (front mounted)
4 Auxiliary contact (side mounted)
. .
Figure 22 - 140M-C-WBE
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Provides product selection and specification information for Bulletin 140UT molded case
Molded Case Circuit Breaker Specifications, publication 140UT-TD001 circuit breakers.
Short-circuit Current Ratings and Your Industrial Control Panel, Provides examples for short-circuit current ratings of panels based on the methods stated
publication SCCR-AT002 in UL 508A Supplement B
Provides coordinated high-fault branch circuit solutions for motor starters, soft starters,
Rockwell Automation Global SCCR tool, rok.auto/sccr and component drives.
IEC Contactor Specifications, publication 100-TD013 Provides product selection and specification information for IEC contactors.
American Standards, Configurations, and Ratings: Introduction to Provides an overview of American motor circuit design based on methods that are outlined
Motor Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur