Motor Protection Circuit Breaker and Motor Circuit Protector Specifications
Motor Protection Circuit Breaker and Motor Circuit Protector Specifications
Motor Protection Circuit Breaker and Motor Circuit Protector Specifications
Summary of Changes
This publication adds product selection and accessory information.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Use of Motor Protection Circuit Breakers with Variable- Frequency Drives, Provides application information about using 140M devices with variable-frequency
publication 140M-AT002 drives.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, https://www.rockwellautomation.com/global/certification/ Provides declarations of conformity, certificates, and other certification details.
overview.page?
Notes:
In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-
Protected Combination Motor Controller.
The 140M-C, D, and F frame Motor Protection Circuit Breakers may have two cULus Listings - as Manual, Self-Protected Combination Motor
Controllers and as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). Cat. No. 140M-D8V* can
also be applied at the output of a variable frequency drive (VFD) in multi-motor applications. See Application Conditions (140M-D8V) on
page 41 for more information.
When UL/CSA listed as Manual, Self-Protected Combination Motor Controllers, the 140M Motor Protection Circuit Breakers provide all of the
necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices.
At some higher voltages and currents (particularly at 600V), a few of the 140M-C, D, and F frame devices are only UL/CSA Listed as Manual
Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must
be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD).
By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or
solid-state motor controller (such as a Bulletin 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller,
additional short-circuit protection is not required for the individual motor circuits.
A combination of a Bulletin 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E self-
protected combination motor controller. In this case, both the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical
operational test. In some cases, this may require over sizing of the Bulletin 140M MPCB or the 100-C contactor to achieve weld free performance
and meet the additional life requirements.
140M – C 2 E – A63 – KN – CC – GJ
a b c d e f g h
a b c d
Bulletin Number Frame/Rating Interrupting Rating/Breaking Capacity Protection Type
Code Description Code Description Code Description Code Description
140M Motor Protection Circuit Breaker C 32 A 2 Normal Break E Adj Thermal/ Fixed Mag(13 x In)
Adj Thermal/Fixed Mag
D 32A 8 High Break T (Fixed at 16...20 x In)
Adj Thermal/Fixed Mag application at
F 45A V output of VFD (multi-motor)
e f g
Current Range Miscellaneous Auxiliary Trip Contacts
Code Description Example Code Description Frame Size C, D, F Frames
1st 2nd
A A=0.10 A16=0.16 KN Black Lockable Knob C,D,F Description Description
Code Code
B B=1.0 B16=1.6 KRY Red/Yellow Lockable Knob C,D,F Bottom Front Right Side
C C=10 C16=16 Spacing Adapter for Self- X Placeholder X Placeholder
TE C,D,F
D D=100 D16=160 Protected Starters (Type E) A 1 N.C. C 1 N.O.+1 N.C.
E E=1000 E16=1600 MT STD BusBar Mount, Top C,D,F B 1 N.O. D 2 N.O.
C 1 N.O.+1 N.C. E 2 N.C.
D 2N.O. K 1 N.C. (SC+OL) + 1 N.C. (SC)
E 2N.C. L 1 N.O. (SC+OL) + 1 N.O. (SC)
1 N.C.+ 1 N.O.
R M 1 N.C. (SC + OL)+ 1 N.O. (SC)
(SC + OL)
S 1 N.O.+1 N.O.(SC+OL) N 1 N.O. (SC + OL) + 1 N.C. (SC)
Q 1 N.O. (SC)+1 N.C.(SC)
h
UV and Shunt Trips
C, D, F Frame
1st Code Description 2nd Code Description
Left Side Voltage
G Undervoltage Trip J 24V AC, 60 Hz
K 24V AC, 50 Hz
D 120V AC, 60 Hz
C 110V AC, 50 Hz
H 208V AC, 60 Hz
F 220…230V AC, 50 Hz
P Shunt Trip A 240V AC, 60Hz
T 277V AC, 60 Hz
N 380…400V AC, 50 Hz
B 480V AC, 60Hz and 415V AC, 50 Hz
VC 600V AC, 60Hz
M 575V AC, 60Hz and 500V AC, 50 Hz
Application Diagrams
There is only one Branch Circuit Protective Device (BCPD) for the “Group”.
Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and other loads
to be connected to the same branch-circuit…”. The most restrictive part of the conditions specified for Group Installation is the requirement for the
protection of the conductors for each motor circuit. In the U.S. NEC for 2002, a new rule for the conductor sizing was added for devices that are
listed and marked “Suitable for use as Tap Conductor Protection”.
Figure 1 shows an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”.
Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Group Installation: conductors from the BCPD to each motor must be
a minimum of 1/3 the ampacity of the Branch Circuit conductors.
Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Tap conductor Protection in Group Installations: conductors from
the BCPD to manual motor controller listed as “…Tap Conductor Protection…” must be minimum of 1/10 the rating or setting of the BCPD.
Conductors from the controller to the motor must be 125% of the motor FLA.
Fuses or
Circuit Breaker Tap Conductor Protection in Group
Installation:
Group Installation Conductors from BCPD to manual motor
Single motor taps must be controller listed as “…Tap Conductor
1/3 the ampacity of the Protection…” must be minimum of 1/10
Branch Circuit Conductors
branch circuit conductors the rating or setting of the BCPD
Bulletin 140M Motor Protection Circuit Breakers (MPCBs) are UL/CSA Listed as Type E Manual Self-Protected Combination Motor
Controllers or UL/CSA Listed as Circuit Breakers. These UL/CSA Listings allow the Bulletin 140M MPCBs to provide the branch-circuit,
short-circuit protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the
protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream protective
device. Figure 2 shows an example that illustrates installations involving multiple motors, each with its own branch-circuit protection (BCPD).
Product Selection
140M-RC2
Max. Short
Rated Magnetic Circuit Current Max. 3-phase Hp Ratings(1) Max. kW, 3-Phase — AC-3(1)
Motor Current
Operational Trip [kA]
Adjustment Cat. No.
Current (Ie) Current 480V
Range [A] 400V
[A] [A] (group 200V 230V 460V 575V 230V 400/415V 500V 690V
(Icu)
motor)
C-Frame
0.16 0.10…0.16 2.1 100 65 — — — — — 0.02 0.06 0.06 140M-RC2E-A16
0.25 0.16…0.25 3.3 100 65 — — — — — 0.04 0.09 0.09 140M-RC2E-A25
0.4 0.25…0.40 5.2 100 65 — — — 0.25 0.06 0.09 0.12 0.18 140M-RC2E-A40
0.63 0.40…0.63 8.2 100 65 — — 0.25 0.33 0.09 0.18 0.18 0.25 140M-RC2E-A63
1 0.63…1.0 13 100 65 — — 0.5 0.75 0.18 0.25 0.37 0.55 140M-RC2E-B10
1.6 1.0…1.6 21 100 65 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140M-RC2E-B16
2.5 1.6…2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-RC2E-B25
4 2.5…4.0 52 100 65 1 1 3 3 0.75 1.5 2.2 3.0 140M-RC2E-B40
6.3 4.0…6.3 82 100 65 1.5 2 5 5 1.5 2.2 3.0 4.0 140M-RC2E-B63
10 6.3…10 130 100 65 3 3 7.5 10 2.2 4.0 6.3 7.5 140M-RC2E-C10
16 10…16 208 65 30 5 5 10 15 4.0 7.5 10 13 140M-RC2E-C16
(1) Horsepower/kW ratings show are for reference. The final selection of the MPCB depends on the actual motor full load current.
In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-
Protected Combination Motor Controller.
The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193
overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. These starters are then able to provide all of the
necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices.
140M – C 2 N – A63 – KN – CC – GJ
a b c d e f g h
a b c d
Bulletin Number Frame/Rating Interrupting Rating/Breaking Capacity Protection Type
Code Description Code Description Code Description Code Description
140M Motor Circuit Protector C 25 A 2 Normal Break N Fixed Mag only (13 x In)
D 32A 8 High Break
F 45A
e f g
Current Range Miscellaneous Auxiliary Trip Contacts
Code Description Example Code Description Frame Size C, D, F Frames
2nd
A A=0.10 A16=0.16 KN Black Lockable Knob C,D,F 1st Code Description Description
Code
B B=1.0 B16=1.6 KRY Red/Yellow Lockable Knob C,D,F Bottom Front Right Side
C C=10 C16=16 Spacing Adapter for Self- X Placeholder X Placeholder
TE C,D,F
D D=100 D16=160 Protected Starters (Type E) A 1 N.C. C 1 N.O.+1 N.C.
E E=1000 E16=1600 MT STD BusBar Mount, Top C,D,F B 1 N.O. D 2 N.O.
C 1 N.O.+1 N.C. E 2 N.C.
D 2N.O. K 1 N.C. (SC+OL) + 1 N.C. (SC)
E 2N.C. L 1 N.O. (SC+OL) + 1 N.O. (SC)
R 1 N.C.+ 1 N.O. (SC + OL) M 1 N.C. (SC + OL)+ 1 N.O. (SC)
S 1 N.O.+1 N.O.(SC+OL) N 1 N.O. (SC + OL) + 1 N.C. (SC)
Q 1 N.O. (SC)+1 N.C.(SC)
h
UV and Shunt Trips
C, D, F Frame
1st Code Description 2nd Code Description
Left Side Voltage
G Undervoltage Trip J 24V AC, 60 Hz
K 24V AC, 50 Hz
D 120V AC, 60 Hz
C 110V AC, 50 Hz
H 208V AC, 60 Hz
F 220…230V AC, 50 Hz
P Shunt Trip A 240V AC, 60Hz
T 277V AC, 60 Hz
N 380…400V AC, 50 Hz
B 480V AC, 60Hz and415V AC, 50 Hz
VC 600V AC, 60Hz
M 575V AC, 60Hz and500V AC, 50 Hz
Application Diagrams
There is only one Branch Circuit Protective Device (BCPD) for the “Group”.
Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and other loads
to be connected to the same branch-circuit…”. The most restrictive part of the conditions specified for Group Installation is the requirement for the
protection of the conductors for each motor circuit.
Figure 3 shows an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”.
Bulletin 140M Motor Circuit Protectors UL/CSA Listed for Group Installation: conductors from the BCPD to each motor must be a minimum
of 1/3 the ampacity of the Branch Circuit conductors. MCPs do not provide thermal protection, so a separate overload relay must be used. Because
of this, MCPs cannot be UL/CSA Listed for Tap Conductor Protection in group installations.
Fuses or
Circuit Breaker
Group Installation
Single motor taps must be
1/3 the ampacity of the
Branch Circuit Conductors
branch circuit conductors
Bulletin 140M Motor Circuit Protectors (MCPs) are UL/CSA Listed as part of a Combination Motor Controllers or a Self-Protected
Combination Motor Controller consisting of a 140M Motor Circuit Protector, a 100-C Contactor, and a 193 Overload Relay. These UL/CSA
Listings allow the Bulletin 140M MCPs to provide the branch-circuit, short-circuit protection for each individual motor circuit. Additional short-
circuit protection is not required for the protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit
conductors by an upstream protective device. Figure 4 shows an example that illustrates installations involving multiple motors, each with its own
branch-circuit protection (BCPD).
Product Selection
• For trip Class 10 motor applications
Notes:
Accessories
Auxiliary Contacts
Operator Position(1)
OFF ON Tripped Term. Contact Connection
Description For Use With Cat. No.
No. Description Diagram(2)
140M Operator
Trip Contacts
Operator Position(1)
OFF ON Tripped Term. Contact Connection
Description For Use With Cat. No.
No. Description Diagram(2)
(short-circuit) 78 66
140M Operator
Operator Position(1)
OFF ON Tripped Term. Contact Connection
Description For Use With Cat. No.
No. Description Diagram(2)
13
140M-C, D, F;
140M-RC
11
• 1-pole or 2-pole
• No additional space O X O 13-14 N.O. Aux 13 21
required
• - Only 1 per device 14 22
140M-RC-AFA11
X O X 21-22 N.C. Aux
140M-C, D, F;
O X O 13-14 N.O. Aux 13 23
140M-RC
140M-RC-AFA20
O X O 23-24 N.O. Aux I >>
14 24
overload) 12 28
140M Operator
Description Connection Diagram(1) Trip Rating For Use With Cat. No.
24V, 60 Hz 140M-C-UXJ
24V, 50 Hz 140M-C-UXK
120V, 60 Hz 140M-C-UXD
110V, 50 Hz 140M-C-UXC
Undervoltage Trip 208V, 60 Hz 140M-C-UXH
• Left-side mounted D1
• Adds 18 mm to the width of the U<
220…230V, 50 Hz 140M-C-UXF
140M-C, D, F; 140U-D
device 240…260V, 60 Hz 140M-C-UXA
• Automatically trips MPCB/MCP I >>
D2
when voltage falls below 35…70% 277V, 60 Hz 140M-C-UXT
380…400V, 50 Hz 140M-C-UXN
480V, 60 Hz/415V, 50 Hz 140M-C-UXB
575V, 60 Hz/500V, 50 Hz 140M-C-UXM
600V, 60 Hz 140M-C-UXVC
24V, 60 Hz 140M-C-UCJ
24V, 50 Hz 140M-C-UCK
120V, 60 Hz 140M-C-UCD
D1 07 110V, 50 Hz 140M-C-UCC
Undervoltage Trip
• Left-side mounted 208V, 60 Hz 140M-C-UCH
• 2 early make contacts integrated 220…230V, 50 Hz 140M-C-UCF
U<
• Adds 18 mm to the width of the 140M-C, D, F
device D2 08 240…260V, 60 Hz 140M-C-UCA
I>
• Automatically trips MPCB/MCP 277V, 60 Hz 140M-C-UCT
when voltage falls below 35…70%
380…400V, 50 Hz 140M-C-UCN
480V, 60 Hz/415V, 50 Hz 140M-C-UCB
575V, 60 Hz/500V, 50 Hz 140M-C-UCM
600V, 60 Hz 140M-C-UCVC
24V, 60 Hz 140M-C-SNJ
24V, 50 Hz 140M-C-SNK
110V, 50 Hz/120V, 60 Hz 140M-C-SND
Shunt Trip 208V, 60 Hz 140M-C-SNH
• Left-side mounted C1 220…230V, 50 Hz 140M-C-SNF
• Adds 18 mm to the width of the
device 240…260V, 60 Hz 140M-C-SNA
140M-C, D, F; 140U-D
• Provides remote tripping of the 277V, 60 Hz 140M-C-SNT
MPCB/MCP I >>
C2
• Maximum on time for DC operated 380…400V, 50 Hz 140M-C-SNN
devices: 5 sec. 480V, 60 Hz/415V, 50 Hz 140M-C-SNB
575V, 60 Hz/500V, 50 Hz 140M-C-SNM
600V, 60 Hz 140M-C-SNVC
24V DC 140M-C-SNZJ
(1) Connection Diagram Reference:
140M Operator
Additional Accessories
Anti-Tamper Shield
• Provides protection against inadvertent adjustment of the current setting 140M-C, D, F 140M-C-CA
• Must be ordered in multiples of 10 (10 pcs/pkg)
Black 140M-C-KN1
Lockable Twist Knob 140M-C, D, F
• For one padlock 5 mm (3/16 in.) diameter shackle
• Can be locked in OFF position Red/Yellow 140U- D 140M-C-KRY1
Coupler 140M-C, D, F
140M-C-DNC
• Included with Cat. Nos. 140M-C-DN66 and 140M-C-DRY66 140U- D
Notes:
Specifications
Application Ratings
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-K Contactors
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors
UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors (Separate Overload Protection Required)
In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical,
fully short-circuit coordinated starter combinations with Type 2 coordination.
Cat.No.140M-C2E-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 C25 C29 C32
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25 29 32
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325 406 448
Switching of Standard Three-Phase Motors, AC-3
230/240V [kW] — — 0.06 0.09 0.18 0.25 0.37 0.75 1.5 2.2 4.0 5.5 5.5 7.5 7.5
400/415V [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75 1.5 2.2 4.0 7.5 10 11 13 15
500V [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1 2.2 3.0 6.3 10 11 15 18.5 20
690V [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8 3.0 4.0 7.5 13 17 22 25 25
Back-Up Fuses gG, gL, only if Icc ≥ Icu
(1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
230/240V [A] 100 100 125 125
400/415V [A] (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) 80 100 100 125 125
440/460V [A] (1) (1) (1) (1) (1) (1) (1) (1) (1) 63 80 80 80 100 100
500V [A] (1) (1) (1) (1) (1) (1) (1) (1) (1) 80 80 80 80 100 100
690V [A] (1) (1) (1) (1) (1) 16 20 35 50 50 63 63 63 80 80
Ultimate Short Circuit Breaking Capacity, Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 65 65 50 50
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 65 50 15 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 6 6
690V [kA] 100 100 100 100 100 8 6 6 4 4 3 3 3 3 3
Rated Service Short Circuit Breaking Capacity, Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50 25 25
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 6 6
690V [kA] 100 100 100 100 100 8 6 6 4 4 3 3 3 3 3
(1) No back-up fuse required.
Cat.No.140M-D8E- Cat.No.140M-F8E-
B25 B40 B63 C10 C16 C20 C25 C29 C32 C10 C16 C20 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 20 25 29 32 10 16 20 25 32 45
Magnetic Release Current [A] 33 52 82 130 208 260 325 406 448 130 208 260 325 416 585
Switching of Standard Three-Phase Motors, AC-3
230/240V [kW] 0.37 0.75 1.5 2.2 4.0 5.5 5.5 7.5 7.5 2.2 4.0 5.5 6.3 7.5 13
400/415V [kW] 0.75 1.5 2.2 4.0 7.5 10 11 13 15 4.0 7.5 10 11 15 22
500V [kW] 1.1 2.2 3.0 6.3 10 11 15 18.5 20 6.3 10 11 15 20 30
690V [kW] 1.8 3.0 4.0 7.5 13 17 22 25 25 7.5 13 17 22 30 40
Back-Up Fuses gG, gL, only if Icc ≥ Icu
(1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
230/240V [A]
(1) (1) (1) (1) (1)
400/415V [A] 100 100 125 125 80 100 100 100 125 125
(1) (1) (1) (1)
440/460V [A] 80 100 100 125 125 80 100 100 100 125 125
(1) (1) (1) (1)
500V [A] 80 80 80 100 100 80 100 100 100 125 125
690V [A] 20 35 50 50 63 63 63 80 80 63 80 80 80 100 100
Ultimate Short Circuit Breaking Capacity, Icu
230/240V [kA] 100 100 100 100 100 100 100 65 65 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 65 50 50 100 100 100 100 65 65
440/460V [kA] 100 100 100 50 50 50 50 25 25 65 65 65 65 65 50
500V [kA] 100 100 100 50 50 50 50 25 25 50 50 50 50 50 50
690V [kA] 10 10 6 6 6 6 6 6 6 10 10 10 10 10 10
Rated Service Short Circuit Breaking Capacity, Ics
230/240V [kA] 100 100 100 100 100 100 100 50 50 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 50 25 25 25 25 50 50 50 50 50 50
440/460V [kA] 100 100 100 50 50 25 25 20 20 50 50 50 50 50 50
500V [kA] 100 100 100 50 50 25 25 20 20 50 50 50 50 50 50
690V [kA] 10 10 6 6 4 4 4 4 4 10 10 10 10 6 6
(1) No back-up fuse required.
Cat.No.140M-C2N-
A16 A25 A40 A63 B10 B16 B25
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 32
Switching of Standard Three-Phase Motors, AC-3
230/240V [kW] — — 0.06 0.09 0.18 0.25 0.37
400/415V [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75
500V [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1
690V [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8
Back-Up Fuses gG, gL, only if Icc ≥ Icu
(1) (1) (1) (1) (1) (1) (1)
230/240V [A]
(1) (1) (1) (1) (1) (1) (1)
400/415V [A]
(1) (1) (1) (1) (1) (1) (1)
440/460V [A]
(1) (1) (1) (1) (1) (1) (1)
500V [A]
(1) (1) (1) (1) (1)
690V [A] 16 20
Ultimate Short Circuit Breaking Capacity, Icu
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 10 6
Rated Service Short Circuit Breaking Capacity, Ics
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 8 6
(1) No back-up fuse required.
Cat.No.140M-D8N- Cat.No.140M-F8N-
B25 B63 B40 C10 C16 C25 C32 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 25 32 25 32 45
Magnetic Release Current [A] 32 52 82 130 208 325 448 325 416 585
Switching of Standard Three-Phase Motors, AC-3
230/240V [kW] 0.37 0.75 1.5 2.2 4.0 5.5 7.5 6.3 7.5 13
400/415V [kW] 0.75 1.5 2.2 4.0 7.5 11 15 11 15 22
500V [kW] 1.1 2.2 3.0 6.3 10 15 20 15 20 30
690V [kW] 1.8 3.0 4.0 7.5 13 22 25 22 30 40
Back-Up Fuses gG, gL, only if Icc ≥ Icu
(1) (1) (1) (1) (1) (1) (1)
230/240V [A] 100 125 125
(1) (1) (1) (1) (1)
400/415V [A] 100 125 100 125 125
(1) (1) (1) (1)
440/460V [A] 80 100 125 100 125 125
(1) (1) (1) (1)
500V [A] 80 80 100 100 125 125
690V [A] 20 35 50 50 63 63 80 80 100 100
Ultimate Short Circuit Breaking Capacity, Icu
230/240V [kA] 100 100 100 100 100 100 65 100 100 100
400/415V [kA] 100 100 100 100 100 65 50 100 65 65
440/460V [kA] 100 100 100 50 50 50 25 65 65 50
500V [kA] 100 100 100 50 50 25 25 50 50 50
690V [kA] 10 6 10 6 6 6 6 10 10 10
Rated Service Short Circuit Breaking Capacity, Ics
230/240V [kA] 100 100 100 100 100 100 50 100 100 100
400/415V [kA] 100 100 100 100 50 25 25 50 50 50
440/460V [kA] 100 100 100 50 50 25 20 50 50 50
500V [kA] 100 100 100 50 50 25 20 50 50 50
690V [kA] 10 6 10 6 4 4 4 10 6 6
(1) No back-up fuse required.
Cat.No.140M-C2T-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16
Rated Operational Current, Ie [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16
Magnetic Release Current [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260
Switching of Standard Three-Phase Motors, AC-3
230/240V [kW] — — 0.06 0.09 0.18 0.25 0.37 0.75 1.5 2.2 4.0
400/415V [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75 1.5 2.2 4.0 7.5
500V [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1 2.2 3.0 6.3 10
690V [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8 3.0 4.0 7.5 13
Back-Up Fuses gG, gL, only if Icc ≥ Icu
(1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
230/240V [A]
(1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
400/415V [A] 80
(1) (1) (1) (1) (1) (1) (1) (1) (1)
440/460V [A] 63 80
(1) (1) (1) (1) (1) (1) (1) (1) (1)
500V [A] 80 80
(1) (1) (1) (1) (1)
690V [A] 16 20 35 50 50 63
Ultimate Short Circuit Breaking Capacity, Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50
440/460V [kA] 100 100 100 100 100 100 100 100 100 10 10
500V [kA] 100 100 100 100 100 100 100 100 100 10 10
690V [kA] 100 100 100 100 100 8 6 6 4 4 3
Rated Service Short Circuit Breaking Capacity, Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 10 6
500V [kA] 100 100 100 100 100 100 100 100 100 10 6
690V [kA] 100 100 100 100 100 8 6 6 4 4 3
(1) No back-up fuse required.
Cat.No.140M-D8T- Cat.No.140M-F8T-
C16 C20 C25 C32
Rated Operational Current, Ie [A] 16 20 25 32
Magnetic Release Current [A] 260 325 416 585
Switching of Standard Three-Phase Motors, AC-3
230/240V(1) [kW] 4.0 5.5 6.3 7.5
400/415V(1) [kW] 7.5 10 11 15
(1)
500V [kW] 10 11 15 20
690V(1) [kW] 13 17 22 30
Back-Up Fuses gG, gL, only if Icc ≥ Icu
(2) (2) (2) (2)
230/240V [A]
400/415V [A] 80 100 100 125
440/460V [A] 80 100 100 125
500V [A] 80 80 100 125
690V [A] 63 63 80 100
Ultimate Short Circuit Breaking Capacity, Icu
230/240V [kA] 100 100 100 100
400/415V [kA] 100 65 65 65
440/460V [kA] 50 25 65 65
500V [kA] 50 25 50 50
690V [kA] 6 6 10 10
Rated Service Short Circuit Breaking Capacity, Ics
230/240V [kA] 100 100 100 100
400/415V [kA] 25 25 50 50
440/460V [kA] 25 25 50 50
500V [kA] 25 25 50 50
690V [kA] 4 4 6 6
(1) Consult your local Rockwell Automation sales office or Allen-Bradley distributor.
(2) No back-up fuse required.
General Data
Cat.No. 140M-RC…
Terminal Parts
Type of terminals
2…3.5
Screwdriver
0.2…0.6
Auxiliary Contact Blocks for Front Mounting Auxiliary Contact Blocks for Right-Side Mounting
Cat.No.140M-C-AFA…,140M-C-AFAR… Cat.No.140M-C-ASA…,140M-C-ASAR…
Rated Thermal Current Ith
at 40°C ambient temperature [A] 5 10
at 60°C ambient temperature [A] 4 6
Contact Class Coordination According to NEMA
AC B300 B600
(UL/CSA Standards) DC Q300 Q600
Back-Up Fuses gG, gL [A] 10 10
Rated Supply Current [V] 24 120 240 24 120 240 415 690
AC-15 [A] 4 3 1.5 6 5 3 2 0.7
DC-13 [V] 24 120 240 24 120 240 415
[A] 2 0.5 0.25 2 0.5 0.25 0.15
Terminal Parts
Type of terminals
Screwdriver PozidrivNo.2/BladeNo.3
1.conductor [mm2]/[AWG] 0.5…1.5/18…14 0.5…2.5/18…14
2.conductor [mm2]/[AWG] 0.75…1.5/18…14 0.75…2.5/18…14
Auxiliary Contact Blocks for Front Mounting Auxiliary Contact Blocks for Right-Side Mounting
Cat.No.140M-C-AFA…,140M-C-AFAR… Cat.No.140M-C-ASA…,140M-C-ASAR…
1.conductor [mm2]/[AWG] 0.75…1.5/18…14 0.75…2.5/18…14
2.conductor [mm2]/[AWG] 0.75…1.5/18…14 0.75…2.5/18…14
1.conductor [mm2]/[AWG] 0.75…1.5/18…14 0.75…2.5/18…14
2.conductor [mm2]/[AWG] 0.75…1.5/18…14 0.75…2.5/18…14
Tightening torque [N•m]/[lb•in] 1.2…1.5/10.6…13 1.2…1.5/10.6…13
Cat.No. 140M-RC…
Terminal Parts
Type of terminals
2…3.5
Screwdriver
0.2…0.6
2
1.conductor [mm ]/[AWG] 0.5…1.5/—
2.conductor [mm2]/[AWG] 0.5…1.5/—
1.conductor [mm2]/[AWG] 0.5…1.5/No.18…14
2.conductor [mm2]/[AWG] 0.5…1.5/No.18…14
1.conductor [mm2]/[AWG] 0.5…1.5/No.18…14
2.conductor [mm2]/[AWG] 0.5…1.5/No.18…14
Weights
Cutoff Current
The Bulletin 140-M limits solid short-circuit current Icc(prospective short-circuit current). IDis the maximum cutoff current (highest
instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system
short-circuit current.
Icc asymmetrical
Îs
ID
Icc symmetrical
100
0.25
0.3
0.5
20 A
Peak current [kA]
10 0.7 16 A
29 / 32 A
0.8 25 A
10 A
0.9 6.3 A
4.0 A
0.95
1 2.5 A
cos φ
1.0 A
0.1
0.1 1 10 100
Prospective current [kA r.m.s]
100
0.25
0.3
0.5
29 / 32 A
25 A
Peak current [kA]
10 0.7
16 / 20 A
0.8 10 A
6.3 A
0.9
4.0 A
0.95
1 2.5 A
cos φ
0.1
0.1 1 10 100
Prospective current [kA r.m.s]
0.3
0.5
29 / 32 A
25 A
0.7
10 16 / 20 A
0.8
Peak current [kA]
10 A
6.3 A
0.9
4.0 A
1.6 A
0.1
0.1 1 10 100
100
0.2
0.3
45 A
0.5 32 / 25 A
20 A
Peak current [kA]
10 0.7 16 A
10 A
0.8
0.9
0.95
cos φ
0.1
0.1 1 10 100
Prospective current [kA r.m.s]
1 Half-Cycle (50Hz)
1.00E+05 25 A
29 / 32 A 20 A
Let-through energy [A2s]
16 A
10 A
1.00E+04
6.3 A
4.0 A
1.00E+03
2.5 A
1.6 A
1.00E+02
0.1 1 10 100
Prospective current [kA r.m.s]
1.00E+06
1 Half-Cycle (50Hz)
1.00E+05 32 A
29 A
Let-through energy [A2s]
25 A
20 / 16 A
10 A
1.00E+04
6.3 A
4.0 A
1.00E+03
2.5 A
1.00E+02
0.1 1 10 100
32 A
1.E+05 29 A
25 A
2s]
20 / 16 A
Let-through energy [ A
10 A
1.E+04
6.3 A
4.0 A
2.5 A
1.E+03
1.6 A
1.E+02
0.1 1 10 100
1.00E+06
45 A
1 Half-Cycle (50Hz) 32 A
1.00E+05 25 A
Let-through energy [A2s]
20 A
16 A
10 A
1.00E+04
1.00E+03
1.00E+02
0.1 1 10 100
Prospective current [kA r.m.s]
Time-Current Characteristic
Motor Protection Circuit Breakers Time-Current Characteristic
10 000
1h
1 000
100
1
10
0.1
2
0.01
0.001
0.8 1 2 4 6 10 20 40 60 100
The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an
ambient temperature of 20 °C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single
phasing. The overload characteristic is also valid for transformer protection.
The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13…14 times the maximum value of setting range.
(Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher.
The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC947-4-1. If a different value is prescribed (e.g.,
reduced Ie for cooling medium having a temperature higher than 40 °C or a place of installation higher than 2000 m above sea level), the setting
current is equal to the reduced rated current Ie of the motor.
Notes:
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
§ § §
§ § §
§
§
§ §
§ § §
° 90 30°
90 °
0°
12
. .
140M-C-D…66
4.5
(0.18)
min. 100
(3.93) 3.5
(0.14)
1.5...5
0.06…0.19)
35...45
(1.4…1.8)
b
53.5
(2.10)
53.5
(2.10)
140M-C-DS
a 140M-C-DSL
±5
(0.19) 4...8
(0.16…0.31)
c1
±5
(0.19)
4.5
(0.18) c2
2.4
(0.09)
With Cat. No. 140-M-C-DS Shaft With Cat. No. 140-M-C-DSL Shaft
Cat. No. a b c1 c2 a b c1 c2
105.5 ±5 105.5 ±5
140M-C 117…338 (4.6…13.3) 49.5 (1.95) 40.5 (1.6) 117…438 (4.6…17.2) 49.5 (1.95) 40.5 (1.6)
(4.15 ±0.19) (4.15 ±0.19)
140M-D 126…347 (4.96…13.66) 114.5 ±5 (4.5 ±0.19) 49.5 (1.95) 40.5 (1.6) 126…497 (4.96…19.56) 114.5 ±5 (4.5 ±0.19) 49.5 (1.95) 40.5 (1.6)
148.6…369.6 137.1 ±5 137.1 ±5
140M-F 59.35 (2.34) 50.35 (1.98) 148.6…519 (5.85…20.43) 59.35 (2.34) 50.35 (1.98)
(5.85…14.55) (5.39 ±0.19) (5.39 ±0.19)
140M-C-WBE
Notes:
Product Compatibility and Download Center Get help determining how products interact, check
features and capabilities, and find associated www.rockwellautomation.com/global/support/pcdc.page
(PCDC) firmware.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at https://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Automation maintains current product environmental information on its website at https://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, LISTEN. THINK. SOLVE, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.