SPEC 49406317 SpecificationSheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 58

Technical Data

Original Instructions

Motor Protection Circuit Breaker and Motor Circuit Protector


Specifications
Bulletins 140MP, 140MT, 140M

Topic Page
Summary of Changes 2
Product Line Overview 3
Bulletin 140MP Motor Protection Circuit Breakers 4
Product Overview 4
Group Installation with MPCBs 4
Catalog Number Explanation 5
Product Selection 6
Accessories 7
Specifications 11
MPCB Specifications 11
Application Ratings 12
Accessory Specifications 16
Wiring Diagrams 18
Approximate Dimensions 19
Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors 21
Product Overview 21
Application Diagrams 22
Catalog Number Explanation 24
Product Selection 25
Selection Using Current and Hp/kW Ratings 25
Selection Using Application Ratings 28
Accessories 33
Specifications 40
Approximate Dimensions 52
140MT-C, 140MT-D Devices and Accessories 52
140M-F Devices and Accessories 55
Additional Resources 57
Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Technical Data

Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect
all changes.
Topic Page
Updated Cat. No. Explanation for Bulletin 140MT devices 24
Updated Hp ratings for 140MT-C3E-B16, 140MT-D9E-B16, 140MT-D9E-C10, 140MT-D9E-C25, 140MT-D9V-C10, and 140MT-D9V-C25 devices 25
Updated High Inrush Hp ratings for 140MT-D9T-B16, 140MT-D9T-C10, and 140MT-D9T-C25 devices 26
Updated Hp ratings for 140MT-D9N-B16, 140MT-D9N-C10, and 140MT-D9N-C25 devices 27
Updated current ratings for connecting modules 38
Updated connecting module descriptions; added connecting modules for joining 140MT-C and 140MT-D MPCBs to 100S-E08…E38 safety 38
contactors with QJ coils
Removed “Pending” from Bulletin 140MT cULus Listing, UL 60947 application ratings, and Type 2 coordination ratings 40, 43, 44, 45

2 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Product Line Overview

Bulletin No. 140MP-A 140MT-C 140MT-D 140M-F


Frame Size — C-Frame D-Frame F-Frame
Max. Current Ie 32 A 32 A 40 A 45 A
Current Rating 0.1…32 A 0.1…32 A 0.4…40 A 6.3…45 A
Short-circuit protection    
Standard magnetic trip   140MT-D9E… 140M-F8E…
High magnetic trip — — 140MT-D9T… 140M-F8T…
Magnetic-only trip (Motor Circuit Protector [MCP]) — — 140MT-D9N… 140M-F8N…
Overload protection    
Trip Class 10A 10 10 10
Phase loss sensitivity    
Variable-frequency Drive (VFD) downstream compatible — — 140MT-D9V… 
UL 60947-4-1 Application Ratings:
Motor Disconnect  (see ratings)  (see ratings)  (see ratings)  (see ratings)
Group Installation  (see ratings)  (see ratings)  (see ratings)  (see ratings)
Tap Conductor Protection —  (see ratings)  (see ratings)  (see ratings)
Manual, Self Protected (Type E) —  (see ratings)  (see ratings)  (see ratings)
Type F ratings with 100-C and 100-E Contactors —  (see ratings)  (see ratings)  (see ratings)
Standards Compliance and Certifications:
UL 60947-4-1, CSA C22.2, No. 60947-4-1    
IEC/EN 60947–2, IEC/EN 60947-4-1    
CE    
ATEX —  (1) —
IECEx —  (1) —
EAC    
CCC    
KC  — — —
CB Scheme    
Accessories (Optional)
External rotary operator    
Auxiliary contacts    
Trip Indication contacts    
Undervoltage release    
Shunt release    
Insulated three-phase busbar    
Connecting modules for 100-C contactors    
Connecting modules for 100-E contactors    —
Connecting modules for 100-K contactors   — —
Lockable knob   Standard 
Anti-tamper cover   Standard 
Product Selection page 6 page 25
(1) Does not apply to Cat. No. 140MT-D9N… devices.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 3


Bulletin 140MP Motor Protection Circuit Breakers

Product Overview
Bulletin 140MP Motor Protection Circuit Breakers (MPCBs) or Motor Protective Switching Devices (MPSDs) are UL
Listed as Manual Motor Controllers (with approvals for Suitable as Motor Disconnect and Suitable for use in Group
Installation).

Group motor installations eliminate the need for individual branch short circuit protective devices for each motor
circuit, reducing panel space, installation & wiring time, and costs. There is only one Branch Circuit Protective
Device (BCPD) for the "Group".

According to UL 60947-4-1, CSA C22.2 No.60947-4-1, these devices may provide the following control and protection functions.
• Disconnect for Motor Branch Circuit
• Manual Switching (Motor control means)
• Overload Protection (Thermal Protection)

These devices meet requirement of Motor Protective Switching Devices (MPSD) according to IEC 60947-4-1 and Circuit Beaker according to
IEC 60947-2 standard for application outside of North America. These devices provide the following functions.
• Disconnect for Motor Branch Circuit
• Short-circuit Protection (Magnetic Protection)
• Overload Protection (Thermal Protection)
• Manual Switching (Motor control means)

140MP devices provide Trip Class 10A overload protection and phase loss sensitivity protection. These are suitable for single- and three-
phase application.

Group Installation with MPCBs


There is only one Branch Circuit Protective Device (BCPD) for the “Group”.

Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and
other loads to be connected to the same branch-circuit…” The most restrictive part of the conditions specified for Group Installation is the
requirement for the protection of the conductors for each motor circuit.
Figure 1 shows an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”.

Bulletin 140MP Motor Protection Circuit Breakers are UL/CSA Listed for Group Installation: conductors from the BCPD to each motor
must be a minimum of 1/3 the ampacity of the Branch Circuit conductors.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 4


Bulletin 140MP Motor Protection Circuit Breakers Product Overview

Figure 1 - Group Installation with MPCBs

Branch Circuit Fuse or


Protective Device Circuit Breaker

Group Installation
Single motor taps must be 1/3
the ampacity of the branch
circuit conductors Branch Circuit
Conductors

Catalog Number Explanation


140MP - A 3 E - B10
a b c d e

a b c d e
Interrupting Rating/
Bulletin Number Frame Size Function Current Range
Breaking Capacity
Code Description Code Description Code Description Code Description Code Description
140MP Motor Protection A Frame A 3 Normal break Adjustable Thermal/ A 0.10 (example: A16 = 0.16 A)
140MP E
Circuit Breaker Fixed Magnetic MPCB B 1.0 (example: B16 = 1.6 A)
C 10 (example: C16 = 16 A)

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 5


Bulletin 140MP Motor Protection Circuit Breakers Product Selection

Product Selection
Table 1 - Bulletin 140MP MPCB Selection Using Current and Hp/kW Ratings
Max. Short Circuit
Rated Motor Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Current Magnetic
Current (Ie) Adjustment 400V 480V Cat. No.
Trip
[A] Range [A] Current [A] (I ) (group motor) 200V 230V 460V 575V 230V 400/415V 500V 690V
cu
0.16 0.10…0.16 2 100 30 — — — — — 0.02 0.06 0.06 140MP-A3E-A16
0.25 0.16…0.25 3.1 100 30 — — — — — 0.04 0.09 0.09 140MP-A3E-A25
0.4 0.25…0.40 5 100 30 — — — 0.25 0.06 0.09 0.12 0.18 140MP-A3E-A40
0.63 0.40…0.63 7.9 100 30 — — 0.25 0.33 0.09 0.18 0.18 0.25 140MP-A3E-A63
1 0.63…1.0 12.5 100 30 — — 0.5 0.75 0.18 0.25 0.37 0.55 140MP-A3E-B10
1.6 1.0…1.6 20 100 30 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140MP-A3E-B16
2.5 1.6…2.5 31.3 75 30 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140MP-A3E-B25
4 2.5…4.0 50 75 18 1 1 3 3 0.75 1.5 2.2 3 140MP-A3E-B40
6.3 4.0…6.3 78.8 50 18 1.5 2 5 5 1.5 2.2 3 4 140MP-A3E-B63
10 6.3…10 150 50 18 3 3 7.5 10 2.2 4 6.3 7.5 140MP-A3E-C10
12 8.0…12 180 50 18 3 3 7.5 10 3 5.5 6.3 7.5 140MP-A3E-C12
16 10…16 240 15 18 5 5 10 15 4 7.5 10 13 140MP-A3E-C16
20 16…20 300 15 18 5 7.5 15 20 5.5 10 11 17 140MP-A3E-C20
25 20…25 375 15 18 7.5 7.5 20 20 5.5 11 15 22 140MP-A3E-C25
32 25…32 480 15 18 7.5 10 25 30 7.5 15 20 25 140MP-A3E-C32
(1) Horsepower/kW ratings shown are for reference. The final selection of the MPCB/MPSD depends on the actual motor full load current.

Table 2 - Bulletin 140MP MPCB Selection Using Interrupting Rating/Breaking Capacity


Breaking Capacity, IEC 60947-2
230V AC 400V AC 440V AC 500V AC 690V AC
Cat. No.
Ics Icu Back-up Fuse Ics Icu Back-up Fuse Ics Icu Back-up Fuse Ics Icu Back-up Fuse Ics Icu Back-up Fuse
[kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A]
50 100 50 100 30 100 30 100 30 100 140MP-A3E-A16
50 100 50 100 30 100 30 100 30 100 140MP-A3E-A25
50 100 50 100 30 100 30 100 30 100 140MP-A3E-A40
—(2) —(2) —(2)
50 100 50 100 30 100 30 100 30 100 140MP-A3E-A63
50 100 50 100 30 100 30 100 30 100 140MP-A3E-B10
50 100 —(2) 50 100 —(2) 30 100 30 100 30 100 140MP-A3E-B16
50 75 50 75 10 30 25(3) 10 20 25(3) 5 10 25(3) 140MP-A3E-B25
50 75 50 75 6 18 25 (3) 6 15 25 (3) 2 3 25 (3) 140MP-A3E-B40
50 50 50 50 6 18 63 (3) 6 10 63 (3) 2 3 40 (3) 140MP-A3E-B63
50 50 50 50 6 18 63 (3) 6 10 63 (3) 2 3 50 (3) 140MP-A3E-C10
25 50 80 (3) 25 50 80 (3) 6 15 63 (3) 6 10 63 (3) 2 3 50 (3) 140MP-A3E-C12
15 15 80 (3) 15 15 80 (3) 4 6 63 (3) 4 6 63 (3) 2 3 63 (3) 140MP-A3E-C16
10 15 125 (3) 10 15 125 (3) 3 6 125 (3) 3 6 125 (3) 2 3 80 (3) 140MP-A3E-C20
10 15 125 (3) 10 15 125 (3) 3 6 125 (3) 3 6 125 (3) 2 3 100 (3) 140MP-A3E-C25
10 15 125 (3) 10 15 125 (3) 3 6 125 (3) 3 6 125 (3) 2 3 100 (3) 140MP-A3E-C32
(1) Back-up fuses are type gG, aM.
(2) No Back-up fuse required if Icc<Ics.
(3) Rated back-up fuse for short-circuit up to 50 kA.

6 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Accessories

Accessories
Table 3 - Auxiliary Contacts
Auxiliary Contacts Pkg.
Description Connection Diagram Cat. No.
N.O N.C Qty.
13 21

1 1 14 22
140MP-A-AFA11

1 0 140MP-A-AFA10
Front-mounted Auxiliary Contact
• No additional space required 10
• 1 and 2-pole 21

0 1 22
140MP-A-AFA01
I >>

2 0 140MP-A-AFA20

1 1 140MP-A-ASA11

Right-side-mounted Auxiliary Contact


2 0 140MP-A-ASA20
• 2-pole
• Adds 9 mm (0.35 in.) to the width of the 2
Manual Motor Starter 31 41

• Use compact bus bars with 54 mm (2.13 in.) 0 2 140MP-A-ASA02


32 42
spacing

Lead Contacts 33 41

34 42 140MP-A-ASA20L
2 0

Table 4 - Trip Contacts


Auxiliary Contacts Pkg.
Description Connection Diagram Cat. No.
N.O N.C Qty.

57 65
1 1 140MP-A-ASAR11
I>>

Right-side-mounted Trip Signaling 58 66


Contact
• 2-pole
57 67
• Adds 9 mm (0.35 in.) to the width of the 2 0 2 140MP-A-ASAR20
Manual Motor Starter I>>

58 68
• Use compact bus bars with 54 mm
(2.13 in.) spacing
55 65
0 2 140MP-A-ASAR02
I >>

56 66

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 7


Bulletin 140MP Motor Protection Circuit Breakers Accessories

Table 5 - Undervoltage and Shunt Trip Units


Description Trip Rating Connection Diagram Pkg. Qty. Cat. No.
20V, 50 Hz/
24V, 60 Hz 140MP-A-UXJ
24V, 50 Hz 140MP-A-UXK
48V, 50 Hz 140MP-A-UXY
Undervoltage Trip Release 60V, 50 Hz D1 140MP-A-UXYA
• Left-side mounted 110V, 50 Hz/ 120V, 60 Hz U< 140MP-A-UXC
1
• Adds 18 mm (0.71 in.) to the width of the
Manual Motor Starter 208V, 60 Hz D2 140MP-A-UXH
I >>
230V, 50 Hz/ 240V, 60 Hz 140MP-A-UXF
400V, 50 Hz 140MP-A-UXN
415V, 50 Hz/ 480V, 60 Hz 140MP-A-UXB
575V, 60 Hz 140MP-A-UXM
20…24V, 50/60 Hz 140MP-A-SNKJ
110V, 50/60 Hz 140MP-A-SND
Shunt Trip Release C1
200…240V, 50/60 Hz 140MP-A-SNAF
• Left-side mounted 1
• Adds 18 mm (0.71 in.) to the width of the C2
Manual Motor Starter I >>
350…415V, 50/60 Hz 140MP-A-SNN

Table 6 - Bus Bars


Description Terminal Links For Use With Pkg. Qty. Cat. No.
2 x 3 connections 140MP-A-W452
• 45 mm (1.77 in.) spacing 3 x 3 connections 140MP-A-W453
• For use with front-mounted 140MP 10
auxiliary contact 4 x 3 connections 140MP-A-W454
5 x 3 connections 140MP-A-W455
2 x 3 connections 140MP-A-W542
Compact Bus Bars • 54 mm (2.13 in.) spacing 3 x 3 connections 140MP-A-W543
– UL: 600V, 60 A • For use with side-mounted 140MP 10
– IEC: 690V, 65 A auxiliary contact 4 x 3 connections 140MP-A-W544
5 x 3 connections 140MP-A-W545
2 x 3 connections 140MP-A-W632
• 63 mm (2.5 in.) spacing 3 x 3 connections 140MP-A-W633
• For use with side-mounted 140MP 10
auxiliary contact 4 x 3 connections 140MP-A-W634
5 x 3 connections 140MP-A-W635
Bus Bar Feeder Terminal (Flat)
• Supply of compact bus bars 140MP-A-W 10 140MP-A-WTN
• Increases terminal capacity
Bus Bar Feeder Terminal (High)
• Supply of compact bus bars 140MP-A-W 10 140MP-A-WTNH
• Increases terminal capacity

Table 7 - Connecting Modules


Description For Use With Cat. No.
ECO Connecting Module - 12 A (IEC), 11 A (UL)
• For DOL Starters
140MP-A to 100-K 140MP-A-PEK12
• ECO Starters mount on single DIN Rail (140MP on DIN rail)
• Electrical and mechanical interconnection of 140MP and 100-K Contactors
ECO Connecting Module - 25 A (IEC), 24 A (UL)
• For DOL Starters
140MP-A to 100-C09…C23 140MP-A-PEC23
• ECO Starters mount on single DIN Rail (140MP on DIN rail)
• Electrical and mechanical interconnection of 140MP and 100-C Contactors

8 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Accessories

Table 7 - Connecting Modules (Continued)


Description For Use With Cat. No.
ECO Connecting module (1) 140MP-A3E-A16…C25 to
100(S)-E09…16 140MP-A-PE16
• For DOL starters 16 A
• ECO Starters mount on single DIN Rail (140MP on DIN Rail) 140MP-A3E-A16…C16 to 140MP-A-PE26
• Electrical and mechanical interconnection of 140MP and 100-E 100(S)-E26…38
contactors 140MP-A3E-C20…C32 to
• Package quantity: 10 38 A 140MP-A-PE38
100(S)-E26…38
(1) Not suitable for 100(S)-E09...38QJ or 300(S)-TO...BOQJ contactors.

Table 8 - Additional Accessories


Description For Use With Pkg. Qty. Cat. No.

Blank Space Cover


• For covering unused terminal links 140MP-A-W 50 140MP-A-WSN
• Must be ordered in multiples of 10 (10pieces/package)

Screw Adapter
• For screw arrangement of a motor protection circuit breaker
140MP 10 140MP-A-N45
• Hat (DIN) Rail 35 x 7.5 mm (1.4 x 0.3 in.)
• 44 mm (1.7 in.) length

Red/yellow handle 140MP-A-ENY65

Enclosure
• Up to three padlocks in OFF position 140MP 1
• Protection Class: IP65; UL/CSA Type 12 Black handle 140MP-A-ENN65

Red/yellow handle 140MP-A-DMY65


Door Mounting Kit
• Up to three padlocks in OFF position 140MP 1
• Protection Class: IP65; UL/CSA Type 12 Black handle 140MP-A-DMN65

Red/Yellow 140MP-A-DCY65
Door Coupling Handle
• Up to three padlocks in OFF position
• Defeatable 140MP 1
• Type 1/3R/12
• IP64
Black 140MP-A-DC65

Coupler
• Coded - Positioning of ON indication Driver with screw 140MP-A-DNC
dependent from mounting orientation of the
140MP 140MP 1
• Uncoded - Positioning of ON indication
Driver without
independent from mounting orientation of 140MP-A-DNUC
coding, with screw
the 140MP

Shaft Alignment Ring


• Supports the long shafts for alignment to the handle inlet. It makes 140MP 1 140MP-A-SAR
closing panel doors more easy
• Use for shafts

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 9


Bulletin 140MP Motor Protection Circuit Breakers Accessories

Table 8 - Additional Accessories


Description For Use With Pkg. Qty. Cat. No.
105 mm (4.13 in.) 140MP-A-DS
Extension Shaft 140MP 10
180 mm (7.1 in.) 140MP-A-DSM

Extension Shaft Support


• Supports the shaft in the extension of handle (140MP-A-DC)
• Required for shaft lengths >130 mm (5.1 in.)
140MP 1 140MP-A-SHS
• Snaps on the right side of the MPCB
• Width: 9 mm (0.35 in.)
• For use with screw-mounted or hat rail mounted devices.

Lockable Handle Accessory


140MP 10 140MP-A-KN1
• For locking 140MP devices in the OFF position

10 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Specifications
MPCB Specifications
Table 9 - General Ratings
Attribute Value
IEC IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
Standards compliance
cULus UL 60947-1, UL 60947-4-1, CSA C22.2, No. 60947-4-1
Global RINA (Marine)
Certifications
Regional CCC, KC, EAC, CE, IEC, cULus, CB Scheme
Rated operating voltage Ue 690V AC
Maximum operating voltage (UL) 600V
Rated Frequency 50/60 Hz
Trip Class 10A
Mechanical 100.000 Cycles
Number of operations
Electrical 100,000 Cycles (0.1…16 A); 50,000 Cycles (20…32 A)
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 690V
Pollution Degree 3
Phase loss sensitivity Yes
Disconnect function per IEC/EN 60947-2 Yes
Resistance to shock per IEC 60068-2-27 25 G/11 ms
Resistance to vibrations per IEC 60068-2-6 5 G /3 … 150 Hz
Mounting DIN Rail (EN 60715)
Group mounting (side by side) up to 40 °C (104 °F)
Minimum distance to other Horizontal 0 mm (0 in.)
units same type Vertical 150 mm (5.9 in.)
Horizontal, up to 400V 0 mm (0 in.)
Minimum distance to Horizontal, up to 690V > 1.5 mm (0.06 in.)
electrical conductive board
Vertical 75 mm (2.96 in.)
Housing IP20
Degree of Protection
Main Terminals IP10
@230V, 400V, 440V, 500V, and 690V See Table 2
Short-circuit ratings @480V and 600V—for motor disconnect
See Table 14
@480V and 600V—for group motor installation
IEC 60947-2 (Circuit breaker) A
Utilization Category
IEC 60947-4-1 (Motor Starter) AC-3

Table 10 - Power Loss


Rated Operating Current [A]
Power Loss
0.16…1.6 2.5…6.3 10…12 16…25 32
Power Loss in all 3 Poles up to: [W] 5.1 5.4 7.2 8.4 9.3

Table 11 - Environmental Ratings


Attribute Value
Open—compensated -25 … +55 °C (-13…+131 °F)(1)
Operating Ambient air
temperature Open -25 … +70 °C (-13…+158 °F)(1)
Enclosed 0 … +40 °C (32…104 °F)
Storage Ambient air temperature -50 … +80 °C (-58…+176 °F)
Maximum operating altitude permissible 2000 m (6561 ft)
(1) With derating. See Table 12.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 11


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Table 12 - Ambient Temperature Derating


Ambient Temperature Derating [A]
Cat. No.
40 °C (104 °F) 55 °C (131 °F) 70 °C (158 °F)
140MP-A3E-C10 10 10 8
140MP-A3E-C12 12 12 10
140MP-A3E-C16 16 16 12
140MP-A3E-C20 20 20 18
140MP-A3E-C25 25 25 23
140MP-A3E-C32 32 32 29

Table 13 - MPCB Connecting Characteristics


Connection No. of Conductors Devices Rated ≤ 16 A Devices Rated 20…32 A

Type of terminals

Connection Screw M3.5/Pozidriv No.2 M4/Pozidriv No.2


1…2.5 mm2
Solid 1 or 2 1…4 mm2
2.5…6 mm2

Flexible with ferrule 1 or 2 0.75…2.5 mm2 0.75…6 mm2

Wiring 1.5…2.5 mm2/No.16…8 AWG


Flexible/finely stranded 1 or 2 0.75…2.5 mm2/No. 16…12 AWG
2.5…6 mm2/No.16…8 AWG
1…2.5 mm2/No.16…8 AWG
Stranded per UL/CSA 1 or 2 1…4 mm2/No. 16…12 AWG
2.5…6 mm2/No.16…8 AWG
Stripping length 9 mm (0.35 in.) 10 mm (0.39 in.)
Tightening torques 0.8…1.2 N•m/7…10 lb•in 2 N•m /18 lb•in

Application Ratings
Table 14 lists specific application ratings for MPCBs.
Table 14 - UL/CSA Listed Application Ratings, Motor Protection Circuit Breaker Only
UL 60947-4-1 — Manual Motor Controller
Max. Short Circuit Current [kA]
Cat. No. Branch Circuit Protection Motor Disconnect Group Installation
Max. Size per NEC/CEC [A]
480V 600V 480V 600V
140MP-A3E-A16 175 30 5 30 5
140MP-A3E-A25 175 30 5 30 5
140MP-A3E-A40 175 30 5 30 5
140MP-A3E-A63 175 30 5 30 5
140MP-A3E-B10 175 30 5 30 5
140MP-A3E-B16 175 30 5 30 5
140MP-A3E-B25 175 30 5 30 5
140MP-A3E-B40 175 18 5 18 5
140MP-A3E-B63 175 18 5 18 5
140MP-A3E-C10 175 18 5 18 5
140MP-A3E-C12 175 18 5 18 5
140MP-A3E-C16 175 18 5 18 5
140MP-A3E-C20 400 18 5 18 5
140MP-A3E-C25 400 18 5 18 5
140MP-A3E-C32 400 18 5 18 5

12 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Table 15 through Table 20 lists specific application ratings for MPCBs in combination with Bulletin 100-K, 100-C, and 100-E contactors.

Type 1 Coordination—Specified 100-K contactors are suitable for motor group applications when they are used on the load side of the
140MP-A3E Manual Motor Controllers that are specified in Table 15.
Table 15 - Type 1 Application Ratings, 140MP to 100-K Miniature IEC Contactors
SCCR
Manual Motor Controller Contactor (1) Maximum Fuse or Circuit Breaker
480V AC [kA] 600V AC [kA] sized per NEC [A]
140MP-A3E-A16 30 5 175
140MP-A3E-A25 30 5 175
140MP-A3E-A40 30 5 175
140MP-A3E-A63 100-K05 30 5 175
140MP-A3E-B10 100-K09 30 5 175
140MP-A3E-B16 100-K12 30 5 175
140MP-A3E-B25 30 5 175
140MP-A3E-B40 18 — 175
140MP-A3E-B63 18 — 175
100-K09
140MP-A3E-C10 18 — 175
100-K12
140MP-A3E-C12 18 — 175
100-K12
140MP-A3E-C16 18 — 175
(1) May be used with 140MP-A-PEK12 connecting module between 140MP-A3E manual motor controller and 100-K contactor.

Type 1 Coordination—Specified 100-C contactors (without R suffix) are suitable for motor group applications when they are used on the load
side of the specified Manual Motor Controllers.
Table 16 - Type 1 Application Ratings, 140MP to 100-C IEC Contactors
SCCR
Manual Motor Controller Contactor (1) Maximum Fuse or Circuit
480V AC [kA] 600V AC [kA] Breaker sized per NEC [A]
140MP-A3E-A16 30 5 175
140MP-A3E-A25 30 5 175
140MP-A3E-A40 30 5 175
140MP-A3E-A63 30 5 175
100-C09
140MP-A3E-B10 100-C12 30 5 175
140MP-A3E-B16 100-C16 30 5 175
100-C23
140MP-A3E-B25 30 5 175
140MP-A3E-B40 18 5 175
140MP-A3E-B63 18 5 175
140MP-A3E-C10 18 5 175
100-C12
140MP-A3E-C12 100-C16 18 5 175
100-C23
140MP-A3E-C16 (2) 100-C16, 100-C23 18 5 175
100-C23
140MP-A3E-C20 100-C30 18 5 400
100-C37
140MP-A3E-C25 (3) 100-C23 18 — 400
140MP-A3E-C25 (3) 100-C30, 100-C37 18 5 400
140MP-A3E-C32 (4) 100-C30, 100-C37 18 5 400
(1) 140MP-A-PEC23 connection modules may be used with 100-C09…-C23 up to 24 A.
(2) Limited to 15.5 FLA maximum when used in a 365 x 235 x 140 mm (14.4 x 9.3 x 5.5 in.) (200%) or larger enclosure. Limited to 14.5 FLA maximum when used in 115 x 290 x 180 mm
(4.5 x 11.4 x 7.1 in.) (150%) minimum sized enclosure.
(3) Minimum enclosure size is 170 x 670 x 235 mm (6.7 x 26.4 x 9.3 in.) (250%) at full load current. If end use current is 22.5 FLA or less, may be used in an enclosure as small as
115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%).
(4) May be used at 30.8 FLA maximum when used ambient temperature of 40 °C (104 °F) maximum. May be used up to 29 FLA when used in a 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%)
minimum size enclosure.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 13


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Table 17 - Type 2 Coordination Ratings per IEC 60947-4-1, 140MP to 100-C IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, IEC 60947-4-1
Cat. No. 400/415V
Max. Short Circuit Current [kA] For Use With Contactor Cat. No.
140MP-A3E-A16 50 100-C09
140MP-A3E-A25 50 100-C09
140MP-A3E-A40 50 100-C09
140MP-A3E-A63 50 100-C09
140MP-A3E-B10 50 100-C09
140MP-A3E-B16 50 100-C09
140MP-A3E-B25 50 100-C09
140MP-A3E-B40 50 100-C09
140MP-A3E-B63 50 100-C09
140MP-A3E-C10 50 100-C09
140MP-A3E-C12 25 100-C12
140MP-A3E-C16 10 100-C23
140MP-A3E-C20 10 100-C30
140MP-A3E-C25 10 100-C30
140MP-A3E-C32 10 100-C30

Table 18 - Type 2 Coordination Ratings per IEC 60947-4-1, 140MP to 100-E IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, IEC 60947-4-1
Cat. No. 400V
Max. Short Circuit Current [kA] Minimum Contactor Size
140MP-A3E-A16 50 100-E09
140MP-A3E-A25 50 100-E09
140MP-A3E-A40 50 100-E09
140MP-A3E-A63 50 100-E09
140MP-A3E-B10 50 100-E09
140MP-A3E-B16 50 100-E09
140MP-A3E-B25 50 100-E09
140MP-A3E-B40 50 100-E26
140MP-A3E-B63 50 100-E26
140MP-A3E-C10 50 100-E26
140MP-A3E-C12 25 100-E26
140MP-A3E-C16 16 100-E26
140MP-A3E-C20 10 100-E30
140MP-A3E-C25 10 100-E30
140MP-A3E-C32 10 100-E38

14 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Table 19 - Type 2 Coordination Ratings per UL 60947-4-1, 140MP to 100-C IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, UL 60947-4-1
Max. Fuse or Circuit Breaker Size
Cat. No. Contactor (1) 480V 600V per NEC [A]
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]
140MP-A3E-A16 30 5 175
140MP-A3E-A25 30 5 175
100-C09
140MP-A3E-A40 100-C12 30 5 175
140MP-A3E-A63 100-C16 30 5 175
100-C23
140MP-A3E-B10 30 5 175
140MP-A3E-B16 30 5 175
100-C12
140MP-A3E-B25 100-C16 30 5 175
100-C23
100-C16
140MP-A3E-B40 18 5 175
100-C23
140MP-A3E-B63 100-C23 18 5 175
140MP-A3E-C10 18 5 175
140MP-A3E-C12 18 5 175
140MP-A3E-C16 (2) 100-C30 18 5 175
140MP-A3E-C20 100-C37 18 5 400
140MP-A3E-C25 (3) 18 5 400
140MP-A3E-C32 (4) 18 5 400
(1) 140MP-A-PEC23 connection modules may be used with 100-C09…-C23 up to 24 A.
(2) Limited to 15.5 FLA maximum when used in a 365 x 235 x 140 mm (14.4 x 9.3 x 5.5 in.) (200%) or larger enclosure.
Limited to 14.5 FLA maximum when used in 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%) minimum sized enclosure.
(3) Minimum enclosure size is 170 x 670 x 235 mm (6.7 x 26.4 x 9.3 in.) (250%) at full load current.
If end use current is 22.5 FLA or less, may be used in an enclosure as small as 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%).
(4) May be used at 30.8 FLA maximum when used ambient temperature of 40 °C (104 °F) maximum.
May be used up to 29 FLA when used in a 115 x 290 x 180 mm (4.5 x 11.4 x 7.1 in.) (150%) minimum size enclosure.

Table 20 - Type 2 Coordination Ratings per UL 60947-4-1, 140MP to 100-E IEC Contactors, Standard Motor Protection
Type 2 Coordination Ratings, UL 60947-4-1
Max. Fuse or Circuit 480V 600V
Cat. No. Breaker per NEC Max. Short-circuit Current Minimum Contactor Size Max. Short-circuit Current Minimum Contactor Size
[kA] [kA]
140MP-A3E-A16 175 30 100-E09 5 100-E09
140MP-A3E-A25 175 30 100-E09 5 100-E09
140MP-A3E-A40 175 30 100-E09 5 100-E09
140MP-A3E-A63 175 30 100-E09 5 100-E09
140MP-A3E-B10 175 30 100-E09 5 100-E09
140MP-A3E-B16 175 30 100-E09 5 100-E09
140MP-A3E-B25 175 30 100-E16 5 100-E16
140MP-A3E-B40 175 18 100-E26 5 100-E16
140MP-A3E-B63 175 18 100-E26 5 100-E26
140MP-A3E-C10 175 18 100-E26 5 100-E30
140MP-A3E-C12 175 18 100-E26 5 100-E30
140MP-A3E-C16 175 18 100-E26 5 100-E40
140MP-A3E-C20 400 18 100-E26 5 100-E40
140MP-A3E-C25 400 18 100-E30 5 100-E40
140MP-A3E-C32 400 18 100-E38 5 100-E40

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 15


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Accessory Specifications
Table 21 - Auxiliary Contact, Signaling Contact, and Short-circuit Signaling Contact Specifications
Side-mounted Auxiliary, Signaling,
Attribute Front-mounted Auxiliary Contacts
and Short-circuit Signaling Contacts
IEC IEC/EN 60947–1, IEC/EN 60947-5-1 IEC/EN 60947–1, IEC/EN 60947-5-1
Standards compliance
UL/cULus UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1 UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1
Rated operating voltage Ue 690V AC/600V DC 250V AC/250V DC
Conventional free-air thermal current Ith 6A 5A
Rated Frequency 50/60 Hz 50/60 Hz
Rated impulse withstand voltage Uimp 6 kV 6 kV
Rated insulation voltage Ui 690V AC 250V AC
Pollution Degree 3 3
Operation -25 … +60 °C (-13…+140 °F) -25 … +60 °C (-13…+140 °F)
Ambient air temperature
Storage -50 … +80 °C (-58…+176 °F) -50 … +80 °C (-58…+176 °F)
Resistance to shock per IEC 60068-2-27 25 G/11 ms 25 G/11 ms
Resistance to vibrations per IEC 60068-2-6 5 G/3 … 150 Hz 5 G/3 … 150 Hz
24V, 120V 6A 3A
Rated operational current Ie 240V 4A 1.5 A
AC-15 per IEC/EN 60947-5-1 for
utilization category 400V 3A —
440V, 690V 1A —
24V 2A 1A
Rated operational current IeDC- 125V 0.55 A 0.27 A
13 per IEC/EN 60947-5-1 for
utilization category 250V 0.27 A 0.11 A
440V, 600V 0.15 A —
Minimum switching capacity 17V DC/5 mA 17V DC/5 mA
Short-circuit protective device (N.O, N.C) 10 A Type gG 10 A Type gG
Duty time 100% 100%
Mounting Right side Front
Mechanical
Number of operations 50,000 cycles 50,000 cycles
Electrical
Contact utilization characteristics according to UL/CSA
Rated operating voltage Ue per UL/CSA 600V AC/600V DC 250V AC/250V DC
Pilot duty B600, Q600 B300, R300
AC thermal rated current 5A 5A
making 3600 3600 VA
AC maximum volt-ampere
breaking 360 360 VA
DC thermal rated current 2.5 A 2.5 A
making
DC maximum volt-ampere 69 VA 28 VA
breaking
Connecting characteristics Table 24 Table 24

16 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Specifications

Table 22 - Undervoltage Release Specifications


Attribute Value
IEC IEC/EN 60947–1, IEC/EN 60947-5-1
Standards compliance
UL/cULus UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1
Rated control supply voltage
See Table 5
Rated frequency
Tripping 0.35 … 0.7 x Us
Operating voltage
Coil 0.85 … 1.1 x Us
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 690V
Pollution degree 3
Operation -25 … +60 °C (-13…+140 °F)
Ambient air temperature
Storage -50 … +80 °C (-58…+176 °F)
Resistance to shock per IEC 60068-2-27 25 G/11 ms
Resistance to vibrations per IEC 60068-2-6 5 G/3 … 150 Hz
Mounting left side of MPCB

Table 23 - Shunt Trip Specifications


Attribute Value
IEC IEC/EN 60947–1, IEC/EN 60947-5-1
Standards compliance
UL/cULus UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1
Rated control supply voltage
See Table 5
Rated frequency
Operating voltage Tripping 0.7 … 1.1 x Us
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 690V
Pollution degree 3
Operation -25 … +60 °C (-13…+140 °F)
Ambient air temperature
Storage -50 … +80 °C (-58…+176 °F)
Resistance to shock per IEC 60068-2-27 15 G/11ms
Resistance to vibrations per IEC 60068-2-6 5 G/3 … 150 Hz
Mounting left side of MPCB

Table 24 - Auxiliary Contact Connecting Characteristics


Connection No. of Conductors Side Mounted Front Mounted

Solid 1 or 2 1…1.5 mm2 1…2.5 mm2

Flexible with ferrule 1 or 2 0.75…1.5 mm2


Wiring
Flexible 1 or 2 0.75…1.5 mm2

Stranded per UL/CSA 1 or 2 No. 16…14 AWG

Stripping length 8 mm (0.31 in.)


Tightening torques 0.8…1.2 N•m/7 lb•in
Recommended screwdriver Pozidriv No.2

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 17


Bulletin 140MP Motor Protection Circuit Breakers Wiring Diagrams

Table 25 - Feeder Terminal and Bus Bar Current Ratings


Attribute 140MP-A-W45…,-W54…, -W63… 140MP-A-WT…
Rated operational voltage Ue 690V
Rated operational voltage Ue per UL/CSA 600V AC
Rated operational current Ie 65 A
Rated operational current Ie per UL/CSA 60 A 65 A
Suitable for enclosure size (UL) 200% of Size of 140MP-A with bus bars
Rated frequency 50/60 Hz
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 690V AC

Table 26 - Main Circuit Connecting Characteristics


Connection No. of Conductors Value

Solid 1 6…25 mm2

Flexible with ferrule 1 6…16 mm2

Flexible with insulated ferrule 1 6…16 mm2


Wiring
Flexible 1 6…16 mm2

Stranded per UL/CSA 1 No. 10…4 AWG

Stripping length 10 mm (0.39 in.)


Tightening torques 2.5 N•m/22 lb•in
Recommended screwdriver Pozidriv No.2

Wiring Diagrams
Figure 2 illustrates basic wiring for the 140MP MPCB and accessories.

Figure 2 - 140MP Wiring Example


Front-mounted 13
Right-side-
Auxiliary Contact mounted Auxiliary
Shunt Trip 140MP-A-AFA… Contact
140MP-A-SN… 14 140MP-A-ASA…

C1 21 31 41 55 65 Right-side-mounted Trip
Signaling Contact
140MP-A-ASAR…
C2 22 32 42 56 66

D1 13 23 33 43 57 67
Undervoltage Release
140MP-A-UX… U<
D2 1 L1 3 L2 5 L3
14 24 34 44 58 68

13 21 33 41 57 65

14 22 34 42 58 66

I> I> I>


140MP MPCB
2 T1 4 T2 6 T3

18 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MP Motor Protection Circuit Breakers Approximate Dimensions

Approximate Dimensions
Dimensions are in millimeters (inches) and are not intended for manufacturing purposes.

Figure 3 - Mounting Position


180°
30°
120°

90°

Figure 4 - Cat. No. 140MP-A3E…, 140MP-A-N45 ≤16 A


Ø 4.5 (0.18) 9 (0.35) 5.4 (0.21)

122
(4.8)

110
(4.33)

17.5 (0.69)

Figure 5 - Cat. No. 140MP-A3E…, 140MP-A-N45 ≥20 A

Ø 4.5 (0.18) 9 (0.35) 5.4 (0.21)

122
(4.8)

110
(4.33)

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 19


Bulletin 140MP Motor Protection Circuit Breakers Approximate Dimensions

Figure 6 - Cat. No. 140MP-A3E-C16 with Accessories


80 (3.15)

18 (0.71) 9 (0.35) 9 (0.35) 70 (2.76)


1.5
(0.06) 5.5 (0.22) 43.5 (1.71)

1.65 37.0
(0.1) (1.46)
90
(3.54) 57.7
45.0 (2.27)
27.4 (1.77)
(1.08)

14 (0.55) 14 (0.55)
45 (1.77)

Figure 7 - Cat. No. 140MP-A3E-C32 with Accessories


80 (3.15)

70 (2.76)

5.5 (0.22) 43.5 (1.71)


18 (0.71) 9 (0.35) 9 (0.35)
1.5
(0.06)

75
(2.95)

1.65
(0.1) 37.0
(1.46)
45.0 57.25
26.93 (1.77) (2.27)
(1.06) 96.8
(3.81)

14 (0.55) 14 (0.55)
45 (1.77)

20 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors

Product Overview
Bulletin 140MT Motor Protection Circuit Breakers (MPCBs) or Motor Protective
Switching Devices (MPSDs) are UL Listed as Manual, Self-Protected Combination Motor
Controllers (Type E) and Manual Motor Controllers (with approvals for Suitable as Motor
Disconnect and Suitable for use in Group Installation).

When UL/CSA Listed as Manual, Self-Protected Combination Motor Controllers, the


140MT Motor Protection Circuit Breakers provide all of the necessary NEC/CEC 140MT-C3E… 140MT-D9E… 140M-F8E…
requirements for the protection and control of individual Motor Branch Circuits
without additional branch circuit protective devices.

According to UL 60947-4-1, CSA C22.2 No.60947-4-1, these devices may provide the following control and protection functions.
• Disconnect for motor branch circuit
• Short-circuit Protection (magnetic protection)
• Overload protection (thermal protection)
• Manual switching (motor control means)

Group motor installations eliminate the need for individual branch short-circuit protective devices for each motor circuit, reducing panel
space, installation and wiring time, and costs. There is only one Branch Circuit Protective Device (BCPD) for the "Group". Bulletin 140MT
devices are also UL Listed for Tap Conductor protection in group installations, which helps reduce conductor sizing.

According to UL 60947-4-1, CSA C22.2 No.60947-4-1, these devices these devices certified for group motor installation may provide the
following control and protection functions.
• Disconnect for motor branch circuit
• Overload protection (thermal protection)
• Manual switching (motor control means)

Bulletin 140MT devices meet requirement of Motor Protective Switching Devices (MPSD) according to IEC 60947-4-1 and Circuit Beaker
according to IEC 60947-2 standard for application outside of North America. These devices provide the following functions.
• Disconnect for motor branch circuit
• Short-circuit Protection (magnetic protection)
• Overload protection (thermal protection)
• Manual switching (motor control means)

Bulletin 140MT devices provide Trip Class 10 overload protection and phase loss sensitivity protection. These are suitable for single- and
three- phase applications.

Cat. No. 140MT-D9V devices can also be applied at the output of a variable frequency drive (VFD) in multi-motor applications.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 21


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Overview

Application Diagrams

Group Installation with MPCBs


There is only one Branch Circuit Protective Device (BCPD) for the “Group”.

Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and
other loads to be connected to the same branch-circuit…”. The most restrictive part of the conditions specified for Group Installation is the
requirement for the protection of the conductors for each motor circuit. In the U.S. NEC for 2002, a new rule for the conductor sizing was
added for devices that are listed and marked “Suitable for use as Tap Conductor Protection”.

Figure 8 shows an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”.

Bulletin 140MT Motor Protection Circuit Breakers UL/CSA Listed for Group Installation: conductors from the BCPD to each motor must be a
minimum of 1/3 the ampacity of the Branch Circuit conductors.

Bulletin 140MT Motor Protection Circuit Breakers UL/CSA Listed for Tap conductor Protection in Group Installations: conductors from the
BCPD to manual motor controller listed as “…Tap Conductor Protection…” must be minimum of 1/10 the rating or setting of the BCPD.
Conductors from the controller to the motor must be 125% of the motor FLA.

Figure 8 - Group Installation with MPCBs


Branch Circuit Protective Device

Fuses or
Circuit Breaker
Tap Conductor Protection in Group
Group Installation Installation:
Single motor taps must Conductors from BCPD to manual motor
be 1/3 the ampacity of controller listed as “…Tap Conductor
the branch circuit Branch Circuit Protection…” must be minimum of 1/10 the
conductors Conductors rating or setting of the BCPD

Tap Conductor Protection in Group


Installation:
Conductors to each motor sized normally
at 125% of motor FLA

22 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Overview

Multiple Motor Installation with MPCBs


Each Motor has an Individual Branch Circuit Protective Device.

Bulletin 140MT Motor Protection Circuit Breakers (MPCBs) are UL/CSA Listed as Type E Manual Self-Protected Combination Motor Controllers
or UL/CSA Listed as Circuit Breakers. These UL/CSA Listings allow the Bulletin 140MT MPCBs to provide the branch-circuit, short-circuit
protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the
protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream
protective device. Figure 9 shows an example that illustrates installations involving multiple motors, each with its own branch-circuit
protection (BCPD).

Figure 9 - Multiple Motor Installation with MPCBs


Feeder Circuit Conductors

Bulletin 140MT-C, 140MT-D, and 140M-F (Type E


Self-Protected Combination Motor Controllers)
may provide the branch-circuit protection for each
individual motor circuit feeder

Conductors to each motor


sized normally at 125% of
motor FLA

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 23


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Catalog Number Explanation

Catalog Number Explanation


C- and D-Frame Devices
140MT - C 3 E - B63
a b c d e

a b c d e
Current Rating/ Interrupting Rating/
Bulletin Number Function Current Range
Frame Size Breaking Capacity
Code Description Code Description Code Description Code Description Code Description
140MT Motor Protective C 32 A, Frame C 3 Normal break Adjustable Thermal/Fixed A 0.10 (example: A16 = 0.16 A)
140MT Switching E Magnetic (14 x In) MPCB
Device (Thermal) D 40 A, Frame D 9 High break B 1.0 (example: B16 = 1.6 A)
N Fixed Magnetic (14 x In) MCP C 10 (example: C16 = 16 A)
Adjustable Thermal/Fixed
T Magnetic (18…22 x In) MPCB
Fixed Magnetic (application at
V output of VFD multi-motor)

F-Frame Devices
140M - F 8 E - C10
a b c d e

a b c d e
Current Rating/ Interrupting Rating/
Bulletin Number Function Current Range
Frame Size Breaking Capacity
Code Description Code Description Code Description Code Description Code Description
140M Motor Protection F 45 A, Frame F 8 High break Adjustable Thermal/Fixed C 10 (example: C16 = 16 A)
140M E Magnetic (14 x In) MPCB
Circuit Breaker)
N Fixed Magnetic (14 x In) MCP
Adjustable Thermal/Fixed
T Magnetic (18…22 x In) MPCB

24 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Product Selection
Selection Using Current and Hp/kW Ratings
Table 27 - Motor Protective Switching Devices
Max Short-circuit
Rated Motor Current Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Adjustment Magnetic Trip Cat. No.
Current (Ie) [A] Range [A] Current [A] 400V 480V
(Icu) (group motor) 200V 230V 460V 575V 230V 400/415V 500V 690V

C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)


0.16 0.10…0.16 2.2 100 65 — — — — — 0.02 0.06 0.06 140MT-C3E-A16
0.25 0.16…0.25 3.5 100 65 — — — — — 0.04 0.09 0.09 140MT-C3E-A25
0.4 0.25…0.40 5.6 100 65 — — — — 0.06 0.09 0.12 0.18 140MT-C3E-A40
0.63 0.40…0.63 8.8 100 65 — — — — 0.09 0.18 0.18 0.25 140MT-C3E-A63
1 0.63…1.0 14 100 65 — — 0.5 0.5 0.18 0.25 0.37 0.55 140MT-C3E-B10
1.6 1.0…1.6 22 100 65 — — 0.75 — 0.25 0.55 0.75 1.1 140MT-C3E-B16
2.5 1.6…2.5 35 100 65 0.5 0.5 1 1.5 0.37 0.75 1.1 1.8 140MT-C3E-B25
4 2.5…4.0 56 100 65 0.75 0.75 2 3 0.75 1.5 2.2 3 140MT-C3E-B40
6.3 4.0…6.3 88 100 65 1 1.5 3 5 1.5 2.2 3 4 140MT-C3E-B63
10 6.3…10 140 100 65 2 2 5 7.5 2.2 4 6.3 7.5 140MT-C3E-C10
16 10…16 224 65 30 3 5 10 10 4 7.5 10 13 140MT-C3E-C16
20 14.5…20 280 50 30 5 5 10 15 5.5 10 11 17 140MT-C3E-C20
25 18…25 350 15 30 5 7.5 15 20 5.5 11 15 22 140MT-C3E-C25
29 23…29 406 15 30 7.5 10 20 25 7.5 13 18.5 25 140MT-C3E-C29
32 26.5…32 448 15 30 7.5 10 20 30 7.5 15 20 25 140MT-C3E-C32
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
0.63 0.40…0.63 8.8 100 65 — — — — 0.09 0.18 0.18 0.25 140MT-D9E-A63
1 0.63…1.0 14 100 65 — — 0.5 0.5 0.18 0.25 0.37 0.55 140MT-D9E-B10
1.6 1.0…1.6 22 100 65 — — 0.75 — 0.25 0.55 0.75 1.1 140MT-D9E-B16
2.5 1.6…2.5 35 100 65 0.5 0.5 1 1.5 0.37 0.75 1.1 1.8 140MT-D9E-B25
4 2.5…4.0 56 100 65 0.75 0.75 2 3 0.75 1.5 2.2 3 140MT-D9E-B40
6.3 4.0…6.3 88 100 65 1 1.5 3 5 1.5 2.2 3 4 140MT-D9E-B63
10 6.3…10 140 100 65 2 2 5 7.5 2.2 4 6.3 7.5 140MT-D9E-C10
16 10…16 224 100 65 3 5 10 10 4 7.5 10 13 140MT-D9E-C16
20 14.5…20 280 100 65 5 5 10 15 5.5 10 11 17 140MT-D9E-C20
25 18…25 350 65 50 5 7.5 15 20 5.5 11 15 22 140MT-D9E-C25
29 23…29 406 50 50 7.5 10 20 25 7.5 13 18.5 25 140MT-D9E-C29
32 26.5…32 448 50 50 7.5 10 20 30 7.5 15 20 25 140MT-D9E-C32
36 30…36 432 50 30 10 10 25 30 18.5 20 25 140MT-D9E-C36(2)
40 34…40 480 50 30 10 10 30 30 11 20 24 30 140MT-D9E-C40(2)
D-Frame, Fixed Magnetic (application at output of VFD multi-motor)
1.6 1.0…1.6 88 100 65 — — 0.75 — 0.25 0.55 0.75 — 140MT-D9V-B16
2.5 1.6…2.5 88 100 65 0.5 0.5 1 — 0.37 0.75 1.1 — 140MT-D9V-B25
4 2.5…4.0 88 100 65 0.75 0.75 2 — 0.75 1.5 2.2 — 140MT-D9V-B40
6.3 4.0…6.3 88 100 65 1 1.5 3 — 1.5 2.2 3 — 140MT-D9V-B63
10 6.3…10 140 100 65 2 2 5 — 2.2 4 6.3 — 140MT-D9V-C10
16 10…16 224 100 65 3 5 10 — 4 7.5 10 — 140MT-D9V-C16
20 14.5…20 280 100 65 5 5 10 — 5.5 10 11 — 140MT-D9V-C20
25 18…25 350 65 50 5 7.5 15 — 5.5 11 15 — 140MT-D9V-C25
29 23…29 406 50 50 7.5 10 20 — 7.5 13 18.5 — 140MT-D9V-C29
32 26.5…32 448 50 50 7.5 10 20 — 7.5 15 20 — 140MT-D9V-C32
36 30…36 432 50 30 10 10 25 — — 18.5 20 — 140MT-D9V-C36(2)
40 34…40 480 50 30 10 10 30 — 11 20 24 — 140MT-D9V-C40(2)

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 25


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Table 27 - Motor Protective Switching Devices (Continued)


Max Short-circuit
Rated Motor Current Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Adjustment Magnetic Trip Cat. No.
Current (Ie) [A] Range [A] Current [A] 400V 480V
(Icu) (group motor) 200V 230V 460V 575V 230V 400/415V 500V 690V

F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)


10 6.3…10 130 100 65 2 3 5 7.5 2.2 4 6.3 7.5 140M-F8E-C10
16 10…16 208 100 65 3 5 10 10 4 7.5 10 13 140M-F8E-C16
20 14.5…20 260 100 65 5 5 10 15 5.5 10 11 17 140M-F8E-C20
25 18…25 325 100 65 7.5 7.5 15 20 5.5 11 15 22 140M-F8E-C25
32 23…32 416 65 65 7.5 10 20 30 7.5 15 20 25 140M-F8E-C32
45 32…45 585 65 65 10 15 30 40 13 22 30 40 140M-F8E-C45
25 18…25 416 65 65 7.5 7.5 15 20 5.5 11 15 22 140M-F8T-C25
32 23…32 585 65 65 7.5 10 20 30 7.5 15 20 25 140M-F8T-C32
(1) Horsepower/kW ratings shown are for reference. The final selection of the MPCB/MPSD depends on the actual motor full load current.
(2) Suitable for continuous operation at 90% current rating at 480V only if used in a minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).

Table 28 - High Inrush Motor Protection Switching Devices


Max Short-circuit
Rated Motor Current Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Adjustment Magnetic Trip Cat. No.
400V 480V
Current (Ie) [A] Range [A] Current [A] 200V 230V 460V 575V 230V 400/415V 500V 690V
(Icu) (group motor)
D-Frame, Adjustable Thermal/Fixed Magnetic (18…22 x In)
0.16 0.10…0.16 3.5 100 65 — — — — — 0.02 0.06 0.06 140MT-D9T-A16
0.25 0.16…0.25 5.5 100 65 — — — — — 0.04 0.09 0.09 140MT-D9T-A25
0.4 0.25…0.40 8.8 100 65 — — — — 0.06 0.09 0.12 0.18 140MT-D9T-A40
0.63 0.40…0.63 14 100 65 — — — — 0.09 0.18 0.18 0.25 140MT-D9T-A63
1 0.63…1.0 22 100 65 — — 0.5 0.5 0.18 0.25 0.37 0.55 140MT-D9T-B10
1.6 1.0…1.6 35 100 65 — — 0.75 — 0.25 0.55 0.75 1.1 140MT-D9T-B16
2.5 1.6…2.5 55 100 65 0.5 0.5 1 1.5 0.37 0.75 1.1 1.8 140MT-D9T-B25
4 2.5…4.0 88 100 65 0.75 0.75 2 3 0.75 1.5 2.2 3 140MT-D9T-B40
6.3 4.0…6.3 139 100 65 1 1.5 3 5 1.5 2.2 3 4 140MT-D9T-B63
10 6.3…10 220 100 65 2 2 5 7.5 2.2 4 6.3 7.5 140MT-D9T-C10
16 10…16 320 100 65 3 5 10 10 4 7.5 10 13 140MT-D9T-C16
20 14.5…20 400 100 65 5 5 10 15 5.5 10 11 17 140MT-D9T-C20
25 18…25 450 65 50 5 7.5 15 20 5.5 11 15 22 140MT-D9T-C25
F-Frame, Adjustable Thermal/Fixed Magnetic (16…22 x In)
25 18…25 416 65 65 7.5 7.5 15 20 5.5 11 15 22 140M-F8T-C25
32 23…32 585 65 65 7.5 10 20 30 7.5 15 20 25 140M-F8T-C32
(1) Horsepower/kW ratings shown are for reference. The final selection of the MPCB/MPSD depends on the actual motor full load current.

26 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Table 29 - Motor Circuit Protectors


Max. Short Circuit
Rated Motor Current Nominal Current [kA] Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Operational Adjustment Magnetic Trip Cat. No.
400V 480V
Current (Ie) [A] Range [A] Current [A] 200V 230V 460V 575V 230V 400/415V 500V 690V
(Icu) (group motor)
D-Frame, Fixed Magnetic (14 x In)
0.16 — 2.2 100 65 — — — — — 0.02 0.06 0.06 140MT-D9N-A16
0.25 — 3.5 100 65 — — — — — 0.04 0.09 0.09 140MT-D9N-A25
0.4 — 5.6 100 65 — — — — 0.06 0.09 0.12 0.18 140MT-D9N-A40
0.63 — 8.8 100 65 — — — — 0.09 0.18 0.18 0.25 140MT-D9N-A63
1 — 14 100 65 — — 0.5 0.5 0.18 0.25 0.37 0.55 140MT-D9N-B10
1.6 — 22 100 65 — — 0.75 — 0.25 0.55 0.75 1.1 140MT-D9N-B16
2.5 — 35 100 65 0.5 0.5 1 1.5 0.37 0.75 1.1 1.8 140MT-D9N-B25
4 — 56 100 65 0.75 0.75 2 3 0.75 1.5 2.2 3 140MT-D9N-B40
6.3 — 88 100 65 1 1.5 3 5 1.5 2.2 3 4 140MT-D9N-B63
10 — 140 100 65 2 2 5 7.5 2.2 4 6.3 7.5 140MT-D9N-C10
16 — 224 100 65 3 5 10 10 4 7.5 10 13 140MT-D9N-C16
20 — 280 100 65 5 5 10 15 5.5 10 11 17 140MT-D9N-C20
25 — 350 65 50 5 7.5 15 20 5.5 11 15 22 140MT-D9N-C25
29 — 406 50 50 7.5 10 20 25 7.5 13 18.5 25 140MT-D9N-C29
32 — 448 50 50 7.5 10 20 30 7.5 15 20 25 140MT-D9N-C32
36 — 432 50 30 10 10 25 30 — 18.5 20 25 140MT-D9N-C36(2)
40 — 480 50 30 10 10 30 30 11 20 24 30 140MT-D9N-C40(2)
F-Frame, Fixed Magnetic (13 x In)
25 — 325 100 65 7.5 10 20 25 6.3 11 15 22 140M-F8N-C25
32 — 416 65 65 7.5 10 25 30 7.5 15 20 30 140M-F8N-C32
45 — 585 65 65 10 15 30 40 13 22 30 40 140M-F8N-C45
(1) Horsepower/kW ratings shown are for reference. The final selection of the MCP depends on the actual motor full load current.
(2) Suitable for continuous operation at 90% current rating at 480V only if used in a minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).

Motor Circuit Protectors (Cat. No. 140MT-D9N, 140M-F8N) do not provide thermal protection for themselves nor for downstream
components. You must install a separate protective device against thermal overload, such as an overload relay as part of a
starter combination. In applications that use these devices as the short-circuit protection device of heavy-duty starting motors,
the rated operational current Ie of the devices must be over-sized using the factors in Table 30.

Table 30 - Oversizing for Heavy-duty Starting


Current Range [A] Device Type Class 10 Class 20 Class 30
0.16…10 — — —
16…29 140MT-D9N — — 1.41
32…40 — 1.41 1.73
25…45 140M-F8N — 1.41 1.73

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 27


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Selection Using Application Ratings


See page 42 for combination ratings.
Table 31 - UL/CSA Listed Application Ratings, Motor Protective Switching Devices
UL 60947-4-1 Self-Protected (Type E)
UL 60947-4-1 — Manual Motor Controller Combination Motor Controller
Max. Fuse or Max Short-circuit Current [kA] Cat. No.
Circuit Max Short-circuit Current [kA]
Group Motor Installation Motor Disconnect Tap Conductor Protection
Breaker per
NEC [A] 480V 600V 480V 600V 480Y/277V(1) 600Y/347V(1) 480Y/277V(1) 600Y/347V(1)
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
450 65 50 65 50 65 50 65 50 140MT-C3E-A16
450 65 50 65 50 65 50 65 50 140MT-C3E-A25
450 65 50 65 50 65 50 65 50 140MT-C3E-A40
450 65 50 65 50 65 50 65 50 140MT-C3E-A63
450 65 50 65 50 65 50 65 50 140MT-C3E-B10
450 65 50 65 50 65 50 65 50 140MT-C3E-B16
450 65 30 65 30 65 30 65 30 140MT-C3E-B25
450 65 30 65 30 65 30 65 30 140MT-C3E-B40
450 65 30 65 30 65 — 65 — 140MT-C3E-B63
450 65 30 65 30 65 — 65 — 140MT-C3E-C10
450 30 30 30 30 30 — 30 — 140MT-C3E-C16
450 30 30 30 10 — — — — 140MT-C3E-C20
450 30 18 30 5 — — — — 140MT-C3E-C25
450 30 10 10 -- — — — — 140MT-C3E-C29
450 30 10 10 -- — — — — 140MT-C3E-C32
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
450 65 50 65 50 65 50 65 50 140MT-D9E-A63
450 65 50 65 50 65 50 65 50 140MT-D9E-B10
450 65 50 65 50 65 50 65 50 140MT-D9E-B16
450 65 30 65 30 65 30 65 30 140MT-D9E-B25
450 65 30 65 30 65 30 65 30 140MT-D9E-B40
450 65 30 65 30 65 30 65 30 140MT-D9E-B63
450 65 30 65 30 65 30 65 30 140MT-D9E-C10
450 65 30 65 30 65 30 65 30 140MT-D9E-C16
450 65 30 65 30 65 — 65 — 140MT-D9E-C20
450 50 30 50 30 50 — 50 — 140MT-D9E-C25
450 50 30 50 30 50 — 50 — 140MT-D9E-C29
450 50 30 30 18 30 — 30 — 140MT-D9E-C32
450 30 30 30 18 30 — 30 — 140MT-D9E-C36(2)
450 30 30 30 18 30 — 30 — 140MT-D9E-C40(2)
D-Frame, Adjustable Thermal/Fixed Magnetic (application at output of VFD multi-motor)
450 65 — 65 — 65 — 65 — 140MT-D9V-B16
450 65 — 65 — 65 — 65 — 140MT-D9V-B25
450 65 — 65 — 65 — 65 — 140MT-D9V-B40
450 65 — 65 — 65 — 65 — 140MT-D9V-B63
450 65 — 65 — 65 — 65 — 140MT-D9V-C10
450 65 — 65 — 65 — 65 — 140MT-D9V-C16
450 65 — 65 — 65 — 65 — 140MT-D9V-C20
450 50 — 50 — 50 — 50 — 140MT-D9V-C25
450 50 — 50 — 50 — 50 — 140MT-D9V-C29
450 50 — 30 — 30 — 30 — 140MT-D9V-C32
450 30 — 30 — 30 — 30 — 140MT-D9V-C36(2)

28 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Table 31 - UL/CSA Listed Application Ratings, Motor Protective Switching Devices (Continued)
UL 60947-4-1 Self-Protected (Type E)
UL 60947-4-1 — Manual Motor Controller Combination Motor Controller
Max. Fuse or Max Short-circuit Current [kA] Cat. No.
Circuit Max Short-circuit Current [kA]
Group Motor Installation Motor Disconnect Tap Conductor Protection
Breaker per
NEC [A] 480V 600V 480V 600V 480Y/277V(1) 600Y/347V(1) 480Y/277V(1) 600Y/347V(1)
450 30 — 30 — 30 — 30 — 140MT-D9V-C40(2)
D-Frame, Adjustable Thermal/Fixed Magnetic (18…22 x In)
450 65 50 65 50 65 50 65 50 140MT-D9T-A16
450 65 50 65 50 65 50 65 50 140MT-D9T-A25
450 65 50 65 50 65 50 65 50 140MT-D9T-A40
450 65 50 65 50 65 50 65 50 140MT-D9T-A63
450 65 50 65 50 65 50 65 50 140MT-D9T-B10
450 65 50 65 50 65 50 65 50 140MT-D9T-B16
450 65 30 65 30 65 30 65 30 140MT-D9T-B25
450 65 30 65 30 65 30 65 30 140MT-D9T-B40
450 65 30 65 30 65 30 65 30 140MT-D9T-B63
450 65 30 65 30 65 30 65 30 140MT-D9T-C10
450 65 30 65 30 65 30 65 — 140MT-D9T-C16
450 65 30 65 30 65 — 65 — 140MT-D9T-C20
450 50 30 50 18 50 — 50 — 140MT-D9T-C25
F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)
600 65 30 65 30 65 30 65 30 140M-F8E-C10
600 65 30 65 30 65 30 65 30 140M-F8E-C16
600 65 30 65 30 65 30 65 30 140M-F8E-C20
600 65 30 65 30 65 30 65 30 140M-F8E-C25
600 65 30 65 30 65 30 65 30 140M-F8E-C32
600 65 18 65 18 65 — 65 — 140M-F8E-C45
F-Frame, Adjustable Thermal/Fixed Magnetic (16…22 x In)
600 65 30 65 30 65 30 65 30 140M-F8T-C25
600 65 18 65 18 65 18 65 18 140M-F8T-C32
(1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.
(2) Suitable for continuous operation at 90% current rating at 480V only if used in a minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 29


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Table 32 - UL/CSA Listed Application Ratings, Motor Circuit Protectors


UL 60947-4-1 — Manual Motor Controller
Max. Short Circuit Current [kA]
Max. Fuse or Circuit Cat. No.
Group Motor Installation Motor Disconnect Tap Conductor Protection
Breaker per NEC [A]
480V 600V 480V 600V 480Y/277V(1) 600Y/347V(1)
D-Frame, Fixed Magnetic (14 x In)
450 65 50 65 50 65 50 140MT-D9N-A16
450 65 50 65 50 65 50 140MT-D9N-A25
450 65 50 65 50 65 50 140MT-D9N-A40
450 65 50 65 50 65 50 140MT-D9N-A63
450 65 50 65 50 65 50 140MT-D9N-B10
450 65 50 65 50 65 50 140MT-D9N-B16
450 65 30 65 30 65 30 140MT-D9N-B25
450 65 30 65 30 65 30 140MT-D9N-B40
450 65 30 65 30 65 30 140MT-D9N-B63
450 65 30 65 30 65 30 140MT-D9N-C10
450 65 30 65 30 65 30 140MT-D9N-C16
450 65 30 65 30 65 — 140MT-D9N-C20
450 50 30 50 30 50 — 140MT-D9N-C25
450 50 30 50 30 50 — 140MT-D9N-C29
450 50 30 30 18 30 — 140MT-D9N-C32
450 30 30 30 18 30 — 140MT-D9N-C36(2)
450 30 30 30 18 30 — 140MT-D9N-C40(2)
F-Frame, Fixed Magnetic (13 x In)
600 65 30 65 30 — — 140M-F8N-C25
600 65 30 65 30 — — 140M-F8N-C32
600 65 18 65 18 — — 140M-F8N-C45
(1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.
(2) Suitable for continuous operation at 90% current rating at 480V only if used in a minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).

Table 33 - IEC Application Ratings, Interrupting Rating/Breaking Capacity


Breaking Capacity, IEC 60947-2
230/240V AC 400/415V AC 440/460V AC 500/525V AC 690V AC
Cat. No.
Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse
[kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A]
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
100 100 100 100 100 100 100 100 100 100 140MT-C3E-A16
100 100 100 100 100 100 100 100 100 100 140MT-C3E-A25
100 100 100 100 100 100 100 100 100 100 —(2) 140MT-C3E-A40
100 100 100 100 100 100 100 100 100 100 140MT-C3E-A63
100 100 100 100 —(2) 100 100 —(2) 100 100 —(2) 100 100 140MT-C3E-B10
100 100 —(2) 100 100 100 100 100 100 4 4 16 140MT-C3E-B16
100 100 100 100 100 100 100 100 4 4 20 140MT-C3E-B25
100 100 100 100 100 100 100 100 4 4 35 140MT-C3E-B40
100 100 100 100 100 100 100 100 3 3 50 140MT-C3E-B63
100 100 100 50 80 50 50 80 50 50 63 3 3 50 140MT-C3E-C10
100 100 65 50 80 10 6 80 10 6 80 3 3 63 140MT-C3E-C16
65 50 100 50 15 100 6 6 80 6 6 80 3 2 63 140MT-C3E-C20
65 50 100 15 15 100 6 4 80 6 4 80 3 2 63 140MT-C3E-C25
50 25 125 15 10 125 6 4 100 6 4 100 3 2 80 140MT-C3E-C29
50 25 125 15 10 125 6 4 100 6 4 100 3 2 80 140MT-C3E-C32

30 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Table 33 - IEC Application Ratings, Interrupting Rating/Breaking Capacity (Continued)


Breaking Capacity, IEC 60947-2
230/240V AC 400/415V AC 440/460V AC 500/525V AC 690V AC
Cat. No.
Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse
[kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A]
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
100 100 100 100 100 100 100 100 100 100 140MT-D9E-A63
100 100 100 100 100 100 100 100 100 100 —(2) 140MT-D9E-B10
100 100 100 100 100 100 100 100 100 100 140MT-D9E-B16
100 100 100 100 —(2) 100 100 —(2) 100 100 —(2) 6 4 20 140MT-D9E-B25
100 100 100 100 100 100 100 100 6 4 35 140MT-D9E-B40
—(2)
100 100 100 100 100 100 100 100 6 4 50 140MT-D9E-B63
100 100 100 100 100 100 100 100 6 3 50 140MT-D9E-C10
100 100 100 50 80 50 25 80 50 25 80 4 3 63 140MT-D9E-C16
100 100 100 25 100 50 25 100 50 25 80 4 3 63 140MT-D9E-C20
100 100 65 25 100 35 20 100 35 20 80 4 3 63 140MT-D9E-C25
65 50 125 50 25 125 25 15 125 25 15 100 4 3 80 140MT-D9E-C29
65 50 125 50 25 125 25 15 125 25 15 100 4 3 80 140MT-D9E-C32
50 35 125 50 25 125 12 6 125 12 6 100 3 2 100 140MT-D9E-C36(3)
50 35 125 50 25 125 12 6 125 12 6 100 3 2 100 140MT-D9E-C40(3)
D-Frame, Fixed Magnetic (application at output of VFD multi-motor)
100 100 100 100 100 100 100 100 — — 140MT-D9V-B16
100 100 100 100 100 100 100 100 — — 140MT-D9V-B25
100 100 100 100 —(2) 100 100 —(2) 100 100 —(2) — — 140MT-D9V-B40
100 100 100 100 100 100 100 100 — — 140MT-D9V-B63
—(2)
100 100 100 100 100 100 100 100 — — 140MT-D9V-C10
100 100 100 50 80 50 25 80 50 25 80 — — 140MT-D9V-C16
100 100 100 25 100 50 25 100 50 25 80 — — —(2) 140MT-D9V-C20
100 100 65 25 100 35 20 100 35 20 80 — — 140MT-D9V-C25
65 50 125 50 25 125 25 15 125 25 15 100 — — 140MT-D9V-C29
65 50 125 50 25 125 25 15 125 25 15 100 — — 140MT-D9V-C32
50 35 125 50 25 125 12 6 125 12 6 100 — — 140MT-D9V-C36(3)
50 35 125 50 25 125 12 6 125 12 6 100 — — 140MT-D9V-C40(3)
F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)
100 100 100 50 80 65 50 80 50 50 80 10 10 63 140M-F8E-C10
100 100 100 50 100 65 50 100 50 50 100 10 10 80 140M-F8E-C16
100 100 100 50 100 65 50 100 50 50 100 10 10 80 140M-F8E-C20
—(2)
100 100 100 50 100 65 50 100 50 50 100 10 10 80 140M-F8E-C25
100 100 65 50 125 65 50 125 50 50 125 10 6 100 140M-F8E-C32
100 100 65 50 125 50 50 125 50 50 125 10 6 100 140M-F8E-C45

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 31


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Product Selection

Table 33 - IEC Application Ratings, Interrupting Rating/Breaking Capacity (Continued)


Breaking Capacity, IEC 60947-2
230/240V AC 400/415V AC 440/460V AC 500/525V AC 690V AC
Cat. No.
Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse Icu Ics Back-up Fuse
[kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A] [kA] [kA] Rating(1) [A]
D-Frame, High Inrush, Adjustable Thermal/Fixed Magnetic (18…22 x In)
100 100 100 100 100 100 100 100 100 100 140MT-D9T-A16
100 100 100 100 100 100 100 100 100 100 140MT-D9T-A25
100 100 100 100 100 100 100 100 100 100 140MT-D9T-A40
—(2)
100 100 100 100 100 100 100 100 100 100 140MT-D9T-A63
100 100 100 100 100 100 100 100 100 100 140MT-D9T-B10
—(2) —(2) —(2)
100 100 100 100 100 100 100 100 100 100 140MT-D9T-B16
100 100 —(2) 100 100 100 100 100 100 6 4 20 140MT-D9T-B25
100 100 100 100 100 100 100 100 6 4 35 140MT-D9T-B40
100 100 100 100 100 100 100 100 6 4 50 140MT-D9T-B63
100 100 100 100 100 100 100 100 6 3 50 140MT-D9T-C10
100 100 100 50 80 50 25 80 50 25 80 4 3 63 140MT-D9T-C16
100 100 100 25 100 50 25 100 50 25 80 4 2 63 140MT-D9T-C20
100 100 65 25 100 50 12 100 50 12 80 4 2 63 140MT-D9T-C25
F-Frame, High Inrush, Adjustable Thermal/Fixed Magnetic (16…22 x In)
100 100 65 50 100 65 50 100 50 50 100 10 6 80 140M-F8T-C25
—(2)
100 100 65 50 125 65 50 125 50 50 125 10 6 100 140M-F8T-C32
D-Frame, Motor Circuit Protectors, Fixed Magnetic (14 x In)
100 100 100 100 100 100 100 100 100 100 140MT-D9N-A16
100 100 100 100 100 100 100 100 100 100 140MT-D9N-A25
100 100 100 100 100 100 100 100 100 100 140MT-D9N-A40
—(2)
100 100 100 100 100 100 100 100 100 100 140MT-D9N-A63
100 100 100 100 100 100 100 100 100 100 140MT-D9N-B10
—(2) —(2) —(2)
100 100 100 100 100 100 100 100 100 100 140MT-D9N-B16
100 100 —(2) 100 100 100 100 100 100 6 4 20 140MT-D9N-B25
100 100 100 100 100 100 100 100 6 4 35 140MT-D9N-B40
100 100 100 100 100 100 100 100 6 4 50 140MT-D9N-B63
100 100 100 100 100 100 100 100 6 3 50 140MT-D9N-C10
100 100 100 50 80 50 25 80 50 25 80 4 3 63 140MT-D9N-C16
100 100 100 25 100 50 25 100 50 25 80 4 3 63 140MT-D9N-C20
100 100 65 25 100 35 20 100 35 20 80 4 3 63 140MT-D9N-C25
65 50 125 50 25 125 25 15 125 25 15 100 4 3 80 140MT-D9N-C29
65 50 125 50 25 125 25 15 125 25 15 100 4 3 80 140MT-D9N-C32
50 35 125 50 25 125 12 6 125 12 6 100 3 2 100 140MT-D9N-C36(3)
50 35 125 50 25 125 12 6 125 12 6 100 3 2 100 140MT-D9N-C40(3)
F-Frame, Motor Circuit Protectors, Fixed Magnetic (13 x In)
100 100 100 100 50 100 65 50 100 50 50 100 10 10 80 140M-F8N-C25
100 100 125 65 50 125 65 50 125 50 50 125 10 6 100 140M-F8N-C32
100 100 125 65 50 125 50 50 125 50 50 125 10 6 100 140M-F8N-C45
(1) Back-up fuses are type gG, aM.
(2) No Back-up fuse required if Icc<Ics.
(3) Suitable for continuous operation at 90% current rating at 480V only if used in a minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).

32 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Accessories
Table 34 - Auxiliary Contacts
Operator Position(1)
OFF ON Tripped Term. Contact Connection
Description For Use With Cat. No.
No. Description Diagram(2)

140MT-C, D
140UT-D 140MT-C-AFA10
O X O 13-14 N.O. Aux
140M-F 140M-C-AFA10

X O X 11-12 N.C. Aux 140M-F 140M-C-AFA01

O X O 13-14 N.O. Aux 13 21


140MT-C, D 140MT-C-AFA11
X O X 21-22 N.C. Aux 14 22
140UT-D
Front-Mounted Auxiliary Contact
• 1-pole or 2-pole O X O 13-14 N.O. Aux 13 21
• No additional space required
• Only one per device 14 22
140M-F 140M-C-AFA11
X O X 21-22 N.C. Aux

O X O 13-14 N.O. Aux


140MT-C, D 140MT-C-AFA20
O X O 23-24 N.O. Aux 140UT-D

O X O 13-14 N.O. Aux


140M-F 140M-C-AFA20
O X O 23-24 N.O. Aux

X O X 11-12 N.C. Aux


140M-F 140M-C-AFA02
X O X 21-22 N.C. Aux

O X O 33-34 N.O. Aux


140MT-C, D
140UT-D 140MT-C-ASA20
O X O 43-44 N.O. Aux
O X O 33-34 N.O. Aux
140M-F 140M-C-ASA20
O X O 43-44 N.O. Aux
X O X 31-32 N.C. Aux 31 41

Right Side-Mounted Auxiliary Contact 140MT-C, D 140MT-C-ASA02


• 2-pole X O X 41-42 N.C. Aux 32 42
140UT-D
• Adds 9 mm to the width of the
device X O X 31-32 N.C. Aux 31 41

• One per device 140M-F 140M-C-ASA02


32 42
• Not suitable for UL 489 applications X O X 41-42 N.C. Aux

O X O 33-34 N.O. Aux


140MT-C, D 140MT-C-ASA11
X O X 41-42 N.C. Aux 140UT-D

O X O 33-34 N.O. Aux


140M-F 140M-C-ASA11
X O X 41-42 N.C. Aux

(1) X = Contact Closed; O = Contact Open


(2) Connection Diagram Reference:

140M/MT Operator

Overload (thermal) Trip


I >> Short-circuit (magnetic) Trip

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 33


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Table 35 - Trip Contacts


Operator Position(1)
OFF ON Tripped Term. Contact Connection
Description For Use With Cat. No.
No. Description Diagram(2)

O X O 13-14 N.O. Aux


N.O. Trip 140MT-C, D
140UT-D 140MT-C-AFAR10A10
O O X 27-28 (short-circuit
and overload)
O X O 13-14 N.O. Aux
N.O. Trip 140M-F 140M-C-AFAR10A10
O O X 27-28 (short-circuit
and overload)
X O X 11-12 N.C. Aux 11 27

N.O. Trip 140MT-C, D 140MT-C-AFAR10A01


O O X 27-28 (short-circuit 140UT-D
Front-Mounted Trip Contact 12 28
and overload)
• 2-pole
• Indicates tripping of device X O X 11-12 N.C. Aux 11 27

• No additional space required N.O. Trip 140M-F 140M-C-AFAR10A01


O O X 27-28 (short-circuit
12 28
and overload)
O X O 13-14 N.O. Aux 13 25

N.C. Trip 140MT-C-AFAR01A10


X X O 25-26 (short-circuit
and overload) 14 26
140MT-C, D
N.O. Trip 140UT-D
O O X 17-18 (short-circuit
17 27
and overload) 140MT-C-AFAR10M10
N.O. Trip I >>

O O X 27-28 18 28
(short-circuit)
N.O. Trip
O O X 57-58 (short-circuit
57 67
and overload) 140M-C-ASAR10M10
I>>
N.O. Trip
O O X 67-68 58 68
(short-circuit)
N.O. Trip
O O X 57-58 (short-circuit
Right-Side Mounted Trip and overload) 57 65
140M-C-ASAR10M01
Contact I>>
N.C. Trip
• 2-pole X X O 65-66 (short-circuit)
58 66

• Indicates tripping of the


device N.C. Trip
• Adds 9 mm to the width of the X X O 55-56 (short-circuit
and overload) 55 67 140M-F 140M-C-ASAR01M10
device
• One only per device N.O. Trip I >>

O O X 67-68 56 68
• A right-side mounted (short-circuit)
auxiliary contact may be N.C. Trip
tandem mounted on top of X X O 55-56 (short-circuit
this trip contact and overload) 55 65
140M-C-ASAR01M01
I >>
N.C. Trip
X X O 65-66 56 66
(short-circuit)
N.O. Trip
O O X 77-78 (short-circuit) 77 65
140M-C-ASAM11
N.C. Trip I >>
X X O 65-66 (short-circuit) 78 66

(1) X = Contact Closed; O = Contact Open


(2) Connection Diagram Reference:

140M/MT Operator

Overload (thermal) Trip


I >> Short-circuit (magnetic) Trip

34 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Table 36 - Undervoltage Trip Units


Description Connection Diagram(1) Trip Rating For Use With Cat. No.
24V, 50 Hz/24…28V, 60 Hz 140MT-C-UXK
120V, 60 Hz 140MT-C-UXD
220…230V, 50 Hz 140MT-C, D 140MT-C-UXF
240…260V, 60 Hz 140UT-D 140MT-C-UXA
380…400V, 50 Hz 140MT-C-UXN
480V, 60 Hz/415V, 50 Hz 140MT-C-UXB
24V, 60 Hz 140M-C-UXJ
Undervoltage Trip 24V, 50 Hz 140M-C-UXK
• Left-side mounted D1
120V, 60 Hz 140M-C-UXD
• Adds 18 mm to the width of the device U<
• Automatically trips MPCB/MCP when 110V, 50 Hz 140M-C-UXC
I >>
D2
voltage falls below 35…70% 208V, 60 Hz 140M-C-UXH
220…230V, 50 Hz 140M-C-UXF
140M-F
240…260V, 60 Hz 140M-C-UXA
277V, 60 Hz 140M-C-UXT
380…400V, 50 Hz 140M-C-UXN
480V, 60 Hz/415V, 50 Hz 140M-C-UXB
575V, 60 Hz/500V, 50 Hz 140M-C-UXM
600V, 60 Hz 140M-C-UXVC
24V, 60 Hz 140M-C-UCJ
24V, 50 Hz 140M-C-UCK
120V, 60 Hz 140M-C-UCD
110V, 50 Hz 140M-C-UCC
Undervoltage Trip D1 07
208V, 60 Hz 140M-C-UCH
• Left-side mounted
• 2 early make contacts integrated 220…230V, 50 Hz 140M-C-UCF
U< 140M-F
• Adds 18 mm to the width of the device 240…260V, 60 Hz 140M-C-UCA
• Automatically trips MPCB/MCP when I> D2 08
277V, 60 Hz 140M-C-UCT
voltage falls below 35…70%
380…400V, 50 Hz 140M-C-UCN
480V, 60 Hz/415V, 50 Hz 140M-C-UCB
575V, 60 Hz/500V, 50 Hz 140M-C-UCM
600V, 60 Hz 140M-C-UCVC
(1) Connection Diagram Reference:

140M/MT Operator

Overload (thermal) Trip


I >> Short-circuit (magnetic) Trip

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 35


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Table 37 - Shunt Trip Units


Description Connection Diagram(1) Trip Rating For Use With Cat. No.
24V, 50 Hz/24…28V, 60 Hz 140MT-C-SNK
110V, 50 Hz/120V, 60 Hz 140MT-C-SND
220…230V, 50 Hz 140MT-C-SNF
240…260V, 60 Hz 140MT-C, D 140MT-C-SNA
277V, 60 Hz 140UT-D 140MT-C-SNT
380…400V, 50 Hz 140MT-C-SNN
480V, 60 Hz/415V, 50 Hz 140MT-C-SNB
Shunt Trip 24V DC 140MT-C-SNZJ
• Left-side mounted 24V, 60 Hz 140M-C-SNJ
C1
• Adds 18 mm to the width of the device 24V, 50 Hz 140M-C-SNK
• Provides remote tripping of the MPCB/
MCP 110V, 50 Hz/120V, 60 Hz 140M-C-SND
• Maximum on time for DC operated I >>
C2 208V, 60 Hz 140M-C-SNH
devices: 5 sec. 220…230V, 50 Hz 140M-C-SNF
240…260V, 60 Hz 140M-C-SNA
140M-F
277V, 60 Hz 140M-C-SNT
380…400V, 50 Hz 140M-C-SNN
480V, 60 Hz/415V, 50 Hz 140M-C-SNB
575V, 60 Hz/500V, 50 Hz 140M-C-SNM
600V, 60 Hz 140M-C-SNVC
24V DC 140M-C-SNZJ
(1) Connection Diagram Reference:

140M/MT Operator

Overload (thermal) Trip


I >> Short-circuit (magnetic) Trip

Table 38 - Additional Accessories


Description For Use With Cat. No.

140MT-C, D 140MT-C-CA
Anti-Tamper Shield
• Provides protection against inadvertent adjustment of the current setting
• Must be ordered in multiples of 10 (10 pieces/package)
140M-F 140M-C-CA

Blue 140MT-C-KB
Lockable Twist Knob
Black 140MT-C, D 140MT-C-KN
• For one padlock 4…6 mm (3/16 in.) diameter shackle 140UT- D
• Can be locked in OFF position Red/Yellow 140MT-C-KRY
Black 140M-C-KN1
Lockable Twist Knob
• For one padlock 5 mm (3/16 in.) diameter shackle 140M-F
• Can be locked in OFF position Red/Yellow 140M-C-KRY1

140MT-C-KB
Locking Tag 140MT-C-KN 140MT-C-M3
• Padlock attachment to the lockable handles 140MT-C-KRY
• Up to three padlocks 4…8 mm (5/16 in.) diameter shackle 140M-C-KN1 140M-C-M3
140M- C-KRY1

36 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Table 38 - Additional Accessories (Continued)


Description For Use With Cat. No.
140MT-C, D 140MT-C-DN66
140UT- D
Black
Door Coupling Handle
• For 3 padlocks 4…8 mm (5/16 in.) in diameter 140M-F 140M-C-DN66
• IP66 Protection/Type 1, 4, 4X, 12 Interlock override capability
• Can be modified for locking in ON position 140MT-C, D
140UT- D 140MT-C-DRY66
• Ships with coupling — order extension shaft and legend plate separately
Red/Yellow
140M-F 140M-C-DRY66

Extension Shaft (Short length)


• Cut to required length for mounting depth (front of DIN Rail to front of enclosure door)
140MT-C: 136 mm (5.35 in) 140MT-C-DSS
140MT-D: 143 mm (5.63 in)
140UT-D: 143 mm (5.63 in)
• For Cat. Nos. 140MT-C-DN66 and 140MT-C-DRY66 handles
Extension Shaft (Standard length)
• Cut to required length for mounting depth (front of DIN Rail to front of enclosure door)
140MT-C: 136…358 mm (5.35…14.1 in) 140MT-C, D
140MT-C-DS
140MT-D: 143…364 mm (5.63…14.33 in) 140UT- D
140UT-D: 143…364 mm (5.63…14.33 in)
• For Cat. Nos. 140MT-C-DN66 and 140MT-C-DRY66 handles
Extension Shaft (Extended length)
• Cut to required length for mounting depth (front of DIN Rail to front of enclosure door)
140MT-C: 136…507 mm (5.35…19.96 in) 140MT-C-DSL
140MT-D: 143…513 mm (5.63…20.2 in)
140UT-D: 143…513 mm (5.63…20.2 in)
• For Cat. Nos. 140MT-C-DN66 and 140MT-C-DRY66 handles
Extension Shaft Standard Length 140M-C-DS
• Cut to required length for mounting depth (front of DIN Rail to front of enclosure 140M-F
door) Extended Length 140M-C-DSL
• For Cat. Nos. 140M-C-DN66 and 140M-C-DRY66 handles
140MT-C, D
140UT- D 140MT-SB
Door Coupling Handle Black
• Type 3, 3R, 4, 4X, 12 (IP66) 140M-F 140M-SB
• For up to 2 padlocks
• Fits in 30.5 mm cutout 140MT-C, D
• Requires 140MT-C-DNC (140MT-C, 140MT-D, 140UT-D) or 140M-C-DNC (140M-F) 140UT- D 140MT-SY
coupler Red/Yellow
140M-F 140M-SY

140MT-SB, 140MT-S1
140MT-SY
12 in. (30.48 cm)
140M-SB, 140M-S1
Extension Shaft 140M-SY
• Cut to required length for mounting depth (front of DIN Rail to front of enclosure
door) 140MT-SB, 140MT-S2
140MT-SY
21 in. (53.34 cm)
140M-SB, 140M-S2
140M-SY

Coupler 140MT-C, D 140MT-C-DNC


• Included with Cat. Nos. 140MT-C-DN66 and 140MT-C-DRY66 140UT- D

Coupler
140M-F 140M-C-DNC
• Included with Cat. Nos. 140M-C-DN66 and 140M-C-DRY66

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 37


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Table 38 - Additional Accessories (Continued)


Description For Use With Cat. No.

Extension Shaft Support 140MT-C, D


140UT- D 140MT-C-SHS
• Provides consistent alignment of the140M/MT-C-DS and 140M/MT-C-DSL shafts with the
140M/MT-C-DN66 or 140M/MT-C-DRY66 door coupling handles
• Recommended for shaft lengths >200 mm
• Snaps on the right side of the 140MT-C, -D, 140M-F, or 140UT-D device and allows the addition of one
side-mounted auxiliary contact.
• Width: 9 mm. 140M-F 140M-C-SHS
• For use with screw-mounted or hat rail mounted devices.

Marking: 140MT-C-DN66 140MT-C-DFCN


"Hauptschalter"
and "Main Switch" 140M-C-DN66 140M-C-DFCN
Legend Plate
Marking: "Not- 140MT-C-DRY66 140MT-C-DFCRY
Aus" and
"Emergency Off" 140M-C-DRY66 140M-C-DFCRY

140MT-C, D
Screw Adapter 140UT- D 140MT-C-N45
• For screw arrangement of a motor protection circuit breaker
• Must be ordered in multiples of 10 (10 pieces/pkg) 140M-F 140M-C-N45

Table 39 - Modules and Adapters


Description For Use With Cat. No.
ECO Connecting Module — 12 A (IEC), 11 A (UL)
• For DOL and reversing starters
140MT-C to 100-K 140MT-C-PEK12
• Eco-starters mount on single DIN Rail (140MT on DIN Rail)
• Electrical and mechanical interconnection of 140MT and 100-K contactors
140MT-C to 100(S)-E09…16(1) 140MT-C-PE16
ECO Connecting Modules — 18 A (IEC), 17 A (UL) 140MT-C to 100(S)-E09QJ…16QJ 140MT-C-PSE16
• Eco-starters mount on single DIN Rail (140MT on DIN Rail)
(1) 140MT-D-PE16
• Electrical and mechanical interconnection of 140MT MPCB and 100-E contactors 140MT-D to 100(S)-E09…16
140MT-D to 100(S)-E09QJ…16QJ 140MT-D-PSE16
ECO Connecting Modules — 23 A (IEC), 22 A (UL) 140MT-C to 100-C09…C23 140MT-C-PEC23
• Eco-starters mount on single DIN Rail (140MT on DIN Rail)
• Electrical and mechanical interconnection of 140MT MPCB and 100-C contactors 140MT-D to 100-C09…C23 140MT-D-PEC23
ECO Connecting Modules — 30 A (IEC), 30 A (UL)
• Eco-starters mount on single DIN Rail (140MT on DIN Rail) 140MT-D to 100-C30…C37 140MT-D-PEC37
• Electrical and mechanical interconnection of 140MT MPCB and 100-C contactors
140MT-C to 100(S)-E26…38(1) 140MT-C-PE38
ECO Connecting Modules — 40 A (IEC), 34 A (UL) 140MT-C to 100(S)-E26QJ…38QJ 140MT-C-PSE38
• Eco-starters mount on single DIN Rail (140MT on DIN Rail)
• Electrical and mechanical interconnection of 140MT MPCB and 100-E contactors 140MT-D to 100(S)-E26…38(1) 140MT-D-PE38
140MT-D to 100(S)-E26QJ…38QJ 140MT-D-PSE38
Connecting Modules — 23 A (IEC), 30 A (UL) and 30 A (IEC), 30 A (UL) 140MT-C to 100-C09…C23 140MT-C-PNC23
• Contactor and MPCB MUST BE mounted separately on (2) DIN Rails Electrical 140MT-D to 100-C09…C23 140MT-D-PNC23
interconnection of 140MT and 100-C (with AC coils) 140MT-D to 100-C30…C37 140MT-D-PNC37
Connecting Modules — 25 and 45 A 140M-F to 100-C30…C37 140M-F-PNC37
• Contactor and MPCB MUST BE mounted separately on (2) DIN Rails Electrical 140M-F to 100-C43 140M-F-PNC43
interconnection of 140M-F and 100-C (with AC coils) 140M-F to 100-C30…C43 140M-F-PSC43
140MT-C, -D 140MT-C-TE
Spacing Adapter
• Required for self-protected combination motor controller (Type E) applications of
Bul. 140MT-C, -D, and 140M-F MPCBs. Not for use with bus bars. 140M-F 140M-F-TE

(1) Not suitable for 100(S)-E09...38QJ or 300(S)-TO...BOQJ contactors.

38 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Accessories

Table 40 - Other Accessories


Description For Use With Cat. No.
140MT-C 140MT-C-WBE
Feeder Block for Compact Busbar
• Supply of compact busbars
• Increases terminal capacity 140M-F 140M-F-WBE

Feeder Terminal for Compact Busbar 140MT-C, -D 140MT-C-WTEN


• For supply of compact busbars
• Top feed — overlaps compact busbar 140M-F 140M-F-WTE
• Meets UL Type E spacing requirements
2 connections 140MT-C-W452
Three-phase Compact Busbar for MPCBs — 64 A Max Continuous Current 3 connections 140MT-C-W453
140MT-C, -D
• 45 mm (1.77 in.) spacing
4 connections 140UT-D 140MT-C-W454
• For use with front-mounted auxiliary contact
5 connections 140MT-C-W455
2 connections 140MT-C-W542
Three-phase Compact Busbar for MPCBs — 64 A Max Continuous Current 3 connections 140MT-C-W543
140MT-C, -D
• 54 mm (2.13 in.) spacing
4 connections 140UT-D 140MT-C-W544
• For use with side-mounted auxiliary contact
5 connections 140MT-C-W545
Three-phase Compact Busbar for 45 A Motor Protection Circuit Breakers 2 connections 140M-F-W542
— 115 A Max. Continuous Current 3 connections 140M-F-W543
140M-F
• 54 mm (2.13 in.) spacing
• For use with front-mounted auxiliary contact 4 connections 140M-F-W544
Three-phase Compact Busbar for 45 A Motor Protection Circuit Breakers 2 connections 140M-F-W632
— 115 A Max. Continuous Current 3 connections 140M-F-W633
140M-F
• 63 mm spacing
• For use with side-mounted auxiliary contact 4 connections 140M-F-W634

140MT-C, -D 140MT-C-WSN
Terminal Cover
• For covering of unused compact bus bar terminals IP2X finger protection
• Must be ordered in multiples of 10
• 10 pieces/pkg
140M-F 140M-F-WS

Top Hat Rail Adapter — 10 mm


• Adjusts the depth of the 140MT-C to the 140MT-D
• Allows the use of compact busbars across both frame sizes 140MT-C 140MT-KBH
• Must be ordered in multiples of 10
• 10 pieces/pkg

DIN (#3) symmetrical hat rail 140MT-C, -D


• 35 mm x 7.5 mm x 1 m (1.4 x 0.3 x 39 in.) long 140UT-D 199-DR1
• 10 pieces/package 140M-F

DIN (#3) Symmetrical Rail


• 35 mm x 15 mm x 1 m (1.4 x 0.6 x 39 in.) long 140MT-C, -D
140UT-D 1492-DR9
• Top Hat Rail (DIN #3 Symmetrical Rail) 140M-F
• 5 pieces/package

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 39


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Specifications
Table 41 - General Data
Attribute 140MT-C 140MT-D 140M-F
IEC IEC/EN 60947–2, IEC/EN 60947-4-1
Standards compliance
cULus UL 60947-4-1, CSA C22.2, No. 60947-4-1
Certifications Regional CCC, EAC, CE, cULus Listed, IEC, CB Scheme cULus Listed, CCC, EAC, CE
IEC [V] 690
Rated Insulation Voltage Ui
UL/CSA [V] 600
Pollution degree 3
Rated Impulse Withstand Main circuits Uimp/Overvoltage Category 6 kV/III, 8 kV (Disconnect)
Voltage Uimp
Auxiliary circuits Uimp /Overvoltage Category 6 kV/III
Rated Frequency [Hz] 45-65
IEC 60947-2 (Circuit breaker) A
Utilization Category
IEC 60947-4-1 (Motor starter) AC-3
Mechanical [operations] 100,000 30,000
Life Span
Electrical (Ie max.) [operations] 100,000 30,000
Switching Frequency [operations/hour] max. 25
Storage [ °C ( °F)] -40…+85 (-40…185)
Ambient Temperature
Operation [ °C ( °F)] -25…+70 (-13…158)
Climatic resistance Operating Humidity/Moisture heat (60068-2-3) 5…95% Non-condensing
Site Altitude [m] to 2000 N.N. (6561 ft)
Protection Class IP2X from all directions
ON 15 G/11 ms
Resistance to Shock, Transport (60068-2-27)
OFF 30 G/11 ms
Resistance to Vibration, Operation (60068-2-6) 5G
up to 40 °C (104 °F) ambient temperature [A] 0.1…32 0.63…40 6.3…45
Rated Thermal Current Ith
up to 60 °C (140 °F) ambient temperature [A] 0.1…32 0.63…40 6.3…45
Rated Supply Current Ie [A] 0.1…32 0.63…40 6.3…45
40 °C (104 °F) [A] no reduction
Dependence on 50 °C (122 °F) [A] no reduction
Temperature 60 °C (140 °F) [A] no reduction
70 °C (158 °F) [A] 15% current reduction of the upper rated current Ie
IEC 60947-4-1 Motor protection
Overload Protection Characteristics (except Cat. Nos. 140MT-D9N, 140M-F9N)
Ambient Temperature Compensation [ °C ( °F)] -25…+60 (-13…+140)
Phase-loss Protection Differential release
Trip class 10 (except Cat. Nos. 140MT-D9N, 140M-F8N) fixed setting
Magnetic Release fixed setting
for E, N Version [A] 14 x Ie max.(1) 13 x Ie max
Release current (±20%) for E, N Version C36, C40 [A] 12 x Ie max.(1) —
for T Version [A] 18…22 x Ie max.(2)

Total Power loss Pv Circuit Breaker at rated load/ [W] 4…11 4…14 7…22
operating temp.
Main Disconnect Switch Application Yes, with accessories
140MT-D…C36, -C40: Suitable for continuous operation at 90% current rating at 480V only if used in a
minimum enclosure size of 250 x 175 x 150 mm (10 x 7 x 6 in).
Application Conditions For utilization outside North America, assemblies (of products) shall comply to the IEC 61439-1 requirements
140M and 140MT manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive
or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments.
(1) Ie max. = maximum values of setting ranges fixed magnetic setting for 140MT-D9V; see ratings.
(2) Ie max. = maximum values of setting ranges; see ratings.

40 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Table 42 - MPCB Connecting Characteristics


No. of
Connection 140MT-C, 140MT-D ≤ 16 A 140MT-C, 140MT-D > 16 A 140M-F
Conductors

Type of terminals
Screw Clamp up to 16 A, M4 Screw Clamp greater than 16 A, M4
Connection Screw Pozidriv No.2/Blade No.3 Pozidriv No.2/Blade No.3 Pozidriv No.2/Blade No.3
2 2
1 1…6 mm 1.5…10 mm 2.5…25 mm2
Solid or stranded 1…2.5 mm2 1.5…4 mm2
2 2.5…25 mm2
2.5…6 mm2 4…10 mm2
1 1…6 mm2 1.5…10 mm2 2.5…25 mm2
Flexible with
ferrule (end sleeve) 1…2.5 mm2 1.5…4 mm2
2 2.5…25 mm2
2.5…4 mm2 4…10 mm2
Wiring
1 1.5…6 mm2 2.5…10 mm2 16…25 mm2
Finely stranded 1.5…4 mm2 2.5…6 mm2
2 16…25 mm2
2.5…6 mm2 4…10 mm2
Cross section per 1 No. 14…10 AWG No. 14…8 AWG No.14…8
UL/CSA solid, No. 14…10 AWG
stranded 2 No. 14…10 AWG No.14…8
No. 12…8 AWG
Stripping length 10 mm (0.39 in.) 10 mm (0.39 in.) 10 mm (0.39 in.)
Tightening torques [N•m]/[lb•in] 2…2.5/18…22 2…2.5/18…22 3…3.5/27…30

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 41


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Combination Ratings

Bulletin 140MT Devices with Bulletin 100-K Miniature IEC Contactors


Table 43 - UL 60947 Application Ratings, MPSDs and MCPs with Bulletin 100-K Miniature IEC Contactors
UL 60947-4-1 Manual Motor Controller UL 60947-4-1 Type F
Group Motor Installation Motor Disconnect Combination Motor Controller
Cat. No. Max. Fuse or Max Short-circuit Current Max Short-circuit Current
Minimum Max Short-circuit Current [kA]
Circuit Breaker [kA] [kA] Minimum
Contactor Size
per NEC [A] Contactor Size
480V 600V 480V 600V 480Y/277V(1) 600Y/347V(1)
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-C3E-A16 450 100-K05 65 50 65 50 100-K05 65 50
140MT-C3E-A25 450 100-K05 65 50 65 50 100-K05 65 50
140MT-C3E-A40 450 100-K05 65 50 65 50 100-K05 65 50
140MT-C3E-A63 450 100-K05 65 50 65 50 100-K05 65 50
140MT-C3E-B10 450 100-K05 65 50 65 50 100-K05 65 50
140MT-C3E-B16 450 100-K05 65 50 65 50 100-K05 65 50
140MT-C3E-B25 450 100-K05 65 30 65 30 100-K05 65 30
140MT-C3E-B40 450 100-K05 65 30 65 30 100-K05 65 30
140MT-C3E-B63 450 100-K05 65 30 65 30 100-K05 65 —
140MT-C3E-C10 450 100-K09 65 30 65 30 100-K09 65 —
140MT-C3E-C16 450 100-K12 30 30 30 30 100-K12 30 —
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-D9E-A63 450 100-K05 65 50 65 50 100-K05 65 50
140MT-D9E-B10 450 100-K05 65 50 65 50 100-K05 65 50
140MT-D9E-B16 450 100-K05 65 50 65 50 100-K05 65 50
140MT-D9E-B25 450 100-K05 65 30 65 30 100-K05 65 30
140MT-D9E-B40 450 100-K05 65 30 65 30 100-K05 65 30
140MT-D9E-B63 450 100-K05 65 30 65 30 100-K05 65 30
140MT-D9E-C10 450 100-K09 65 30 65 30 100-K09 65 30
140MT-D9E-C16 450 100-K12 65 30 65 30 100-K12 65 30
(1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

42 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Bulletin 140MT/M Devices with Bulletin 100-C IEC Contactors


Table 44 - UL 60947 Application Ratings, MPSDs with Bulletin 100-C IEC Contactors
UL 60947-4-1 Manual Motor Controller UL 60947-4-1 Type F
Group Motor Installation Motor Disconnect Combination Motor Controller
Cat. No. Max. Fuse or Minimum Max Short-circuit Max Short-circuit
Circuit Breaker Contactor Minimum Max Short-circuit Current [kA]
Current [kA] Current [kA] Contactor
per NEC [A] Size
480V 600V 480V 600V Size 480Y/277V(1) 600Y/347V(1)
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-C3E-A16 450 100-C09 65 50 65 50 100-C09 65 50
140MT-C3E-A25 450 100-C09 65 50 65 50 100-C09 65 50
140MT-C3E-A40 450 100-C09 65 50 65 50 100-C09 65 50
140MT-C3E-A63 450 100-C09 65 50 65 50 100-C09 65 50
140MT-C3E-B10 450 100-C09 65 50 65 50 100-C09 65 50
140MT-C3E-B16 450 100-C09 65 50 65 50 100-C09 65 50
140MT-C3E-B25 450 100-C09 65 30 65 30 100-C09 65 30
140MT-C3E-B40 450 100-C09 65 30 65 30 100-C09 65 30
140MT-C3E-B63 450 100-C09 65 30 65 30 100-C09 65 —
140MT-C3E-C10 450 100-C09 65 30 65 30 100-C09 65 —
140MT-C3E-C16 450 100-C12 30 30 30 30 100-C12 30 —
140MT-C3E-C20 450 100-C16 30 30 30 10 — — —
450 100-C23 30 18 10 5 — — —
140MT-C3E-C25
450 100-C30 30 18 30 5 — — —
140MT-C3E-C29 450 100-C30 30 10 10 — — — —
140MT-C3E-C32 450 100-C37 30 10 10 — — — —
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-D9E-A63 450 100-C09 65 50 65 50 100-C09 65 50
140MT-D9E-B10 450 100-C09 65 50 65 50 100-C09 65 50
140MT-D9E-B16 450 100-C09 65 50 65 50 100-C09 65 50
140MT-D9E-B25 450 100-C09 65 30 65 30 100-C09 65 30
140MT-D9E-B40 450 100-C09 65 30 65 30 100-C09 65 30
140MT-D9E-B63 450 100-C09 65 30 65 30 100-C09 65 30
140MT-D9E-C10 450 100-C09 65 30 65 30 100-C09 65 30
140MT-D9E-C16 450 100-C12 65 30 65 30 100-C12 65 30
140MT-D9E-C20 450 100-C23 65 30 65 30 100-C23 65 —
140MT-D9E-C25 450 100-C23 50 30 50 30 100-C23 50 —
140MT-D9E-C29 450 100-C30 50 30 50 30 100-C30 50 —
140MT-D9E-C32 450 100-C37 50 30 30 18 100-C37 30 —
140MT-D9E-C36 450 100-C37 30 30 30 18 100-C37 30 —
140MT-D9E-C40 450 100-C37 30 30 30 18 100-C37 30 —
F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)
140M-F8E-C10 600 100-C30 65 30 65 30 100-C30 65 30
140M-F8E-C16 600 100-C30 65 30 65 30 100-C30 65 30
140M-F8E-C20 600 100-C30 65 30 65 30 100-C30 65 30
140M-F8E-C25 600 100-C30 65 30 65 30 100-C30 65 30
140M-F8E-C32 600 100-C30 65 30 65 30 100-C30 65 30
140M-F8E-C45 600 100-C37 65 18 65 18 100-C37 65 —
(1) For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 43


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Table 45 - UL 60947 Application Ratings, MCPs with Bulletin 100-C IEC Contactors
UL 60947-4-1 Manual Motor Controller
Group Motor Installation Motor Disconnect
Cat. No. Max. Fuse or Circuit Minimum Contactor Max Short-circuit Current [kA] Max Short-circuit Current [kA]
Breaker per NEC [A] Size
480V 600V 480V 600V
D-Frame, Motor Circuit Protectors, Fixed Magnetic (14 x In)
140MT-D9N-A16 450 100-C09 65 50 65 50
140MT-D9N-A25 450 100-C09 65 50 65 50
140MT-D9N-A40 450 100-C09 65 50 65 50
140MT-D9N-A63 450 100-C09 65 50 65 50
140MT-D9N-B10 450 100-C09 65 50 65 50
140MT-D9N-B16 450 100-C09 65 50 65 50
140MT-D9N-B25 450 100-C09 65 30 65 30
140MT-D9N-B40 450 100-C09 65 30 65 30
140MT-D9N-B63 450 100-C09 65 30 65 30
140MT-D9N-C10 450 100-C09 65 30 65 30
140MT-D9N-C16 450 100-C12 65 30 65 30
140MT-D9N-C20 450 100-C23 65 30 65 30
140MT-D9N-C25 450 100-C23 50 30 50 30
140MT-D9N-C29 450 100-C30 50 30 50 30
140MT-D9N-C32 450 100-C37 50 30 30 18
140MT-D9N-C36 450 100-C37 30 30 30 18
140MT-D9N-C40 450 100-C37 30 30 30 18
F-Frame, Motor Circuit Protectors, Fixed Magnetic (13 x In)
140M-F8N-C25 600 100-C23 65 30 65 30
140M-F8N-C32 600 100-C30 65 30 65 30
140M-F8N-C45 600 100-C37 65 18 65 18

44 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Table 46 - Type 2 Coordination Ratings, MPSDs with Bulletin 100-C IEC Contactors
Cat. No. 400V 480V 600V
Standard Motor High Inrush Motor Circuit Max Short-circuit Minimum Max Short-circuit Minimum Max Short-circuit Minimum
Protection Motor Protection Protection Current [kA] Contactor Size Current [kA] Contactor Size Current [kA] Contactor Size
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-C3E-A16 — — 100 100-C09 — — — —
140MT-C3E-A25 — — 100 100-C09 — — — —
140MT-C3E-A40 — — 100 100-C09 — — — —
140MT-C3E-A63 — — 100 100-C09 — — — —
140MT-C3E-B10 — — 100 100-C09 — — — —
140MT-C3E-B16 — — 100 100-C09 — — — —
140MT-C3E-B25 — — 65 100-C23 — — — —
140MT-C3E-B40 — — 65 100-C23 — — — —
140MT-C3E-B63 — — 65 100-C23 — — — —
140MT-C3E-C10 — — 65 100-C23 — — — —
140MT-C3E-C16 — — 50 100-C30 — — — —
140MT-C3E-C20 — — 50 100-C30 — — — —
140MT-C3E-C25 — — 15 100-C30 — — — —
140MT-C3E-C29 — — 15 100-C30 — — — —
140MT-C3E-C32 — — 15 100-C30 — — — —
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-D9E-A63 — — 100 100-C09 — — — —
140MT-D9E-B10 140MT-D9T-A63 140MT-D9N-B10 100 100-C09 — — — —
140MT-D9E-B16 140MT-D9T-B10 140MT-D9N-B16 100 100-C09 — — — —
140MT-D9E-B25 140MT-D9T-B16 140MT-D9N-B25 100 100-C09 — — — —
140MT-D9E-B40 140MT-D9T-B25 140MT-D9N-B40 65 100-C09 — — — —
140MT-D9E-B63 140MT-D9T-B40 140MT-D9N-B63 65 100-C09 — — — —
140MT-D9E-C10 140MT-D9T-B63 140MT-D9N-C10 65 100-C09 — — — —
140MT-D9E-C16 140MT-D9T-C10 140MT-D9N-C16 65 100-C23 — — — —
140MT-D9E-C20 140MT-D9T-C16 140MT-D9N-C20 65 100-C23 — — — —
140MT-D9E-C25 140MT-D9T-C20 140MT-D9N-C25 65 100-C23 — — — —
140MT-D9E-C29 140MT-D9T-C25 140MT-D9N-C29 65 100-C30 — — — —
140MT-D9E-C32 140MT-D9T-C29 140MT-D9N-C32 65 100-C30/C37 — — — —
140MT-D9E-C36 140MT-D9T-C32 — 65 100-C30/C37 — — — —
140MT-D9E-C40 140MT-D9T-C36 140MT-D9N-C40 65 100-C30/C37 — — — —
F-Frame, Adjustable Thermal/Fixed Magnetic (13 x In)
140M-F8E-C10 — — 100 100-C09 65 100-C09 30 100-C30
140M-F8E-C16 — — 100 100-C12 65 100-C12 30 100-C30
140M-F8E-C20 — — 100 100-C23 65 100-C23 30 100-C30
140M-F8E-C25 — 140M-F8N-C25 100 100-C30 65 100-C30 30 100-C30
140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 100 100-C30 65 100-C30 30 100-C30
140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 100 100-C37 65 100-C37 10 100-C37

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 45


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Bulletin 140MT/M Devices with Bulletin 100-E IEC Contactors


Table 47 - UL 60947 Application Ratings, MPSDs with Bulletin 100-E IEC Contactors
UL 60947-4-1 Manual Motor Controller UL 60947-4-1 Type F
Group Motor Installation Motor Disconnect Combination Motor Controller
Cat. No. Max. Fuse or Minimum Max Short-circuit Max Short-circuit
Circuit Breaker Contactor Minimum Max Short-circuit Current [kA]
Current [kA] Current [kA] Contactor
per NEC [A] Size
480V 600V 480V 600V Size 480Y/277V(1) 600Y/347V(1)
C-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-C3E-A16 450 100-E09 65 50 65 50 100-E09 65 50
140MT-C3E-A25 450 100-E09 65 50 65 50 100-E09 65 50
140MT-C3E-A40 450 100-E09 65 50 65 50 100-E09 65 50
140MT-C3E-A63 450 100-E09 65 50 65 50 100-E09 65 50
140MT-C3E-B10 450 100-E09 65 50 65 50 100-E09 65 50
140MT-C3E-B16 450 100-E09 65 50 65 50 100-E09 65 50
140MT-C3E-B25 450 100-E09 65 30 65 30 100-E09 65 30
140MT-C3E-B40 450 100-E09 65 30 65 30 100-E09 65 30
140MT-C3E-B63 450 100-E09 65 30 65 30 100-E09 65 —
140MT-C3E-C10 450 100-E09 65 30 65 30 100-E09 65 —
140MT-C3E-C16 450 100-E12 30 30 30 30 100-E12 30 —
140MT-C3E-C20 450 100-E16 30 30 30 10 — — —
450 100-E26 30 18 10 5 — — —
140MT-C3E-C25
450 100-E30 30 18 30 5 — — —
140MT-C3E-C29 450 100-E30 30 10 10 — — — —
140MT-C3E-C32 450 100-E38 30 10 10 — — — —
D-Frame, Adjustable Thermal/Fixed Magnetic (14 x In)
140MT-D9E-A63 450 100-E09 65 50 65 50 100-E09 65 50
140MT-D9E-B10 450 100-E09 65 50 65 50 100-E09 65 50
140MT-D9E-B16 450 100-E09 65 50 65 50 100-E09 65 50
140MT-D9E-B25 450 100-E09 65 30 65 30 100-E09 65 30
140MT-D9E-B40 450 100-E09 65 30 65 30 100-E09 65 30
140MT-D9E-B63 450 100-E09 65 30 65 30 100-E09 65 30
140MT-D9E-C10 450 100-E09 65 30 65 30 100-E09 65 30
140MT-D9E-C16 450 100-E12 65 30 65 30 100-E12 65 30
140MT-D9E-C20 450 100-E26 65 30 65 30 100-E26 65 —
140MT-D9E-C25 450 100-E26 50 30 50 30 100-E26 50 —
140MT-D9E-C29 450 100-E30 50 30 50 30 100-E30 50 —
140MT-D9E-C32 450 100-E38 50 30 30 18 100-E38 30 —
140MT-D9E-C36 450 100-E38 30 30 30 18 100-E38 30 —
140MT-D9E-C40 450 100-E38 30 30 30 18 100-E38 30 —
140MT-D9E-C40 450 100-E40 30 30 30 18 100-E40 30 —
(1) For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

46 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Accessory Specifications
Table 48 - Auxiliary Contact Specifications—For 140MT-C… and 140MT-D… Devices
Front-mounted Auxiliary Contacts Right Side-mounted Auxiliary Contacts
Attribute Cat. Nos. 140MT-C-AFA, -AFAR/ -AFAR10M10 Cat. No. 140MT-C-ASA
at 40 °C (104 °F) ambient temperature [A] 5 10
Rated Thermal Current Ith
at 60 °C (140 °F) ambient temperature [A] 4 6
Back-up Fuses gG, gL [A] 10 10
General Use current [A] 5 10
IEC [V] 250 690
Rated insulation voltage Ui
UL/CSA [V] 240 600
AC B300 A600
Contact rating code designation (UL/CSA)
DC R300 Q600
24V [A] 4 6
120V [A] 3 5
AC-15 240V [A] 1.5 3
415V [A] — 2
690V [A] — 1
Rated Supply Current Ie
24V [A] 1.2 2
125V [A] 0.22 0.55
DC-13 250V [A] 0.11 0.27
400V [A] — 0.15
500V [A] — 0.13

Type of Terminals

Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3

Flexible with insulated ferrule 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.5…2.5 mm2/No. 18…14 AWG

Flexible 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG

Stranded per UL/CSA 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG

Solid 1 or 2 conductors 0.5…1.5 mm2/No. 18…14 AWG 0.5…2.5 mm2/No. 18…14 AWG
Conductor steps Max 2 conductor steps allowed Max 2 conductor steps allowed
Tightening torque 1…1.2 N•m/8.9…10.6 lb•in 1…1.2 N•m/8.9…10.6 lb•in1…1.2

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 47


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Table 49 - Auxiliary Contact Specifications—For 140M-F… Devices


Front-mounted Auxiliary Contacts Right Side-mounted Auxiliary Contacts
Attribute Cat. Nos. 140M-C-AFA…, 140M-C-AFAR… Cat. Nos. 140M-C-ASA…, 140M-C-ASAR…
at 40 °C (104 °F) ambient temperature [A] 5 10
Rated Thermal Current Ith
at 60 °C (140 °F) ambient temperature [A] 4 6
Back-up Fuses gG, gL [A] 10 10
AC B300 B600
Contact rating code designation (UL/CSA)
DC Q300 Q600
24V [A] 4 6
120V [A] 3 5
AC-15 240V [A] 1.5 3
415V [A] — 2
Rated Supply Current Ie 690V [A] — 0.7
24V [A] 2 2
120V [A] 0.5 0.5
DC-13
240V [A] 0.25 0.25
415V [A] — 0.15

Type of Terminals

Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3
1 conductor 0.5…1.5 mm2 0.5…2.5 mm2
Flexible with insulated ferrule
2 conductors 0.75…1.5 mm2 0.75…2.5 mm2

Stranded per UL/CSA 1 or 2 conductors 0.75…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG

Solid 1 or 2 conductors 0.75…1.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Tightening torque 1.2…1.5 N•m/10.6…13 lb•in 1.2…1.5 N•m/10.6…13 lb•in

48 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Table 50 - Undervoltage and Shunt Trip Specifications—For 140MT-C… and 140MT-D… Devices
Undervoltage Trip for Left-side Mounting Shunt Trip for Left-side Mounting
Attribute Cat. No. 140MT-C-UX Cat. No. 140MT-C-SN
Pick-up [V] 0.85…1.1 x Us 0.7…1.1 x Us
Actuating Voltage
Drop-out [V] 0.7…0.35 x Us 0.7…1.1 x Us
50 Hz [V AC] 24 —
140MT-C-UXK
60 Hz [V AC] 28 —
50 Hz [V AC] 110 —
140MT-C-UXD
60 Hz [V AC] 120 —
50 Hz [V AC] 220…230 —
140MT-C-UXF
60 Hz [V AC] — —
50 Hz [V AC] — —
140MT-C-UXA
60 Hz [V AC] 240…260 —
50 Hz [V AC] 380…400 —
140MT-C-UXN
60 Hz [V AC] 440…460 —
50 Hz [V AC] 415 —
140MT-C-UXB
60 Hz [V AC] 480 —
50 Hz [V AC] — 24
140MT-C-SNK
60 Hz [V AC] — 24…28
Rated AC Control Voltage 50 Hz [V AC] — 110
140MT-C-SND
60 Hz [V AC] — 120
50 Hz [V AC] — 220…230
140MT-C-SNF
60 Hz [V AC] — —
50 Hz [V AC] — —
140MT-C-SNA
60 Hz [V AC] — 240…260
50 Hz [V AC] — 240
140MT-C-SNT
60 Hz [V AC] — 277
50 Hz [V AC] — 380…400
140MT-C-SNN
60 Hz [V AC] — 440…460
50 Hz [V AC] — 415
140MT-C-SNB
60 Hz [V AC] — 480
On-time Continuous duty Continuous duty
Pick-up [VA/W] 8.5/8 8.5/8
Coil consumption
Hold-in [VA/W] 4/2 4/2
140MT-C-SNZJ [V DC] — 24
Rated DC Control Voltage On-time Max 5 s
Coil consumption Pick-up [W] 50

Type of Terminals

Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3

Flexible with insulated ferrule 1 or 2 conductors 0.5…2.5 mm2/ No. 18…14 AWG 0.5…2.5 mm2/ No. 18…14 AWG

Flexible 1 or 2 conductors 0.75…2.5 mm2/ No. 18…14 AWG 0.75…2.5 mm2/ No. 18…14 AWG

Stranded per UL/CSA 1 or 2 conductors 0.75…2.5 mm2/ No. 18…14 AWG 0.75…2.5 mm2/ No. 18…14 AWG

Solid 1 or 2 conductors 0.5…2.5 mm2/ No. 18…14 AWG 0.5…2.5 mm2/ No. 18…14 AWG
Conductor steps Max 2 conductor steps allowed Max 2 conductor steps allowed
Tightening torque 1…1.2 N•m/8.9…10.6 lb•in 1…1.2 N•m/8.9…10.6 lb•in1…1.2

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 49


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Table 51 - Undervoltage and Shunt Trip Specifications—For 140M-F… Devices


Undervoltage Trip for Left-side Mounting Shunt Trip for Left-side Mounting
Attribute Cat. No. 140M-C-UX…, -UC… Cat. No. 140M-C-SN…
Pick-up [V] 0.85…1.1 x Us 0.7…1.1 x Us
Actuating Voltage
Drop-out [V] 0.7…0.35 x Us 0.7…1.1 x Us
50 Hz [V AC] 21 21
Min
60 Hz [V AC] 24 24
Max 60 Hz [V AC] 600 600
Rated AC Control Voltage
On-time Continuous duty Continuous duty
Pick-up [VA/W] 8.5/8 8.5/8
Coil consumption
Hold-in [VA/W] 4/2 4/2

Type of Terminals

Recommended screwdriver Pozidriv No. 2/Blade No.3 Pozidriv No. 2/Blade No.3
1 conductor 0.5…2.5 mm2 0.5…2.5 mm2
Flexible with insulated ferrule
2 conductors 0.75…2.5 mm2 0.75…2.5 mm2

Stranded per UL/CSA 1 or 2 conductors 0.75…2.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG

Solid 1 or 2 conductors 0.75…2.5 mm2/No. 18…14 AWG 0.75…2.5 mm2/No. 18…14 AWG
Tightening torque 1.2…1.5 N•m/10.6…13.3 lb•in 1.2…1.5 N•m/10.6…13.3 lb•in

Table 52 - Feeder Terminals


Compact Busbar Feeder Terminal Compact Busbar
140MT-C-WTEN 140M-F-WTE 140MT-C-W… 140M-F-W…
Rated Thermal Current Ith
[A] 64 120 64 120
at 60 °C (140 °F) ambient temperature
Flexible with insulated
ferrule 1 conductor 2.5…25 mm2/No. 14…4 AWG — — —

Stranded per UL/CSA 1 conductor 2.5…25 mm2/No. 14…4 AWG 4…50 mm2/No. 12…1/0 MCM — —

Solid 1 conductor 2.5…25 mm2/No. 14…4 AWG 2.5…50 mm2/No. 12…1/0 MCM — —

De-isolation (stripping) length [mm (in)] 14 (0.55) — —


Tightening torque 3…3.5 N•m/27…31 lb•in 5…6 N•m/45…54 lb•in — —

Table 53 - Feeder Blocks for Compact Busbars


IEC 60947 UL 60947/CAN/CSA-C22.2 No. 60947
140MT-C-WBE 140MT-C-WBE 140MT-C-WBE 140MT-C-WBE 140M-F-WBE L1, 140M-F-WBE T1,
1, 3, 5 2, 4, 6 L1, L2, L3 T1, T2, T3 L2, L3 T2, T3
Rated Thermal Current Ith
[A] 64 64 IEC120/UL115
at 60 °C (140 °F) ambient temperature
Flexible with insulated for use with for use with 4…50 mm2/ for use with
ferrule 1 conductor 4…25 mm2 140MT-C-W No. 10…4 AWG 140MT-C-W No. 10…4 AWG 140M-F-W
for use with for use with
Flexible 1 conductor 4…25 mm2 140MT-C-W No. 10…4 AWG 140MT-C-W — —

for use with for use with 4…25 mm2/ for use with
Stranded per UL/CSA 1 conductor 4…25 mm2 140MT-C-W No. 10…4 AWG 140MT-C-W 140M-F-W
No. 10…4 AWG
for use with for use with 2.5…25 mm2/ for use with
Solid 1 conductor 2.5…25 mm2 140MT-C-W No. 14…4 AWG 140MT-C-W 140M-F-W
No. 14…4 AWG
Tightening torque 3…3.5 N•m 2…2.5 N•m 27…31 lb•in 18…22 lb•in 5…6 N•m/45…54 lb•in

50 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Specifications

Time-Current Characteristic
Figure 10 - Motor Protection Circuit Breakers Time-Current Characteristic
10 000
1h

1 000

100

1
10

Release Time [s]


1

0.1
2

0.01

0.001
0.8 1 2 4 6 10 20 40 60 100
Multiple of set current Ie
140MT-C, -D, 140M-F Motor Protection Circuit Breakers (for 140MT-D9V, see ratings)

Thermal Release Trip Current


The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current
at an ambient temperature of 20 °C (68 °F) starting from the cold state. Careful testing and setting ensures effective motor protection even
in the case of single phasing. The overload characteristic is also valid for transformer protection.

Magnetic Release Trip Current


The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13…14 times the maximum value of the setting
range. (Transformer protection up to 20 x Ie max.) At a lower setting, it is correspondingly higher.

Current Setting IeF

The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC 60947-4-1. If a different value is prescribed
(for example, reduced Ie for cooling medium having a temperature higher than 40 °C (104 °F) or a place of installation higher than 2000 m
(6561 ft) above sea level), the setting current is equal to the reduced rated current Ie of the motor.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 51


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Approximate Dimensions

Approximate Dimensions
Dimensions are in millimeters (inches) and are not intended for manufacturing purposes.

140MT-C, 140MT-D Devices and Accessories


Figure 11 - Mounting Position
30°

90° 90°
120°

Figure 12 - Spacing Requirements


X1

46.8
(1.83)
45
96.3 (1.77)
5.8 (3.79)
(0.23)
48.15
(1.9)

X2
Z
Y 24.8 Y 49 (1.93)
(0.98)
69 (2.71) 7.5
18 45 9 (0.3)
(0.71) (1.77) (0.35)

Minimum Distance to Grounded Parts or Walls [mm (in)]


Frame Size Voltage [V AC] Z
X1 X2 Y
400 30 (1-3/16) 30 (1-3/16) 9 (23/64)
C-Frame 500 30 (1-3/16) 30 (1-3/16) 9 (23/64) 7.5 (19/64)
690 50 (1-31/32) 50 (1-31/32) 30 (1-3/16)
400 30 (1-3/16) 30 (1-3/16) 9 (23/64)
D-Frame 500 30 (1-3/16) 30 (1-3/16) 9 (23/64) 13.5 (17/32)
690 50 (1-31/32) 50 (1-31/32) 30 (1-3/16)

52 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Approximate Dimensions

Figure 13 - Motor Protection Circuit Breaker (C-Frame), Cat. No. 140MT-C3…


79 (3.11)
34.6 (1.36) 9.2 71.6 (2.82)
(0.36)
2.4 6.9
(0.27) 4.4 52.1 (2.05)
18 (0.09) (0.17)
(0.71)

(1)

4.5
(0.18)
36.8 44.8
96.3 100 (1.45 (1.76)
(3.8) (3.94) 57.9
(2) (2.28)
23
(0.91)

6.9
(0.27) (3) (4)

2.7
14.4 14.4 (0.11)
(0.57) (0.57) 4.8
44.7 (1.76) (0.19)

Note Information Note Information


1 Undervoltage/shunt trip 3 Auxiliary contact (side mounted)
2 Auxiliary contact (front mounted) 4 Screw mounting adapter

Figure 14 - Motor Protection Circuit Breaker (D-Frame), Cat. No. 140MT-D9…


34.6 (1.36) 89.2 (3.51)
9.2
(0.36)
2.4 77.6 (3.06)
(0.09) 6.9
18 (0.27) 4.5
(0.71) 58.1 (2.29)
(0.18)

(1)

4.5
(0.18) 36.8 44.8
96.3 100 (1.45 (1.76)
(3.8) (3.94) 57.9
(2) 22.9 (2.28)
(0.9)

6.9
(0.27) (3) (4)
4.75
(0.19)
14.4 14.4 8.7
(0.57) (0.57) (0.34)
44.9 (1.77)

Note Information Note Information


1 Undervoltage/shunt trip 3 Auxiliary contact (side mounted)
2 Auxiliary contact (front mounted) 4 Screw mounting adapter

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 53


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Approximate Dimensions

Figure 15 - Feeder Terminal for Compact Busbar, Cat. No. 140MT-C-WTEN


14.4 14.4
2 (0.56) (0.56)
(0.1)
11.2
(0.4)
29.2
15.6 (1.15)
(0.6)
55.7
(2.2)
15.1
(0.6)

11.4
(0.4)

44.25
(1.7)

44.8
(1.8)

Figure 16 - Terminal Cover, Cat. No. 140MT-C-WSN


Ø7
(0.3)
1.5
(0.1) Ø 5.4
7
(0.3) (0.2)
Ø 3.56
(0.1)

30.55
(1.2)

17.3
(0.7)

35.8 (1.4)

Figure 17 - 140MT-C and 140MT-D with Cat. No. 140MT-C-TE Type E Adapter
45
(1.77)
140MT-C: 52.1 (2.05)
43.1 140MT-D: 58.1 (2.29)
(1.70)

19
(0.78)

67
(2.64)

45
(1.77)

45
(1.77)

54 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Approximate Dimensions

140M-F Devices and Accessories


Figure 18 - Mounting Position/Safety Clearance
8 (1) 8
(1)
(5/16) (5/16)

30 (1) 30°
(1-3/16)
90° 90°
120°

(1)
30
(1-3/16)

Note Information
1 Minimum distance to grounded parts or walls

Figure 19 - Motor Protection Circuit Breaker (F-Frame), Cat. No. 140M-F8…


54.5
(2.14)
(4)
72 (2)
(2.83) 47.8
(4)
(4) (1.88)
47 62
(1.85) (2.44)
(2)

4.5 55.7
(0.18) (2.19) (1)

91 92 45
(3.58) (3.62) 111.4 (1.77)
(4.39)

55.7
(2.19)

12
(0.47)
2.4 4.5
62 (0.09) (0.18) 91 (3)
(2.44) (3.58)
54 92 (3)
18 9 (3.62)
(0.71) (2.12)
(0.35)
102
(4.01) 8
(0.31)
110
(4.33)

Note Information
1 Mounting on 35 mm DIN Rail
2 Undervoltage/shunt trip
3 Auxiliary contact (front mounted)
4 Auxiliary contact (side mounted)

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 55


Bulletin 140MT Motor Protective Switching Devices and Motor Circuit Protectors Approximate Dimensions

Figure 20 - Cat. No. 140M-F-TE Type E adapter on Cat. No. 140M-F8E…

Figure 21 - Screw Adapter, Cat. No. 140M-C-N45

. .

Figure 22 - 140M-C-WBE

56 Rockwell Automation Publication 140-TD005B-EN-P - September 2021


Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Technical Data

Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Provides product selection and specification information for Bulletin 140UT molded case
Molded Case Circuit Breaker Specifications, publication 140UT-TD001 circuit breakers.
Short-circuit Current Ratings and Your Industrial Control Panel, Provides examples for short-circuit current ratings of panels based on the methods stated
publication SCCR-AT002 in UL 508A Supplement B
Provides coordinated high-fault branch circuit solutions for motor starters, soft starters,
Rockwell Automation Global SCCR tool, rok.auto/sccr and component drives.
IEC Contactor Specifications, publication 100-TD013 Provides product selection and specification information for IEC contactors.
American Standards, Configurations, and Ratings: Introduction to Provides an overview of American motor circuit design based on methods that are outlined
Motor Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 140-TD005B-EN-P - September 2021 57


Rockwell Automation Support
Use these resources to access support information.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.

Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Publication 140-TD005B-EN-P - September 2021


Supersedes Publication 140-TD005A-EN-P August 2021 Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.