Transformer Protection and Control RET620: Application Manual
Transformer Protection and Control RET620: Application Manual
Transformer Protection and Control RET620: Application Manual
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/relion
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure
would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that
all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure network.
It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the necessary
measures (such as, but not limited to, installation of firewalls, application of
authentication measures, encryption of data, installation of anti virus programs, etc.)
to protect the product and the network, its system and interface included, against any
kind of security breaches, unauthorized access, interference, intrusion, leakage and/or
theft of data or information. ABB is not liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2014/35/EU). This
conformity is the result of tests conducted by ABB in accordance with the product
standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in
accordance with the international standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................3
This manual........................................................................................ 3
Intended audience.............................................................................. 3
Product documentation.......................................................................4
Product documentation set............................................................4
Document revision history............................................................. 4
Related documentation..................................................................5
Symbols and conventions...................................................................5
Symbols.........................................................................................5
Document conventions.................................................................. 6
Functions, codes and symbols...................................................... 6
RET620 1
Application Manual
Table of contents
Section 5 Glossary......................................................................... 99
2 RET620
Application Manual
1MRS757659 D Section 1
Introduction
Section 1 Introduction
This manual addresses the protection and control engineer responsible for planning,
pre-engineering and engineering.
RET620 3
Application Manual
Section 1 1MRS757659 D
Introduction
Maintenance
Engineering
Planning &
Installation
Operation
purchase
Quick start guide
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual
Communication protocol manual
IEC 61850 engineering guide
Point list manual
Cyber security deployment guideline
GUID-6087BB7C-D675-413B-B1CD-C4FEEEED8EEB V2 EN
Figure 1: The intended use of documents during the product life cycle
4 RET620
Application Manual
1MRS757659 D Section 1
Introduction
1.4.1 Symbols
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
RET620 5
Application Manual
Section 1 1MRS757659 D
Introduction
• Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the
push button icons.
To navigate between the options, use and .
• Menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in nonvolatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• Input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
• This document assumes that the parameter setting visibility is "Advanced".
6 RET620
Application Manual
1MRS757659 D Section 1
Introduction
RET620 7
Application Manual
Section 1 1MRS757659 D
Introduction
8 RET620
Application Manual
1MRS757659 D Section 1
Introduction
RET620 9
Application Manual
Section 1 1MRS757659 D
Introduction
10 RET620
Application Manual
1MRS757659 D Section 1
Introduction
RET620 11
Application Manual
12
1MRS757659 D Section 2
RET620 overview
2.1 Overview
The 620 series has been designed to unleash the full potential of the IEC 61850
standard for communication and interoperability of substation automation devices.
The 620 series relays support a range of communication protocols including IEC
61850 with Edition 2 support, process bus according to IEC 61850-9-2 LE, IEC
60870-5-103, Modbus® and DNP3. Profibus DPV1 communication protocol is
supported by using the protocol converter SPA-ZC 302.
RET620 13
Application Manual
Section 2 1MRS757659 D
RET620 overview
• Signal Matrix
• Graphical Display Editor
• Communication Management
• IED User Management
• IED Compare
• Firmware Update
• Fault Record Tool
• Load Record Profile
• Differential Characteristics Tool
• Lifecycle Traceability
• Configuration Wizard
• AR Sequence Visualizer
• Label Printing
• IEC 61850 Configuration
• IED Configuration Migration
The protection relay consists of two main parts: plug-in unit and case. The content
depends on the ordered functionality.
14 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
Rated values of the current and voltage inputs are basic setting parameters of the
protection relay. The binary input thresholds are selectable within the range 16…176
V DC by adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and
the plug-in unit.
RET620 15
Application Manual
Section 2 1MRS757659 D
RET620 overview
The LHMI is used for setting, monitoring and controlling the protection relay. The
LHMI comprises the display, buttons, LED indicators and communication port.
Overcurrent protection
SG1 DR Earth-fault protection
Enabled Trigger
Voltage protection
SG4 AR Supervision
Enabled Disable Autoreclose in progress
Arc detected
SG5
Enabled
SG6
Enabled
GUID-3F974E01-28BD-41C3-B8AB-E3C3A01D98D9 V1 EN
2.4.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and rows
fitting the view depends on the character size.
16 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
Table 4: Display
1 2
3 4
A070705 V3 EN
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are 11 matrix programmable LEDs and 16 programmable push buttons with
LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the
operation mode can be selected with the LHMI, WHMI or PCM600.
2.4.3 Keypad
The LHMI keypad contains push buttons which are used to navigate in different views
or menus. With the push buttons you can give open or close commands to objects in
the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The
RET620 17
Application Manual
Section 2 1MRS757659 D
RET620 overview
push buttons are also used to acknowledge alarms, reset indications, provide help and
switch between local and remote control mode.
A071176 V1 EN
Figure 4: LHMI keypad with object control, navigation and command push
buttons and RJ-45 communication port
GUID-4D43320C-F429-4BD6-BECE-1CE6F6F94C30 V1 EN
The LHMI keypad on the left side of the protection relay contains 16 programmable
push buttons with red LEDs.
18 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
The buttons and LEDs are freely programmable, and they can be configured both for
operation and acknowledgement purposes. That way, it is possible to get
acknowledgements of the executed actions associated with the buttons. This
combination can be useful, for example, for quickly selecting or changing a setting
group, selecting or operating equipment, indicating field contact status or indicating
or acknowledging individual alarms.
The WHMI allows secure access to the protection relay via a Web browser. When the
Secure Communication parameter in the protection relay is activated, the Web server
is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.The
WHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
RET620 19
Application Manual
Section 2 1MRS757659 D
RET620 overview
GUID-5166D299-CFBE-499C-8900-6D8B13BCD7F5 V2 EN
• Locally by connecting the laptop to the protection relay via the front
communication port.
• Remotely over LAN/WAN.
2.6 Authorization
Four user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
The default passwords in the protection relay delivered from the factory can be
changed with Administrator user rights.
20 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
Audit trail is a chronological record of system activities that allows the reconstruction
and examination of the sequence of system and security-related events and changes in
the protection relay. Both audit trail events and process related events can be
examined and analyzed in a consistent method with the help of Event List in LHMI
and WHMI and Event Viewer in PCM600.
The protection relay stores 2048 audit trail events to the nonvolatile audit trail.
Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit
trail and event list work according to the FIFO principle. Nonvolatile memory is based
on a memory type which does not need battery backup nor regular component change
to maintain the memory storage.
Audit trail events related to user authorization (login, logout, violation remote and
violation local) are defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined user names or user categories. The user audit
trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.
RET620 21
Application Manual
Section 2 1MRS757659 D
RET620 overview
PCM600 Event Viewer can be used to view the audit trail events and process related
events. Audit trail events are visible through dedicated Security events view. Since
only the administrator has the right to read audit trail, authorization must be used in
PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in LHMI/WHMI Event list
together with process related events.
To expose the audit trail events through Event list, define the
Authority logging level parameter via Configuration/
Authorization/Security. This exposes audit trail events to all users.
22 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
2.7 Communication
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings, disturbance recordings and fault records
can be accessed using the IEC 61850 protocol. Disturbance recordings are available
to any Ethernet-based application in the IEC 60255-24 standard COMTRADE file
format. The protection relay can send and receive binary signals from other devices
(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile,
where the highest performance class with a total transmission time of 3 ms is
supported. Furthermore, the protection relay supports sending and receiving of analog
values using GOOSE messaging. The protection relay meets the GOOSE
RET620 23
Application Manual
Section 2 1MRS757659 D
RET620 overview
The protection relay can support five simultaneous clients. If PCM600 reserves one
client connection, only four client connections are left, for example, for IEC 61850
and Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The protection relay can be connected to
Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the
fiber-optic LC connector (100Base-FX).
Client A Client B
Network A
Network B
GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN
24 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
PRP specifies that each device is connected in parallel to two local area networks.
HSR applies the PRP principle to rings and to the rings of rings to achieve cost-
effective redundancy. Thus, each device incorporates a switch element that forwards
frames from port to port. The HSR/PRP option is available for all 620 series protection
relays.
PRP
Each PRP node, called a double attached node with PRP (DAN), is attached to two
independent LANs operated in parallel. These parallel networks in PRP are called
LAN A and LAN B. The networks are completely separated to ensure failure
independence, and they can have different topologies. Both networks operate in
parallel, thus providing zero-time recovery and continuous checking of redundancy to
avoid communication failures. Non-PRP nodes, called single attached nodes (SANs),
are either attached to one network only (and can therefore communicate only with
DANs and SANs attached to the same network), or are attached through a redundancy
box, a device that behaves like a DAN.
RET620 25
Application Manual
Section 2 1MRS757659 D
RET620 overview
COM600
SCADA
GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V3 EN
HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the two
directions as two virtual LANs. For each frame sent, a node, DAN, sends two frames,
one over each port. Both frames circulate in opposite directions over the ring and each
node forwards the frames it receives, from one port to the other. When the originating
node receives a frame sent to itself, it discards that to avoid loops; therefore, no ring
protocol is needed. Individually attached nodes, SANs, such as laptops and printers,
must be attached through a “redundancy box” that acts as a ring element. For example,
a 615 or 620 series protection relay with HSR support can be used as a redundancy
box.
26 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V3 EN
UniGear Digital switchgear concept relies on the process bus together with current
and voltage sensors. The process bus enables several advantages for the UniGear
Digital like simplicity with reduced wiring, flexibility with data availability to all
devices, improved diagnostics and longer maintenance cycles.
With process bus the galvanic interpanel wiring for sharing busbar voltage value can
be replaced with Ethernet communication. Transmitting measurement samples over
process bus brings also higher error detection because the signal transmission is
automatically supervised. Additional contribution to the higher availability is the
possibility to use redundant Ethernet network for transmitting SMV signals.
RET620 27
Application Manual
Section 2 1MRS757659 D
RET620 overview
Common Ethernet
Station bus (IEC 61850-8-1), process bus (IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronization
GOOSE
GOOSE
GOOSE
GOOSE
GOOSE
GOOSE
GOOSE
SMV
SMV
SMV
SMV
SMV
SMV
SMV
GUID-2371EFA7-4369-4F1A-A23F-CF0CE2D474D3 V5 EN
The 620 series supports IEC 61850 process bus with sampled values of analog
currents and voltages. The measured values are transferred as sampled values using
the IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as the
IEC 61850-8-1 station bus. The intended application for sampled values is sharing the
measured voltages from one 620 series protection relay to other devices with phase
voltage based functions and 9-2 support.
The 620 series protection relays with process bus based applications use IEEE 1588 v2
Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile for
high accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructure
requirement is reduced by allowing time synchronization information to be
transported over the same Ethernet network as the data communications.
28 RET620
Application Manual
1MRS757659 D Section 2
RET620 overview
Primary Secondary
IEEE 1588 v2 IEEE 1588 v2
master clock master clock
(optional)
IEC 61850
HSR
SMV traffic
Backup 1588
master clock
GUID-7C56BC1F-F1B2-4E74-AB8E-05001A88D53D V6 EN
Figure 11: Example network topology with process bus, redundancy and IEEE
1588 v2 time synchronization
The process bus option is available for all 620 series protection relays equipped with
phase voltage inputs. Another requirement is a communication card with IEEE 1588
v2 support (COM0031...COM0034 or COM0037). See the IEC 61850 engineering
guide for detailed system requirements and configuration details.
RET620 29
Application Manual
30
1MRS757659 D Section 3
RET620 default configurations
The 620 series relays are configured with default configurations, which can be used as
examples of the 620 series engineering with different function blocks. The default
configurations are not aimed to be used as real end-user applications. The end-users
always need to create their own application configuration with the configuration tool.
However, the default configuration can be used as a starting point by modifying it
according to the requirements.
RET620 is available with one default configuration. The default signal configuration
can be altered by means of the graphical signal matrix or the graphical application
functionality of the Protection and Control IED Manager PCM600. Furthermore, the
application configuration functionality of PCM600 supports the creation of multi-
layer logic functions utilizing various logical elements including timers and flip-flops.
By combining protection functions with logic function blocks the relay configuration
can be adapted to user specific application requirements.
The default configuration can be used for several purposes; the configuration either
already contains the required functionality or it can be easily modified to suit the
requirements.
• The configuration can be used with 2-winding transformer in different star/delta
connection configurations.
• The main protection is stabilized differential protection.
• Protection is allocated for both sides of transformer, mainly on the high side.
• Both traditional high-impedance earth-fault protection as well as the numerical
method are included in the configuration.
• Synchrocheck
• The configuration can be used with or without the integrated AVR with an on-line
tap changer.
• RET620 controlling the network voltage on load side of the transformer
• Tap changer position via mA inputs or binary inputs
PHLPTOC2 1 LV
Table continues on next page
RET620 31
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
Function A
IEC 61850
(CTs/VTs)
Three-phase non-directional overcurrent protection, high stage PHHPTOC1 1 HV
PHHPTOC2 1 LV
Three-phase non-directional overcurrent protection, instantaneous PHIPTOC1 1 HV
stage
PHIPTOC2 1 LV
Three-phase directional overcurrent protection, low stage DPHLPDOC 1 HV
Three-phase directional overcurrent protection, high stage DPHHPDOC 1 HV
Non-directional earth-fault protection, low stage EFLPTOC1 1 HV1)
EFLPTOC2 1 LV1)
Non-directional earth-fault protection, high stage EFHPTOC1 1 HV1)
EFHPTOC2 1 LV1)
Directional earth-fault protection, low stage DEFLPDEF 2 HV1)
Directional earth-fault protection, high stage DEFHPDEF 1 HV1)
Negative-sequence overcurrent protection NSPTOC1 1 HV
NSPTOC2 1 LV
Residual overvoltage protection ROVPTOV 3 HV
Three-phase undervoltage protection PHPTUV 4 HV
Three-phase overvoltage protection PHPTOV 3 HV
Positive-sequence undervoltage protection PSPTUV 2 HV
Negative-sequence overvoltage protection NSPTOV 2 HV
Frequency protection FRPFRQ 3 HV
Overexcitation protection OEPVPH 2 HV
Three-phase thermal overload protection, two time constants T2PTTR 1 HV
Loss of phase (undercurrent) PHPTUC1 1 HV
PHPTUC2 1 LV
Stabilized and instantaneous differential protection for two-winding
TR2PTDF 1
transformers
Numerical stabilized low-impedance restricted earth-fault protection LREFPNDF1 1 HV
LREFPNDF2 1 LV
High-impedance based restricted earth-fault protection HREFPDIF1 1 HV
HREFPDIF2 1 LV
Circuit breaker failure protection CCBRBRF1 1 HV
CCBRBRF2 1 LV
CCBRBRF3 1 HV
Three-phase inrush detector INRPHAR 1 HV
Master trip TRPPTRC 4
Arc protection ARCSARC (3)2)
Load-shedding and restoration LSHDPFRQ 6 HV
Table continues on next page
32 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
Function A
IEC 61850
(CTs/VTs)
Multipurpose protection MAPGAPC 18
Automatic switch-onto-fault logic (SOF) CVPSOF 1 HV
Underpower protection DUPPDPR 2 HV
Reverse power/directional overpower protection DOPPDPR 3 HV
Control
Circuit-breaker control CBXCBR1 1 HV
CBXCBR2 1 LV
CBXCBR3 1 HV
Disconnector control DCXSWI1 1 HV
DCXSWI2 1 HV
DCXSWI3 1 LV
DCXSWI4 1 LV
Earthing switch control ESXSWI1 1 HV
ESXSWI2 1 LV
ESXSWI3 1 HV
Disconnector position indication DCSXSWI1 1 HV
DCSXSWI2 1 HV
DCSXSWI3 1 LV
DCSXSWI4 1 LV
Earthing switch indication ESSXSWI1 1 HV
ESSXSWI2 1 LV
ESSXSWI3 1 HV
Synchronism and energizing check SECRSYN 1 HV
Tap changer position indication TPOSYLTC 1
Tap changer control with voltage regulator OLATCC (1) LV
Condition monitoring and supervision
Circuit-breaker condition monitoring SSCBR1 1 HV
SSCBR2 1 LV
SSCBR3 1 HV
Trip circuit supervision TCSSCBR1 1 HV
TCSSCBR2 1 LV
Current circuit supervision CCSPVC1 1 HV
CCSPVC2 1 LV
Advanced current circuit supervision for transformers CTSRCTF 1
Fuse failure supervision SEQSPVC 1 HV
Runtime counter for machines and devices MDSOPT 2
Measurement
Table continues on next page
RET620 33
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
Function A
IEC 61850
(CTs/VTs)
Three-phase current measurement CMMXU1 1 HV
CMMXU2 1 LV
Sequence current measurement CSMSQI1 1 HV
CSMSQI2 1 LV
Residual current measurement RESCMMXU1 1 HV
RESCMMXU2 1 LV
Three-phase voltage measurement VMMXU 1 HV
Single-phase voltage measurement VAMMXU2 1 LV
VAMMXU3 1 HV
Residual voltage measurement RESVMMXU 1 HV
Sequence voltage measurement VSMSQI 1 HV
Three-phase power and energy measurement PEMMXU 1 HV
Load profile record LDPRLRC 1 HV
Frequency measurement FMMXU 1 HV
Power quality
Current total demand distortion CMHAI 1 HV
Voltage total harmonic distortion VMHAI 1 HV
Voltage variation PHQVVR 1 HV
Voltage unbalance VSQVUB 1 HV
Other
Minimum pulse timer (2 pcs) TPGAPC 4
Minimum pulse timer (2 pcs, second resolution) TPSGAPC 2
Minimum pulse timer (2 pcs, minute resolution) TPMGAPC 2
Pulse timer (8 pcs) PTGAPC 2
Time delay off (8 pcs) TOFGAPC 4
Time delay on (8 pcs) TONGAPC 4
Set-reset (8 pcs) SRGAPC 4
Move (8 pcs) MVGAPC 4
Integer value move MVI4GAPC 4
Analog value scaling SCA4GAPC 4
Generic control point (16 pcs) SPCGAPC 3
Remote generic control points SPCRGAPC 1
Local generic control points SPCLGAPC 1
Generic up-down counters UDFCNT 12
Programmable buttons (16 buttons) FKEYGGIO 1
Logging functions
Disturbance recorder RDRE 1
Table continues on next page
34 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
Function A
IEC 61850
(CTs/VTs)
Fault recorder FLTRFRC 1
Sequence event recorder SER 1
1, 2, ... = Number of included instances. The instances of a protection function represent the number of
identical protection function blocks available in the standard configuration.
() = optional
HV = The function block is to be used on the high-voltage side in the application.
LV = The function block is to be used on the low-voltage side in the application.
1) Function uses calculated value when the high-impedance based restricted earth-fault protection is
used
2) Io is calculated from the measured phase currents
3.1.1 Addition of control functions for primary devices and the use
of binary inputs and outputs
If extra control functions intended for controllable primary devices are added to the
configuration, additional binary inputs and/or outputs are needed to complement the
default configuration.
The external I/O module’s binary inputs and outputs can be used for the less time-
critical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the protection relay’s default
configuration.
The suitability of the protection relay’s binary outputs which have been selected for
primary device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.
RET620 35
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
GUID-4576631D-C686-454F-8CF0-DC654779B178 V1 EN
Figure 12: Drawing symbol used in the manual and the default connection of the
LED function blocks in the configurations
36 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
L1
L2
L3
A
N
n
Positive
Current
Direction
a
da dn
RET620
X120 X100
60 -
1 210V
+ 1
U1 Uaux
2 N 2
60 - -
P1 3 210V
S1 U2 3
4 N IRF
S2 60 -
P2 5 210V 4
U3
6 N 5
7 1/5A 2)
IL1 PO1
8 N
9 1/5A 6
Uab IL2 7
10 N
11 1/5A
PO2
IL3
HV 12 N
8
13 1/5A
9
Io
14 N 10
SO1
P2 S2
11
12
P1 S1 X115 13
60 -
SO2
1 210V
U_SYN 14
P2 S2 2 N
60 - 16
3 210V
U_AVR PO3
P1 S1 4 N
LV 60 - 17
5 210V 15
Uo
6 N
19
TCS1 18
7 1/5A 2)
IL1B 20
8 N 22
9 1/5A PO4
IL2B
10 N 21
11 1/5A 23
IL3B TCS2 24
12 N
13 1/5A
IoB
14 N
P2
S2
X105
S1
P1
Uab
X110 X110
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
L1 7
22
L2 8 21
L3 BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X130 X130
1 mA 9
mA 1 SO1
2
10
3 11
RTD 1
4 12
5 RTD 1 GND SO2
6 13
RTD 2 14
7
8 RTD 2 GND
SO3
16
17
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
1) Order selectable -Optional
X15 2) The IED features an automatic short-circuit
1) mechanism in the CT connector when plug-in
Light sensor input 3
unit is detached
GUID-B8E8FE37-C9B8-45A0-953F-A3D0464FE251 V3 EN
RET620 37
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
X105/
BIO0005 module
X110 X105/
X110
1
BI 1 14
2
SO1
3 16
BI 2 15
4
17
5 SO2
BI 3
6 19
18
20
BI 4
7 SO3
22
8
BI 5 21
9 23
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
GUID-5298DCA3-4597-44C2-850A-889384DF423B V2 EN
BIO0007 module
X105
X105
1
BI 1
HSO1
2
BI 2 15
16
3 HSO2
BI 3
19
4 20
BI 4
5
HSO3
6
BI 5 23
24
7
BI 6
8
BI 7
9
BI 8
10
GUID-D019E095-29EF-41B1-BDF4-D9D427201B88 V2 EN
Figure 15: Optional BIO0007 module for fast outputs (slot X105)
RTD003 module
X105/
X110
5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22
GUID-987D427B-C5F7-4073-8D5F-D0C37BEAF5E5 V2 EN
38 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
Functional diagrams
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers.The positive
measuring direction of directional protection functions is towards the outgoing feeder.
The functional diagrams are divided into sections with each section constituting one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used several
times in the configuration. To separate the blocks from each other, the IEC 61850
name, IEC symbol and ANSI function number are appended with a running number,
that is an instance number, from one upwards.
3.5.1 Applications
The default configuration is mainly intended for the protection of two-winding power
transformers. The default configuration includes three-phase transformer differential
protection for two-winding transformers, numerical restricted earth-fault protection
for both the HV side and the LV side. Additionally, voltage regulation via automatic
control of an on-line tap changer is included.
RET620 39
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
The IED with a default configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality using PCM600.
40 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
3.5.2 Functions
RET620
Uo
UL1UL2UL3
U12 0. 0 kV
P 0.00 kW
- High-Speed Output module (optional)
- Local/Remote push-button on LHMI
Q 0.00 kVAr
IL2 0 A
- Self-supervision
3I (HV)
I ESC Clear - Time synchronization: IEEE-1588,
3I< I2> 3Ith>T 3I>>> SNTP, IRIG-B
37 46 49T 50P/51P O R
- User management
L
(LV)
3)
Status indication function for
Current transformer 8
primary object
18×
6×RTD OTHER FUNCTIONALITY
2×mA MAP12
MAP12
Io 3×
U12b ARC COLTC
50L/50NL 90V
3I
UL1UL2UL3
2× 4× 2× 2× (HV) U12b
U/f> 3U< U2> U1<
24 27 47O- 47U+
UL1UL2UL3 3× 3×
3× 6×
Uo Uo> 3U> f>/f<, UFLS/R
df/dt
59G 59 81LSH
81
REMARKS
2×
Master Trip Optional 3× No. of Calculated OR Alternative
Lockout relay function instances value function to be
94/86 Io/Uo
defined when
ordering
GUID-BFA69E71-CDBB-4333-A91F-001F2A8A1E6B V2 EN
Figure 17: Functionality overview of default configuration with conventional instrument transformer inputs
RET620 41
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
42 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
RET620 43
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
44 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
RET620 45
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
46 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
Additionally, all the digital inputs that are connected by default are also enabled with
the setting. Default triggering settings are selected depending on the connected input
signal type. Typically all protection START signals are selected to trigger the
disturbance recorded by default.
Table 17: Default analog channel selection and text settings
Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IoA
5 IL1B
6 IL2B
7 IL3B
8 IoB
9 Uo
10 U1
11 U2
12 U3
RET620 47
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
There are eight current channels and six voltage channels in this configuration.
X120 X115
60 - 1 60 -
1 210V
210V U_SYN
U1
2 2 N
N
60 - 60 -
3
3 210V
210V U_AVR
U2 3U
4 N
4 N
60 -
60 - 5
5 210V
210V Uo
U3 6
6 N
N
7 1/5A
7 1/5A
IL1B
IL1
8 N
8 N
9 1/5A
9 1/5A
IL2B 3IB
IL2 3I
10 N
10 N
11 1/5A
11 1/5A
IL3B
IL3
12 N
12 N
13 1/5A
13 1/5A
IoB
Io
14 N
14 N
GUID-B28195C5-9345-49D3-9A3B-BE85D1F57D62 V1 EN
The physical analog channels of all functions which require current or voltage inputs
in this configuration are listed in Table 20. Meaning of the symbols is explained in
Table 19.
48 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
RET620 49
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
50 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
The analog channels, measurements from CTs and VTs have fixed connections to the
different function blocks inside the relay. Exceptions from this rule are the 12 analog
RET620 51
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
channels available for the disturbance recorder function. These channels are freely
selectable and a part of the disturbance recorder’s parameter settings.
The signal marked with 3I represents the three phase currents from the high-voltage
side of the transformer. The signal marked with 3IB represents the three phase
currents from the low-voltage side of the transformer. The signal marked with Io
represents the ground current measured between the neutral point of the transformer
and grounding on the high-voltage side, and the signal marked with IoB represents
the ground current measured between the neutral point of the transformer and earthing
on the low-voltage side.
The signal marked with 3U represents the three phase system voltages from the high-
voltage side of the transformer. These inputs are typically connected in Delta. Star
connection is also possible. In addition, the signal marked with Uo represents the
measured residual voltage via VT open-delta connection.
The signal marked Usyn is measured from the VT on the high-voltage side of the
transformer. This signal is used to check synchronizing purposes. Care is taken in
setting the synchro-check function with correct phase angle correction, especially in
applications such as voltages, fed to synchro-check across a transformer with vector
shift.
The signal marked with Uavr is measured from the VT on the low-voltage side of the
transformer. This signal is used for tap changer control purposes. The input is fixed to
phase-to-phase voltage U12.
The relay offers six different setting groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the relay.
There are 16 programmable push buttons offered in the front panel of the unit. The
relay offers six different setting groups which the user can set based on individual
needs. Each group can then be activated or deactivated by using a programmable
button. In addition to this, the programmable button can be also used for manual
trigger of disturbance recorder, lower or raise tap changer, transformer control mode
changing, circuit breaker control interlocking bypass, master trip lockout reset, and so
on.
52 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
PROTECTION
SG_LOGIC_SEL
SG_1_ACT
BI_SG_2 SG_2_ACT
BI_SG_3 SG_3_ACT
BI_SG_4 SG_4_ACT
BI_SG_5 SG_5_ACT
BI_SG_6 SG_6_ACT
BEH_BLK
BEH_TST
SRGAPC1_S1
AND
SRGAPC1_S2
AND
FKEYGGIO1 SPCGAPC1
SRGAPC1_S3
R_TRIG
BLOCK AND
L1 K1 IN1 O1 SRGAPC1_S4 R_TRIG_Q
OR CLK Q
L2 K2 IN2 O2 AND
L3 K3 IN3 O3 SRGAPC1_S5
L4 K4 IN4 O4 AND
L5 K5 IN5 O5 SRGAPC1_S6
L6 K6 IN6 O6 AND
L7 K7 IN7 O7
L8 K8 IN8 O8 SPCGAPC1_O8_LOWER_REQUEST
L9 K9 IN9 O9 SPCGAPC1_O9_DR_MANUAL_TRIGGER
L10 K10 IN10 O10 SPCGAPC1_O10_LOCKOUT_RESET
L11 K11 IN11 O11 SPCGAPC1_O11_ITL_BYPASS_ENABLE
L12 K12 IN12 O12 SPCGAPC1_O12_PARALLEL_ENABLE
L13 K13 IN13 O13 SPCGAPC1_O13_AUTO_ENABLE
L14 K14 IN14 O14
L15 K15 IN15 O15
L16 K16 IN16 O16 SPCGAPC1_O16_RAISE_REQUEST
SRGAPC1
S1 Q1 BI_SG_2
AND R1 Q2 BI_SG_3
SPCGAPC1_O2
S2 Q3 BI_SG_4
AND R2 Q4 BI_SG_5
SPCGAPC1_O3
S3 Q5 BI_SG_6
R_TRIG_Q
AND R3 Q6
SPCGAPC1_O4
S4 Q7
AND R4 Q8
SPCGAPC1_O5
S5
AND R5
SPCGAPC1_O6
S6
R6
S7
R7
S8
R8
GUID-5E0E4D71-2EDB-4FE5-A811-3D7BC28FD513 V2 EN
The functional diagrams describe the relay’s protection functionality in detail and
picture the default connections.
RET620 53
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
TPGAPC2
IN1 OUT1
TR2PTDF1
3dI>T(1)
87T(1)
3I OPERATE LED 1
3IB OPR_LS
BLOCK OPR_HS
LED 2
BLK_OPR_LS BLKD2H
BLK_OPR_HS BLKD5H
BLKDWAV
GUID-0BC2B34D-033F-4BC8-80DA-76A6FFA2F78A V2 EN
For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF1.
The OPERATE signal is connected to the Master Trip and output X105-SO2 via
generic timer TPGAPC2. The OPR_LS output is connected to alarm LED 1, which is
used for biased low-stage operation indication, and the OPR_HS output is connected
to alarm LED 2, which is used for instantaneous high-stage operation indication.
54 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
PHLPTOC1
INRPHAR1
3I>(1)
3I2f >(1)
51P-1(1)
68(1)
3I BLK2H 3I OPERATE
ENA_MULT
OR LED 4
TPGAPC2
PHHPTOC1 DPHLPDOC1
3I>>(1) 3I>→ (1) X105-SO2
IN1 OUT1
51P-2(1) 67-1(1)
IN2 OUT2
OPERATE
3I OPERATE 3U OPERATE
PHHPTOC2_START START 3I
OR BLOCK START START
NON_DR
ENA_MULT ENA_MULT
PHIPTOC1 DPHHPDOC1
PHPTUC1 3I>>>(1) 3I>>→ (1)
3I<(1) 50P/51P(1) 67-2(1)
37(1)
3I OPERATE 3U OPERATE
3I
OPERATE BLOCK START START
3I
NON_DR
BLOCK START ENA_MULT
ENA_MULT
Blocking
PHLPTOC2
3I>(2)
51P-1(2)
3IB OPERATE
BLOCK START
ENA_MULT
PHPTUC2 PHHPTOC2
3I<(2) 3I>>(2)
37(2) 51P-2(2)
OPERATE
3IB OPERATE
3I OPERATE START
BLOCK START
BLOCK START
ENA_MULT
PHIPTOC2
3I>>>(2)
50P/51P(2)
3IB OPERATE
BLOCK START
ENA_MULT
GUID-CD98DE17-BF96-4D49-8703-AF360E394ECC V2 EN
Five stages for high-voltage side and three stages for low-voltage side as a total of
eight overcurrent stages are offered for overcurrent and short-circuit protection. Three
stages are for directional functionality DPHxPDOC, while the others are only for non-
directional overcurrent protection PHxPTOC. The high stage of high-voltage side
PHHPTOC1 and instantaneous stage of low-voltage side PHIPTOC2 can be blocked
by energizing the binary input X105-BI1. The inrush detection block’s INRPHAR1
output BLK2H enables either blocking the function or multiplying the active settings
for any of the described protection function blocks.
Two undercurrent stages PHPTUC1/2 are offered for undercurrent protection. The
START and OPERATE outputs from this function are connected to disturbance
recorder, but this function is not configured to trip the circuit breaker by default.
The OPERATE outputs are connected to the Master Trip and alarm LED 4, except for
those specially mentioned previously. LED 4 is used for combined protection operate
indication.
RET620 55
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
EFLPTOC1
Io>(1)
51N-1(1)
Io OPERATE
BLOCK START
ENA_MULT
EFHPTOC1
Io>>(1)
51N-2(1)
Io OPERATE
BLOCK START
ENA_MULT
DEFLPDEF2
DEFLPDEF1
Io>→ (1)
67N-1(1)
Io OPERATE
Uo START OR LED 4
BLOCK
ENA_MULT
RCA_CTL
DEFHPDEF1
Io>>→ (1) TPGAPC3
67N-2(1)
Io OPERATE
IN1 OUT1 X105-SO3
Uo START
IN2 OUT2
BLOCK
ENA_MULT
RCA_CTL
EFLPTOC2
Io>(2)
51N-1(2)
IoB OPERATE
BLOCK START
ENA_MULT
EFHPTOC2
Io>>(2)
51N-2(2)
IoB OPERATE
BLOCK START
ENA_MULT
GUID-04DB4F0B-3609-4108-8F81-68C07EAA5E57 V2 EN
Five stages for high-voltage side and two stages for low-voltage side, as a total of
seven stages, are offered for earth-fault protection. Two stages are for directional
functionality DEFxPDEF, while the others are only for non-directional earth-fault
protection EFxPTOC.
The OPERATE outputs are connected to the Master Trip and output X105-SO3 via
generic timer TPGAPC3, and also to the alarm LED 4.
56 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
HREFPDIF1
dIoHi>(1)
87NH(1)
Io OPERATE
BLOCK START
LREFPNDF1
dIoLo>(1)
87NL(1)
3I OPERATE
Io START
BLOCK BLK2H
HREFPDIF2 OR LED 3
dIoHi>(2)
87NH(2)
IoB OPERATE
BLOCK START
LREFPNDF2
dIoLo>(2)
87NL(2)
3IB OPERATE
IoB START
BLOCK BLK2H
GUID-360D0248-4B20-4D8C-8EEA-EADC0DE56DCE V2 EN
The restricted earth-fault current and the numerical differential current stage operate
exclusively on earth faults occurring in the protected area, that is, in the area between
the phase and neutral current transformers. An earth fault in this area appears as a
RET620 57
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
differential current between the residual current of the phase currents and the neutral
current of the conductor between the star-point of the transformer and earth.
The OPERATE outputs are connected to the Master Trip and alarm LED 3. LED 3 is
used for restricted earth-fault protection operate indication.
NSPTOC1
I2>(1)
46(1)
3I OPERATE
ENA_MULT
NSPTOC2
I2>(2)
46(2)
3IB OPERATE
ENA_MULT
T2PTTR1
3Ith>T/G/C (1)
49T/G/C (1)
3I OPERATE LED 5
BLOCK START
AMB_TEMP ALARM
BLK_CLOSE
TPGAPC3
NSPTOC1_OPERATE
IN1 OUT1
NSPTOC2_OPERATE OR IN2 OUT2 X105-SO4
T2PTTR1_OPERATE
GUID-503E49E8-7913-42A2-AC6C-9CF011424A73 V2 EN
58 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
The OPERATE outputs of NSPTOC1/2 are connected to the Master Trip and alarm
LED 4. The OPERATE output of T2PTTR1 is connected to the Master Trip and alarm
LED 5. The OPERATE outputs of these function are also connected to output X105-
SO4 via generic timer TPGAPC3.
PHPTOV3
PHPTOV2
PHPTOV1
3U>(1)
59(1)
3U OPERATE
BLOCK START
PHPTUV3
OR LED 4
PHPTUV2
PHPTUV1
3U<(1)
27(1)
3U OPERATE
GUID-56286915-7A5E-48F4-958B-67214935ECDB V2 EN
RET620 59
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
The OPERATE outputs of voltage functions are connected to the Master Trip and
alarm LED 4.
PSPTUV2
PSPTUV1
U1<(1)
47U+(1)
3U OPERATE
BLOCK START
OR LED 4
NSPTOV2
NSPTOV1
U2>(1)
47O-(1)
3U OPERATE
GUID-760892EE-2D68-4DDF-BB74-F68C78ED066E V2 EN
60 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
ROVPTOV3
ROVPTOV2
ROVPTOV1
Uo>(1)
59G(1)
Uo OPERATE LED 4
BLOCK START
TPGAPC3
IN2 OUT2
GUID-2ACB21C2-192D-46E9-9092-FCBD4D4E0A79 V2 EN
RET620 61
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
OEPVPH1
U/f>(1)
24(1)
3I OPERATE
3U START
F BLK_RESTART
BLOCK COOL_ACTIVE
OR LED 4
OEPVPH2
U/f>(2)
24(2)
3I OPERATE
3U START
F BLK_RESTART
BLOCK COOL_ACTIVE
GUID-590DD7EB-A5D3-44AE-A4FD-F21F8FCB0EB7 V2 EN
The OPERATE outputs are connected to the Master Trip and alarm LED 4.
62 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
FRPFRQ3
FRPFRQ2
FRPFRQ1
f>/f<,df/dt(1)
81(1)
3U OPERATE
BLOCK OPR_UFRQ
OPR_OFRQ
OPR_FRG
START
ST_UFRQ
ST_OFRQ
ST_FRG
OR LED 4
LSHDPFRQ6
LSHDPFRQ5
LSHDPFRQ4
LSHDPFRQ3
LSHDPFRQ2
LSHDPFRQ1
UFLS/R(1)
81LSH(1)
3U OPERATE
BLOCK OPR_FRQ
BLOCK_REST OPR_FRG
MAN_RESTORE START
ST_FRQ
ST_FRG
RESTORE
ST_REST
GUID-3B47BEC4-1249-4B9E-9F76-82FC6D31BFAB V2 EN
RET620 63
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
TR2PTDF1_OPERATE
PHLPTOC1/2_OPERATE
CCBRBRF1
PHHPTOC1/2_OPERATE
3I>/Io>BF(1)
PHIPTOC1/2_OPERATE 51BF/51NBF(1)
DPHLPDOC1_OPERATE 3I CB_FAULT_AL
DPHHPDOC1_OPERATE
Io TRBU X130-SO3
EFLPTOC1/2_OPERATE TRRET
OR START
EFHPTOC1/2_OPERATE
POSCLOSE
DEFLPDEF1/2_OPERATE
CB_FAULT
DEFHPDEF1_OPERATE
BLOCK
NSPTOC1/2_OPERATE
HREFPDIF1/2_OPERATE
LREFPNDF1/2_OPERATE
ARCSARC1/2/3_OPERATE
X110-BI1
TR2PTDF1_OPERATE
PHLPTOC1/2_OPERATE OR LED 7
CCBRBRF2
PHHPTOC1/2_OPERATE
3I>/Io>BF(2)
PHIPTOC1/2_OPERATE 51BF/51NBF(2)
DPHLPDOC1_OPERATE 3IB CB_FAULT_AL
DPHHPDOC1_OPERATE
IoB TRBU
EFLPTOC1/2_OPERATE TRRET
OR START
EFHPTOC1/2_OPERATE
POSCLOSE
DEFLPDEF1/2_OPERATE
CB_FAULT
DEFHPDEF1_OPERATE
BLOCK
NSPTOC1/2_OPERATE
HREFPDIF1/2_OPERATE
LREFPNDF1/2_OPERATE
ARCSARC1/2/3_OPERATE
X110-BI3
GUID-A800D27A-E627-4BC3-987D-507F51125F4D V2 EN
The breaker failure protection CCBRBRF1/2 is initiated via the START input by a
number of different protection stages in the relay. The breaker failure protection
function offers different operating modes associated with the circuit breaker position
and the measured phase and residual currents.
The breaker failure protection has two operating outputs: TRRET and TRBU. The
TRRET output is used for retripping its own breaker, CCBRBRF1 for high-voltage
side through the Master Trip 1 and CCBRBRF2 for low-voltage side through the
Master Trip 2. The TRBU output is used to give a backup trip to the breaker feeding
upstream. For this purpose, the TRBU output signal of CCBRBRF1 is connected to
output X130-SO3. The TRBU outputs of both functions are connected to alarm LED
7. LED 7 is used for backup (TRBU) operate indication.
64 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
ARC PROTECTION
ARCSARC3
ARCSARC2
ARCSARC1
ARC(1)
50L/50NL(1)
3I OPERATE LED 11
Io FLT_ARC_DET
BLOCK
REM_FLT_ARC
OPR_MODE
GUID-96A078F7-47C8-47C2-A289-18E3FB975F6C V2 EN
The arc protection offers individual function blocks for three arc sensors that can be
connected to the relay. Each arc protection function block has two different operation
modes, with or without phase and residual current check. The OPERATE outputs from
the arc protection function blocks are connected to the Master Trip and alarm LED 11.
RET620 65
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
DISTURBANCE RECORDER
RDRE1
GUID-CDC10093-A66F-4C11-9923-1036EAEF4F24 V2 EN
All START and OPERATE outputs from the protection stages are routed to trigger the
disturbance recorder or, alternatively, only to be recorded by the disturbance recorder,
depending on the parameter settings. Additionally, some selected signals from
different functions and some binary inputs from X110 and X105 are also connected.
66 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
The manual trigger signal from push button is used to trigger disturbance recorder
manually as needed.
RET620 67
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
TCSSCBR1
TCS(1)
TCM(1)
TRPPTRC1_TRIP
OR BLOCK ALARM
X110-BI2
TCSSCBR2
TCS(2)
TCM(2)
TRPPTRC2_TRIP
OR BLOCK ALARM
X110-BI4
CCSPVC1
MCS 3I(1)
CSM 3I(1)
3I FAIL
Io
ALARM
BLOCK
CCSPVC2
MCS 3I(2)
CSM 3I(2) OR LED 9
3IB FAIL
IoB
ALARM
BLOCK
SEQSPVC1
FUSEF(1)
60(1)
3I
FUSEF_3PH
3U
FUSEF_U
BLOCK
X110-BI1 CB_CLOSED
CB Closed Position (HV) DISCON_OPEN
GOO SERCV_BIN4_OUT MINCB_OPEN
MCB Open Position (HV)
X110-BI1 MDSOPT1
OPTS(1)
CB Closed Position (HV) OPTM(1)
X110-BI5
AND POS_ACTIVE ALARM
DC1 Closed Position(HV)
RESET WARNING
X110-BI7
BLOCK
DC2 Closed Position(HV)
X110-BI1
GOO SERCV_BIN0_OUT
DC1 Closed Position (LV)
GOOSERCV_BIN2_OUT
DC2 Closed Position (LV)
GUID-C2BF7084-B216-4FFA-8583-99BE4AFA5EE1 V2 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for output
X100-PO3 and TCSSCBR2 for output X100-PO4. Both functions are blocked by the
68 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
Master Trip TRPPTRC1 and TRPPTRC2, and the circuit breaker open signal. The
TCS alarm indication is connected to the LED 9.
The running time counter MDSOPT1/2 provides history data since last
commissioning. The alarm of the runtime counter is connected to alarm LED 9.
SECRSYN1
GOOSERCV_BIN4_OUT SYNC(1)
MCB Open Position (HV) 25(1)
3U SYNC_INPRO
GOOSERCV_BIN6_OUT U_SYN SYNC_OK LED 6
MCB Open Position (SYN) OR BLOCK CL_FAIL_AL
CL_COMMAND CMD_FAIL_AL
SEQSPVC1_FUSEF_U BYPASS LLDB
LLLB
DLLB
DLDB
GUID-216D649B-56E1-4376-BA74-1DD4821386E5 V2 EN
RET620 69
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
The main purpose of the synchronism and energizing check SECRSYN1 is to provide
control over the closing of the circuit breakers in power networks to prevent the
closing if the conditions for synchronism are not fulfilled. The energizing function
allows closing, for example, when one side of the breaker is dead.
SECRSYN1 measures voltages from high-voltage bus side and transformer high-
voltage side and compares them to set conditions. When all the measured quantities
are within the set limits, the output SYNC_OK is activated for allowing closing or
closing the circuit breaker. The SYNC_OK output signal is connected to the
ENA_CLOSE input of CBXCBR1/2 through control logic, and to alarm LED 6. The
colors of LED 6 indicate the status of SYNC_OK. If SYNC_OK is true, LED 6 is green,
and if SYNC_OK is false, LED 6 is red.
To ensure the validity of the measured voltages on both sides, MCB Open
Position (HV), MCB Open Position (SYN) and FUSEF_U from
SEQSPVC1 are connected to block SECRSYN1. HV and SYN MCB Open Position
come from the received GOOSE signal.
MASTER TRIP #1
TR2PTDF1_OPERATE
PHLPTOC1/2_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1/2_OPERATE
DPHLPDOC1_OPERATE
DPHHPDOC1_OPERATE
EFLPTOC1/2_OPERATE
EFHPTOC1/2_OPERATE
DEFLPDEF1/2_OPERATE TRPPTRC1
DEFHPDEF1_OPERATE Master Trip(1)
NSPTOC1/2_OPERATE 94/86(1)
ROVPTOV1/2/3_OPERATE
PHPTOV1/2/3_OPERATE OR OPERATE TRIP X100 PO3
PHPTUV1/2/3_OPERATE
PSPTUV1/2_OPERATE BLOCK CL_LKOUT
NSPTO V1/2_OPERATE RST_LKOUT
FRPFRQ1/2/3_OPERATE
LSHDPFRQ1/2/3/4/5/6_OPERATE
Wit h lock-out mode selection
OEPVPH1/2_OPERATE
HREFPDIF1/2_OPERATE
LREFPNDF1/2_OPERATE
MVGAPC1 T2PTTR1_OPERATE
ARCSARC1/2/3_OPERATE
CCBRBRF1_TRRET
GOOSERCV_BIN11_OUT IN1 Q1
Transformer Gas Relay External Trip IN2 Q2
GOOSERCV_BIN10_OUT
Transformer Gas Relay Alarm
SPCGAPC1_O10_LOCKOUT_RESET
MASTER TRIP #2
TR2PTDF1_OPERATE
PHLPTOC1/2_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1/2_OPERATE
DPHLPDOC1_OPERATE
DPHHPDOC1_OPERATE
EFLPTOC1/2_OPERATE
EFHPTOC1/2_OPERATE TRPPTRC2
DEFLPDEF1/2_OPERATE Master Trip(2)
DEFHPDEF1_OPERATE 94/86(2)
NSPTOC1/2_OPERATE
ROVPTOV1/2/3_OPERATE OR OPERATE TRIP X100 PO4
PHPTOV1/2/3_OPERATE
PHPTUV1/2/3_OPERATE BLOCK CL_LKOUT
PSPTUV1/2_OPERATE RST_LKOUT
NSPTO V1/2_OPERATE
FRPFRQ1/2/3_OPERATE
With lock-out mode selection
LSHDPFRQ1/2/3/4/5/6_OPERATE
OEPVPH1/2_OPERATE
HREFPDIF1/2_OPERATE
LREFPNDF1/2_OPERATE
T2PTTR1_OPERATE
ARCSARC1/2/3_OPERATE
CCBRBRF2_TRRET
GUID-7482085E-9961-4669-9855-98D88A5B6770 V2 EN
70 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
The operating signals from the protections and two GOOSE binary inputs are
connected to the two trip output contacts, output X100-PO3 and output X100-PO4,
via the corresponding Master Trips TRPPTRC1 and TRPPTRC2.
RET620 71
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
X110-BI2
DCXSWI1_CLOSEPOS (HV)
AND CB Open Position (HV)
DCXSWI2_CLOSEPOS (HV)
X110-BI1
AND
ESXSWI1_CLOSEPOS (LV) CB Closed Position (HV) CB_OPEN_COMMAND(HV)
CBXCBR1
OR I↔O CB(1)
ESXSWI1_OPENPOS (LV) X100-PO3
I↔O CB(1)
TRPPTRC1_TRIP POSOPEN SELECTED
AND POSCLOSE EXE_OP
SECRSYN1_SYNC_OK
ENA_OPEN EXE_CL X100-PO1
X105-BI4
ENA_CLOSE OPENPOS
CB Spring Charged (HV) BLK_OPEN CLOSEPOS
BLK_CLOSE OKPOS
X105-BI3 CB_CLOSE_COMMAND(HV)
AU_OPEN OPEN_ENAD
Gas Pressure Alarm (HV)
AU_CLOSE CLOSE_ENAD
TRIP
SYNC_OK
SPCGAPC1_O11_ITL_BYPASS_ENABLE SYNC_ITL_BYP
SSCBR1
CBCM(1)
52CM(1)
3I TRV_T_OP_ALM
BLOCK TRV_T_CL_ALM
CB_OPEN_COMMAND(HV) POSOPEN SPR_CHR_ALM
OR OPR_ALM
TRPPTRC1_TRIP POSCLOSE
OPR_LO
OPEN_CB_EXE OR LED 8
IPOW_ALM
CB_CLOSE_COMMAND(HV) CLOSE_CB_EXE IPOW_LO
PRES_ALM_IN CB_LIFE_ALM
PRES_LO_IN MON_ALM
SPR_CHR_ST PRES_ALM
SPR_CHR PRES_LO
RST_IPOW OPENPOS
RST_CB_WEAR INVALIDPOS
RST_TRV_T CLOSEPO S
RST_SPR_T
X110-BI4
CB Open Position (LV)
DCXSWI3_CLOSEPOS (LV)
AND X110-BI3
DCXSWI4_CLOSEPOS (LV)
CB Closed Position (LV) CB_OPEN_COMMAND(LV)
AND CBXCBR1
ESXSWI1_CLOSEPOS (LV)
I↔O CB(1)
I↔O CB(1) X100-PO4
OR
ESXSWI1_OPENPOS (LV) POSOPEN SELECTED
POSCLOSE EXE_OP
TRPPTRC2_TRIP ENA_OPEN EXE_CL X100-PO2
AND ENA_CLOSE
SECRSYN1_SYNC_OK OPENPOS
X105-BI6 BLK_OPEN CLOSEPOS
CB Spring Charged (LV) BLK_CLOSE OKPOS
CB_CLOSE_COMMAND(LV)
AU_OPEN OPEN_ENAD
X105-BI5 AU_CLOSE CLOSE_ENAD
Gas Pressure Alarm (LV) TRIP
SYNC_OK
SPCGAPC1_O11_ITL_BYPASS_ENABLE SYNC_ITL_BYP
SSCBR2
CBCM(2)
52CM(2)
3I TRV_T_OP_ALM
BLOCK TRV_T_CL_ALM
CB_OPEN_COMMAND(LV) POSOPEN SPR_CHR_ALM
OR OPR_ALM
TRPPTRC2_TRIP POSCLOSE
OPR_LO
OPEN_CB_EXE OR LED 8
IPOW_ALM
CB_CLOSE_COMMAND(LV) CLOSE_CB_EXE IPOW_LO
PRES_ALM_IN CB_LIFE_ALM
PRES_LO_IN MON_ALM
SPR_CHR_ST PRES_ALM
SPR_CHR PRES_LO
RST_IPOW OPENPOS
RST_CB_WEAR INVALIDPOS
RST_TRV_T CLOSEPOS
RST_SPR_T
GUID-4513917C-E9F2-43DB-9484-46C6AE8B2A9A V2 EN
The circuit breaker closing is blocked when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
72 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
position statuses of related primary equipment disconnector and earthing switch, the
condition of the circuit breaker (CB gas pressure alarm, CB spring charged), the
master trip logics and the result of synchronism/energizing check. This, together with
non-active trip signal, activates the ENA_CLOSE signal to the circuit breaker control
function block.
One push button can be used through SPCGAPC1_O11, which is connected to the
SYNC_ITL_BYP inputs of CBXCBR1 and CBXCBR2, to ignore the status of the
ENA_CLOSE inputs. However, the BLK_CLOSE input signals are not bypassed with
the interlocking bypass functionality, as they always have the higher priority.
RET620 73
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
X110-BI6
DC1 Open Position (HV)
DCXSWI1
X110-BI5 I↔O DCC(1)
DC1 Closed Position (HV) I↔O DCC(1) X110-SO2
POSOPEN SELECTED
POSCLOSE EXE_OP
ENA_OPEN EXE_CL
CBXCBR1_OPENPOS (HV) ENA_CLOSE OPENPOS
BLK_OPEN X110-SO1
CLOSEPOS
BLK_CLOSE OKPOS
AU_OPEN OPEN_ENAD
AU_CLOSE CLOSE_ENAD
ITL_BYPASS
X110-BI8
DC2 Open Position (HV)
DCXSWI2
X110-BI7 I↔O DCC(2)
DC2 Closed Position (HV)
I↔O DCC(2) X110-SO4
PO SOPEN SELECTED
PO SCLOSE EXE_OP
ENA_OPEN EXE_CL
CBXCBR1_OPENPOS (HV) ENA_CLOSE OPENPOS
X110-SO3
BLK_OPEN CLOSEPO S
BLK_CLOSE OKPOS
AU_OPEN OPEN_ENAD
AU_CLOSE CLOSE_ENAD
ITL_BYPASS
GOOSERCV_BIN1_OUT
DC1 Open Position (LV)
DCXSWI3
GOOSERCV_BIN0_OUT I↔O DCC(3)
DC1 Closed Position (LV) I↔O DCC(3)
POSOPEN SELECTED
PO SCLOSE EXE_OP MVGAPC2_IN2
ENA_OPEN EXE_CL MVGAPC2_IN1
CBXCBR2_OPENPOS (LV) ENA_CLOSE OPENPOS
BLK_OPEN CLOSEPOS
BLK_CLOSE OKPOS
AU_OPEN OPEN_ENAD
AU_CLOSE CLOSE_ENAD
ITL_BYPASS
GOOSERCV_BIN3_OUT
DC2 Open Position (LV)
DCXSWI4
GOOSERCV_BIN2_OUT I↔O DCC(4)
DC2 Closed Position (LV)
I↔O DCC(4)
POSOPEN SELECTED
POSCLOSE EXE_OP MVGAPC2_IN4
ENA_OPEN EXE_CL MVGAPC2_IN3
CBXCBR2_OPENPOS (LV) ENA_CLOSE OPENPOS
BLK_OPEN CLOSEPOS
BLK_CLOSE OKPOS
AU_OPEN OPEN_ENAD
AU_CLOSE CLOSE_ENAD
ITL_BYPASS
X105-BI8
ES1 Open Position (LV)
X105-BI7
ES1 Closed Position (LV)
ESXSWI1
I↔O ESC(1)
DCXSWI1_CLOSEPOS (HV) I↔O ESC(1) X100-SO2
AND POSOPEN SELECTED
DCXSWI2_CLOSEPOS (HV)
POSCLOSE EXE_OP
CBXCBR1_CLOSEPOS (HV)
ENA_OPEN EXE_CL
AND ENA_CLOSE OPENPOS
DCXSWI3_CLOSEPOS (LV) X100-SO1
BLK_OPEN CLOSEPOS
DCXSWI4_CLOSEPOS (LV) AND BLK_CLOSE OKPOS
CBXCBR2_CLOSEPOS (LV) AU_OPEN OPEN_ENAD
AU_CLOSE CLOSE_ENAD
ITL_BYPASS
GUID-DCAD4F43-7C34-4305-A87A-82A47FD9F6A5 V2 EN
74 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
There are two types of disconnector and earthing switch blocks available.
DCXSWI1...4 and ESXSWI1 are controllable type. By default, the controllable
blocks are connected in default configuration logic. If the status-only type is preferred,
the status-only type of disconnector and earthing switch blocks can be used instead of
the controllable blocks type. The connection and configuration of the status-only
blocks can be made using PCM600.
The binary inputs 5 and 6 of the card X110 are used for high-voltage side busbar
disconnector 1 DCXSWI1 position indication. The binary inputs 7 and 8 of the card
X110 are used for high-voltage side busbar disconnector 2 DCXSWI2 position
indication.
Table 21: HV disconnector 1 position indicated by binary inputs
Primary device position Input to be energized
X110-BI5 X110-BI6
HV disconnector 1 closed ●
HV disconnector 1 open ●
RET620 75
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
The binary inputs 7 and 8 of card X105 are designed for the position indication of the
earthing switch.
Table 25: Earthing switch position indicated by binary inputs
Primary device position Input to be energized
X105-BI7 X105-BI8
Earthing switch closed ●
Earthing switch open ●
Control of disconnector 1 and disconnector 2 is enabled only when the circuit breaker
in the high-voltage side is in the open position. Control of disconnector 3 and
disconnector 4 is enabled only when the circuit breaker in the low-voltage side is in the
open position.
Closing of the earthing switch is enabled when the conditions are met.
• Disconnector 1, disconnector 2 and high-voltage side circuit breaker are not in the
closed position at the same time.
• Disconnector 3, disconnector 4 and low-voltage side circuit breaker are not in the
closed position at the same time.
76 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
PHLPTOC1/2_START
PHHPTOC1/2_START COMMON ALARM INDICATION 1 & 2
PHIPTOC1/2_START
DPHLPDOC1_START
DPHHPDOC1_START
EFLPTOC1/2_START
EFHPTOC1/2_START
DEFLPDEF1/2_START
DEFHPDEF1_START
NSPTOC1/2_START
ROVPTOV1/2/3_START OR
PHPTOV1/2/3_START
PHPTUV1/2/3_START
PSPTUV1/2_START
NSPTOV1/2_START
FRPFRQ1/2/3_START
LSHDPFRQ1/2/3/4/5/6_START
OEPVPH1/2_START
HREFPDIF1/2_START
LREFPNDF1/2_START
T2PTTR1_START TPGAPC1
GUID-3F3A3B81-D4A6-49C4-8B58-BB7EFF85F7AC V2 EN
The signal outputs from the relay are connected to give dedicated information.
TPGAPC functions are timers and they are used for setting the minimum pulse length
for the outputs. There are four generic timers TPGAPC1…4 available in the relay. The
remaining ones not described in the functional diagram are available in PCM600 for
connection where applicable.
Common alarm indications are intended to be sent out by GOOSE. It is also connected
to MVGPAC to generate local events.
RET620 77
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
TPOSYLTC1
TPOSM(1)
84T(1)
BI0
BI1
BI2
BI3
BI4
BI5
T_F32_INT8
SIGN_BIT
mA
X130-mA1 F32 INT8 TAP_POS
GUID-F78F6CBC-8C3B-4B90-B4FC-FA78DC7C27ED V2 EN
To increase the sensitivity of the stabilized differential function, the tap position
information from the tap changer is connected to the relay via the tap changer position
indication function TPOSYLTC1. TPOSYLTC1 is connected to the mA input of the
RTD card.
OLATCC1
COLTC(1) X130-SO2
90V(1)
3IB RAISE_OWN
U_AVR LOWER_OWN
TPOSYLTC1_TAP_POS TAP_POS FLLW1_CTL
TR1_TAP_POS FLLW2_CTL X130-SO1
TR2_TAP_POS FLLW3_CTL
TR3_TAP_POS BLKD_I_LOD
SPCGAPC1_O16_RAISE_REQUEST RAISE_LOCAL BLKD_U_UN
SPCGAPC1_O8_LOWER_REQUEST LOWER_LOCAL BLKD_U_OV
TAPCHG_FLLW BLKD_I_CIR
SPCGAPC1_O12_PARALLEL_ENABLE PARALLEL BLKD_LTCBLK
SPCGAPC1_O13_AUTO_ENABLE AUTO ALARM MVGAPC2_IN7
CBXCBR2_CLOSEPOS (LV) CON_STATUS PAR_FAIL
CCSPVC2_FAIL (LV) LTC_BLOCK PARALLEL
TCO AUTO
RSV TIMER_ON
TR1_I_AMPL
TR1_I_ANGL
X105-BI2
TR2_I_AMPL
Tap Changer Operate TR2_I_ANGL
TR3_I_AMPL
TR3_I_ANGL
LED 10
GUID-A26ADF11-3BF4-46B1-83D8-EC9B45C7580A V2 EN
78 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
Both manual and automatic controlling of the on-load tap changer is done via
OLATCC1. The controlling of the local tap changer can be done through external
push button via SPCGAPC1, SPCGAPC1_O8 input for lower request and
SPCGAPC1_O16 for raise request. The operation mode of OLATCC1 can be
controlled externally by push buttons, via SPCGAPC_12 and SPCGAPC_13.
The binary input X105-BI2 indicating the tap changer operating information can be
connected to TCO and the alarm LED 10.
The output commands are routed to the binary outputs, the raising command is
connected to X130-SO2 and the lower command is connected to X130-SO1.
The common alarm signal of OLATCC1 is connected to the GOOSE binary output
MVGAPC2_IN7.
RET620 79
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
POWER QUALITY
CMHAI1
PQM3I(1)
PQM3I(1)
BLOCK ALARM
VMHAI1
PQM3U(1)
PQM3V(1)
BLOCK ALARM
PHQVVR1
PQMU(1)
PQMV(1)
BLOCK ALARM
OPERATE
START
SWELLST
DIPST
INTST
VSQVUB1
PQUUB(1)
PQVUB(1)
BLOCK MN_UNB_AL
PCT_UNB_AL
OBS_PR_ACT
GUID-B23D448E-A074-4678-9858-DE4C022E59A1 V1 EN
The power quality function CMHAI1 is used to measure the harmonic contents of the
phase current.
The power quality function VMHAI1 is used to measure the harmonic contents of the
phase voltages.
The power quality function PHQVVR1 is used to measure the voltage variation, that
is, sags and swells.
80 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
The voltage unbalance power quality function VSQVUB1 monitors the voltage
unbalance conditions in power networks. It is used to monitor the commitment of
power supply utility of providing a balanced voltage supply on a continuous basis.
VSQVUB provides statistics which can be used to verify the compliance of the power
quality.
The above functions are included in default configuration for demonstration purposes
only, but not configured by default. The functions can be configured as needed.
MEASUREMENT FUNCTION
LOW_ALARM LOW_ALARM
LO W_WARN LOW_WARN
PEMMXU1
P, E (1)
P, E (1)
RSTACM
CMMXU2 VAMMXU2
3I (2) U_A (2)
3I (2) V_A (2)
BLOCK HIGH_ALARM BLOCK HIGH_ALARM
HIGH_WARN HIGH_WARN
LOW_ALARM LOW_ALARM LDPRLRC1
LOW_WARN LOW_WARN LOADPROF (1)
LOADPROF (1)
RSTMEM MEM_WARN
MEM_ALARM
CSMSQI1 VAMMXU3
I1, I2, I0 (1) U_A (3)
I1, I2, I0 (1) V_A (3)
BLOCK HIGH_ALARM
HIGH_WARN
LOW_ALARM
FLTRFRC1
LOW_WARN
FAULTREC (1)
CSMSQI2 FAULTREC (1)
I1, I2, I0 (2)
BLOCK
I1, I2, I0 (2)
CB_CLRD
VSMSQI1
U1, U2, U0 (1)
V1, V2, V0 (1)
RESCMMXU1
Io (1)
In (1)
RESVMMXU1
BLOCK HIGH_ALARM Uo (1)
HIGH_WARN
Vn (1)
BLOCK HIGH_ALARM
HIGH_WARN
RESCMMXU2
Io (2)
In (2)
BLOCK HIGH_ALARM
HIGH_WARN
GUID-815B0DED-E2B5-4126-A2C8-E7AF37744669 V1 EN
The high-voltage side and low-voltage side phase current inputs to the relay are
measured by three-phase current measurement CMMXU1 and CMMXU2. The
RET620 81
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
current input is connected to the X120 and X115 cards in the back panel. The sequence
current measurement CSMSQI1 and CSMSQI2 measures the high-voltage side and
low-voltage side sequence current respectively and the residual current measurement
RESCMMXU1 and RESCMMXU2 measures the high-voltage side and low-voltage
side residual current.
The three-phase bus side phase voltage inputs to the relay are measured by three-phase
voltage measurement VMMXU1. The voltage input is connected to the X120 card in
the back panel. The sequence voltage measurement VSMSQI1 measures the sequence
voltage and the residual voltage measurement RESVMMXU1 measures the residual
voltage. The single-phase voltage measurement VAMMXU2 and VAMMXU3
measures the voltage of the transformer high-voltage side and low-voltage side
respectively.
The measurements can be seen in the LHMI and they are available under the
measurement option in the menu selection. Based on the settings, function blocks can
generate low alarm or warning and high alarm or warning signals for the measured
current values.
The frequency measurement FMMXU1 of the power system and the three-phase
power and energy measurement PEMMXU1 are available. Load profile record
LDPRLRC1 is included in the measurements sheet. LDPRLRC1 offers the ability to
observe the loading history of the corresponding bay. FLTRFRC1 is used to record the
monitor data during the fault condition. The records enable the analysis of recent
power system events.
Optional functions are available in the relay default content when a corresponding
option is selected while ordering the relay. However, the functions are not pre-
engineered to be part of the default configuration. The functions can be engineered
into use.
82 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
OLATCC1
COLTC(1) X130-SO2
90V(1)
3IB RAISE_OWN
U_AVR LOWER_OWN
TPOSYLTC1_TAP_POS TAP_POS FLLW1_CTL
TR1_TAP_POS FLLW2_CTL X130-SO1
TR2_TAP_POS FLLW3_CTL
TR3_TAP_POS BLKD_I_LOD
SPCGAPC1_O16_RAISE_REQUEST RAISE_LOCAL BLKD_U_UN
SPCGAPC1_O8_LOWER_REQUEST LOWER_LOCAL BLKD_U_OV
TAPCHG_FLLW BLKD_I_CIR
SPCGAPC1_O12_PARALLEL_ENABLE PARALLEL BLKD_LTCBLK
SPCGAPC1_O13_AUTO_ENABLE AUTO ALARM MVGAPC2_IN7
CBXCBR2_CLOSEPOS (LV) CON_STATUS PAR_FAIL
CCSPVC2_FAIL (LV) LTC_BLOCK PARALLEL
TCO AUTO
RSV TIMER_ON
TR1_I_AMPL
TR1_I_ANGL
X105-BI2
TR2_I_AMPL
Tap Changer Operate TR2_I_ANGL
TR3_I_AMPL
TR3_I_ANGL
LED 10
GUID-379F089A-F7C1-4F36-A407-5B3B845233CA V1 EN
Tap changer control with voltage regulator function is included as optional function.
The on load tap changer control functionality is provided with the OLATCC1
function. Both manual and automatic controlling of the on load tap changer is done via
OLATCC1. The controlling of the local tap changer can be done through external
push button via SPCGAPC1; SPCGAPC1_O8 input for lower request and
SPCGAPC1_O16 for raise request. The operation mode of OLATCC1 can be
controlled externally by push buttons via SPCGAPC_12 and SPCGAPC_13.
The binary input X105-BI2 indicating the tap changer operating information can be
connected to TCO the alarm LED 10.
The output commands are routed to the binary outputs, the raise command is
connected to X130-SO2 and the lower command is connected to X130-SO1.
RET620 83
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
X120
1 60 -
210V
U1 PHPTOV1
2 N
60 -
3 210V
U2 ULTVTR1
4 N
5 60 -
210V
6 U3
N
SECRSYN1
X115
1 60 -
210V VAMMXU3
U_SYN Usyn ULTVTR3
2 N
60 -
60 -
3 210V
U_AVR Uavr ULTVTR2 OLATCC1
4 N
60 -
5 210V
Uo Uo RESTVTR1 VAMMXU2
6 N
ROVPTOV1
*Measured Uo
GUID-1A2A94E0-51AD-46FD-8498-45FC75B86250 V1 EN
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and
Uo. Thus, when the IEDs are used as senders, and the three phase-to-
phase voltages and the residual voltage are connected to the hardware
channels, the three phase-to-earth voltages are calculated from the
input and sent through IEC 61850-9-2 LE.
84 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
SMVRCV ULTVTR1
UL1 UL1 ALARM ULTVTR1[1]_ALARM
UL2 UL2 WARNING ULTVTR1[1]_WARNING
UL3 UL3
Uo MINCB_OPEN
GUID-04B73564-6E17-49E6-8F47-5E7804D7AC55 V1 EN
All three signals UL1, UL2 and UL3 must always be connected
between SMVRCV and ULTVTR1 in Application Configuration.
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and
Uo. When the three phase voltage channels are received from IEC
61850-9-2 LE, the setting VT connection in Configuration/Analog
inputs/Voltage (3U,VT) must be “Wye”.
X120
1 60 -
210V
U1 9 -2 PHPTOV1
2 N
60 -
LE
3 210V
U2
ULTVTR1
4 N
5 60 -
210V
6 U3
N
SECRSYN1
X115
1 60 -
210V VAMMXU3
U_SYN Usyn ULTVTR3
2 N
60 -
60 -
3 210V
U_AVR Uavr ULTVTR2 OLATCC1
4 N
60 -
5 210V
Uo Uo RESTVTR1 VAMMXU2
6 N
ROVPTOV1
*Measured Uo
GUID-958DE574-D129-4B8E-BB19-54CF672760A2 V1 EN
Figure 46: ULTVTR1 uses three phase voltages from received IEC 61850-9-2
LE sample value
RET620 85
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
SMVRCV
UL1
UL2 RESTVTR1
UL3
Uo Uo ALARM RESTVTR1[1]_ALARM
WARNING RESTVTR1[1]_WARNING
GUID-B7081724-A5F9-4CBE-847C-A7D43A00222D V1 EN
X120
1 60 -
210V
U1 PHPTOV1
2 N
60 -
3 210V
U2
3U ULTVTR1
4 N
5 60 -
210V
6 U3
N
SECRSYN1
X115
1 60 -
210V VAMMXU3
U_SYN Usyn ULTVTR3
2 N
60 -
60 -
3 210V
U_AVR Uavr ULTVTR2 OLATCC1
4 N
9-2
60 - LE
5 210V
Uo RESTVTR1 VAMMXU2
6 N
ROVPTOV1
*Measured Uo
GUID-AB3B3ECC-1881-4E96-8BF7-42E2D46421CC V1 EN
Figure 48: RESTVTR1 uses residual voltages from received IEC 61850-9-2 LE
sample value
86 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
SMVRCV ULTVTR1
UL1 UL1 ALARM ULTVTR1[1]_ALARM
UL2 UL2 WARNING ULTVTR1[1]_WARNING
UL3 UL3
Uo MINCB_OPEN
RESTVTR1
Uo ALARM RESTVTR1[1]_ALARM
WARNING RESTVTR1[1]_WARNING
GUID-B7026859-C00C-4809-BFD0-7CABA3CBA333 V1 EN
SMVRCV can also be connected to both ULTVTR1 and RESTVTR1. This means that
both the three phase voltages U1, U2, U3 and the residual voltage Uo are replaced by
the received IEC 61850-9-2 LE sample value.
All three signals UL1, UL2 and UL3 must always be connected
between SMVRCV and ULTVTR1 in Application Configuration.
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and
Uo. When the three phase voltage channels are received from IEC
61850-9-2 LE, the setting VT connection in Configuration/Analog
inputs/Voltage (3U,VT) must be “Wye”.
X120
1 60 -
210V
U1 9-2 PHPTOV1
2 N
60 -
L E
3 210V
U2
ULTVTR1
4 N
5 60 -
210V
6 U3
N
SECRSYN1
X115
1 60 -
210V VAMMXU3
U_SYN Usyn ULTVTR3
2 N
60 -
60 -
3 210V
U_AVR Uavr ULTVTR2 OLATCC1
4 N
9-2
60 - LE
5 210V
Uo RESTVTR1 VAMMXU2
6 N
ROVPTOV1
*Measured Uo
GUID-D58E7C8F-B758-4995-B9B0-A6DF78AF59D0 V1 EN
Figure 50: Both ULTVTR1 and RESTVTR1 use voltages from received IEC
61850-9-2 LE sample value
RET620 87
Application Manual
Section 3 1MRS757659 D
RET620 default configurations
SMVRCV ULTVTR2
UL1 E
USUL1 ALARM
UL2
N OT UL2 WARNING
ULTVTR2[2]_ALARM
ULTVTR2[2]_WARNING
DO
UL3 UL3
Uo MINCB_OPEN
GUID-D1025F4C-2276-4DC5-9953-E1F9978F499B V1 EN
SMVRCV ULTVTR3
UL1 UL1 ALARM ULTVTR3[3]_ALARM
UL2 UL2 WARNING ULTVTR3[3]_WARNING
UL3 UL3
Uo MINCB_OPEN
GUID-76A64768-C875-44B5-A8EF-29676ACA3145 V1 EN
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and
Uo. When U_SYN as a single channel input is received from IEC
61850-9-2 LE, the setting VT connection in Configuration/Analog
inputs/Voltage (3UC,VT) must be “UL1”.
88 RET620
Application Manual
1MRS757659 D Section 3
RET620 default configurations
X120
1 60 -
210V
U1 PHPTOV1
2 N
60 -
3 210V
U2
3U ULTVTR1
4 N
5 60 -
210V
6 U3
N
SECRSYN1
X115 9-2
1 60 - L E VAMMXU3
210V
U_SYN ULTVTR3
2 N
60 -
60 -
3 210V
U_AVR Uavr ULTVTR2 OLATCC1
4 N
60 -
5 210V
Uo Uo RESTVTR1 VAMMXU2
6 N
ROVPTOV1
*Measured Uo
GUID-FEC55D13-7347-4D61-B3F6-6F0E33C5B760 V1 EN
Figure 53: ULTVTR3 uses UL1 voltage from received IEC 61850-9-2 LE sample
value
RET620 89
Application Manual
90
1MRS757659 D Section 4
IED physical connections
4.1 Inputs
RET620 91
Application Manual
Section 4 1MRS757659 D
IED physical connections
RTD/mA inputs of slot X105 are available in the optional RTD module (RTD0003).
Table 33: RTD/mA inputs
Terminal Description
X105:5-6 mA1 (AI1), +
mA1 (AI1), -
X105:7-8 mA2 (AI2), +
mA2 (AI2), -
X105:9-10 RTD1 (AI3), +
RTD1 (AI3), -
X105:11-12 RTD2 (AI4), +
RTD2 (AI4), -
X105:13-14 RTD3 (AI5), +
RTD3 (AI5), -
Table continues on next page
92 RET620
Application Manual
1MRS757659 D Section 4
IED physical connections
Terminal Description
X105:15 Common1)
X105:16 Common2)
X105:17-18 RTD4 (AI6), +
RTD4 (AI6), -
X105:19-20 RTD5 (AI7), +
RTD5 (AI7), -
X105:21-22 RTD6 (AI8), +
RTD6 (AI8), -
RET620 93
Application Manual
Section 4 1MRS757659 D
IED physical connections
Terminal Description
X110:9 BI6, -
X110:10 BI6, +
X110:11 BI7, +
X110:12 BI7, -
X110:12 BI8, -
X110:13 BI8, +
Binary inputs of slot X105 are optional for configuration A. One option is to use
BIO0005 and the other one is to use BIO0007.
Table 36: Binary input terminals X105:1-13 (with optional BIO0005)
Terminal Description
X105:1 BI1,+
X105:2 BI1,-
X105:3 BI2,+
X105:4 BI2,-
X105:5 BI3,+
X105:6 BI3,-
X105:6 BI4,-
X105:7 BI4,+
X105:8 BI5,+
X105:9 BI5,-
X105:9 BI6,-
X105:10 BI6,+
X105:11 BI7,+
X105:12 BI7,-
X105:12 BI8,-
X105:13 BI8,+
94 RET620
Application Manual
1MRS757659 D Section 4
IED physical connections
Terminal Description
X105:7 BI6,-
X105:10 BI6,+
X105:8 BI7,+
X105:10 BI7,-
X105:9 BI8,-
X105:10 BI8,+
4.2 Outputs
RET620 95
Application Manual
Section 4 1MRS757659 D
IED physical connections
Terminal Description
X100:16 PO3, NO
X100:17 PO3, NO
X100:18 PO3 (TCS1 input), NO
X100:19 PO3 (TCS1 input), NO
X100:20 PO4, NO (TCS resistor)
X100:21 PO4, NO
X100:22 PO4, NO
X100:23 PO4 (TCS2 input), NO
X100:24 PO4 (TCS2 input), NO
All other outputs can be used for signaling on start and tripping of the protection relay.
On delivery from the factory, the start and alarm signals from all the protection stages
are routed to signaling outputs.
Table 40: Output contacts X100:10-14
Terminal Description
X100:10 SO1, common
X100:11 SO1, NC
X100:12 SO1, NO
X100:13 SO2, NO
X100:14 SO2, NO
96 RET620
Application Manual
1MRS757659 D Section 4
IED physical connections
Output contacts of X105 are optional for configuration A. One option is to use
BIO0005 and the other one is to use BIO0007.
Table 43: Output contacts X105:14-24 (with optional BIO0005)
Terminal Description
X105:14 SO1,common
X105:15 SO1,NO
X105:16 SO1,NC
X105:17 SO2,common
X105:18 SO2,NO
X105:19 SO2,NC
X105:20 SO3,common
X105:21 SO3,NO
X105:22 SO3,NC
X105:23 SO4,common
X105:24 SO4,NO
4.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of the
protection relay. Under normal operating conditions, the protection relay is energized
and the contact is closed (X100:3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the contact X100:3-5 drops off and the
contact X100:3-4 closes.
RET620 97
Application Manual
Section 4 1MRS757659 D
IED physical connections
98 RET620
Application Manual
1MRS757659 D Section 5
Glossary
Section 5 Glossary
RET620 99
Application Manual
Section 5 1MRS757659 D
Glossary
100 RET620
Application Manual
1MRS757659 D Section 5
Glossary
RET620 101
Application Manual
—
ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
ABB
Nanjing SAC Power Grid Automation Co.,
Ltd.
No.39 Shuige Road, Jiangning District
211153 Nanjing, China
Phone +86 25 69832000
Fax +86 25 69833000
www.abb.com/mediumvoltage
www.abb.com/relion
www.abb.com/substationautomation
1MRS757659 D