Medium Voltage Cable-File PDF
Medium Voltage Cable-File PDF
Medium Voltage Cable-File PDF
6/6 kV
Cu / XLPE / CTS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen,
Application:
For installation indoor, in ground direct buried,
for power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.355 172 154 5.20 1.03
50 0.387 0.494 0.328 205 181 7.43 1.03
70 0.268 0.342 0.310 253 220 10.40 1.03
95 0.193 0.247 0.298 307 263 14.11 1.03
120 0.153 0.196 0.286 352 298 17.83 1.03
150 0.124 0.159 0.379 397 332 22.29 1.03
185 0.0991 0.128 0.272 453 374 27.49 1.03
240 0.0754 0.098 0.266 529 431 35.66 1.37
300 0.0601 0.079 0.259 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEBY 3 x (35 - 300) mm2 6/10 kV
Cu / XLPE / CTS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen,
Application:
For installation indoor, in ground direct buried,
for power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.378 172 154 5.20 1.03
50 0.387 0.494 0.350 205 181 7.43 1.03
70 0.268 0.342 0.330 253 220 10.40 1.03
95 0.193 0.247 0.316 307 263 14.11 1.03
120 0.153 0.196 0.303 352 298 17.83 1.03
150 0.124 0.159 0.295 397 332 22.29 1.03
185 0.0991 0.128 0.287 453 374 27.49 1.03
240 0.0754 0.098 0.279 529 431 35.66 1.37
300 0.0601 0.079 0.268 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEBY 3 x (35 - 300) mm2 8.7/15 kV
Cu / XLPE / CTS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen,
Application:
For installation indoor, in ground direct buried,
for power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.404 172 154 5.20 1.03
50 0.387 0.494 0.374 205 181 7.43 1.03
70 0.268 0.342 0.352 253 220 10.40 1.03
95 0.193 0.247 0.337 307 263 14.11 1.03
120 0.153 0.196 0.322 352 298 17.83 1.03
150 0.124 0.159 0.313 397 332 22.29 1.03
185 0.0991 0.128 0.304 453 374 27.49 1.03
240 0.0754 0.098 0.295 529 431 35.66 1.37
300 0.0601 0.079 0.282 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEBY 3 x (35 - 300) mm2 12/20 kV
Cu / XLPE / CTS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen,
Application:
For installation indoor, in ground direct buried,
for power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.425 172 154 5.20 1.03
50 0.387 0.494 0.394 205 181 7.43 1.03
70 0.268 0.342 0.370 253 220 10.40 1.03
95 0.193 0.247 0.353 307 263 14.11 1.03
120 0.153 0.196 0.338 352 298 17.83 1.03
150 0.124 0.159 0.328 397 332 22.29 1.03
185 0.0991 0.128 0.319 453 374 27.49 1.03
240 0.0754 0.098 0.308 529 431 35.66 1.37
300 0.0601 0.079 0.294 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEFGbY 3 x (35 - 300) mm2 3.6/6 kV
Cu / XLPE / CTS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Inner Sheathed,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.355 172 154 5.20 1.03
50 0.387 0.494 0.328 205 181 7.43 1.03
70 0.268 0.342 0.310 253 220 10.40 1.03
95 0.193 0.247 0.298 307 263 14.11 1.03
120 0.153 0.196 0.286 352 298 17.83 1.03
150 0.124 0.159 0.379 397 332 22.29 1.03
185 0.0991 0.128 0.272 453 374 27.49 1.03
240 0.0754 0.098 0.266 529 431 35.66 1.37
300 0.0601 0.079 0.259 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEFGbY 3 x (35 - 300) mm2 6/10 kV
Cu / XLPE / CTS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Inner Sheathed,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.378 172 154 5.20 1.03
50 0.387 0.494 0.350 205 181 7.43 1.03
70 0.268 0.342 0.330 253 220 10.40 1.03
95 0.193 0.247 0.316 307 263 14.11 1.03
120 0.153 0.196 0.303 352 298 17.83 1.03
150 0.124 0.159 0.295 397 332 22.29 1.03
185 0.0991 0.128 0.287 453 374 27.49 1.03
240 0.0754 0.098 0.279 529 431 35.66 1.37
300 0.0601 0.079 0.268 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEFGbY 3 x (35 - 300) mm2 8.7/15 kV
Cu / XLPE / CTS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Inner Sheathed,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.404 172 154 5.20 1.03
50 0.387 0.494 0.374 205 181 7.43 1.03
70 0.268 0.342 0.352 253 220 10.40 1.03
95 0.193 0.247 0.337 307 263 14.11 1.03
120 0.153 0.196 0.322 352 298 17.83 1.03
150 0.124 0.159 0.313 397 332 22.29 1.03
185 0.0991 0.128 0.304 453 374 27.49 1.03
240 0.0754 0.098 0.295 529 431 35.66 1.37
300 0.0601 0.079 0.282 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEFGbY 3 x (35 - 300) mm2 12/20 kV
Cu / XLPE / CTS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Inner Sheathed,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.425 172 154 5.20 1.03
50 0.387 0.494 0.394 205 181 7.43 1.03
70 0.268 0.342 0.370 253 220 10.40 1.03
95 0.193 0.247 0.353 307 263 14.11 1.03
120 0.153 0.196 0.338 352 298 17.83 1.03
150 0.124 0.159 0.328 397 332 22.29 1.03
185 0.0991 0.128 0.319 453 374 27.49 1.03
240 0.0754 0.098 0.308 529 431 35.66 1.37
300 0.0601 0.079 0.294 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEFGbY 3 x (35 - 300) mm2 18/30 kV
Cu / XLPE / CTS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Inner Sheathed,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.469 172 154 5.20 1.03
50 0.387 0.494 0.436 205 181 7.43 1.03
70 0.268 0.342 0.409 253 220 10.40 1.03
95 0.193 0.247 0.390 307 263 14.11 1.03
120 0.153 0.196 0.373 352 298 17.83 1.03
150 0.124 0.159 0.362 397 332 22.29 1.03
185 0.0991 0.128 0.351 453 374 27.49 1.03
240 0.0754 0.098 0.338 529 431 35.66 1.37
300 0.0601 0.079 0.322 599 482 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 3.6/6 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.355 170 153 5.20 1.03
50 0.387 0.494 0.328 204 181 7.43 1.03
70 0.268 0.342 0.310 253 221 10.40 1.03
95 0.193 0.247 0.298 304 262 14.11 1.03
120 0.153 0.196 0.286 351 298 17.83 1.03
150 0.124 0.159 0.379 398 334 22.29 1.03
185 0.0991 0.128 0.272 455 377 27.49 1.03
240 0.0754 0.098 0.266 531 434 35.66 1.37
300 0.0601 0.079 0.259 606 489 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 6/10 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.378 170 153 5.20 1.03
50 0.387 0.494 0.350 204 181 7.43 1.03
70 0.268 0.342 0.330 253 221 10.40 1.03
95 0.193 0.247 0.316 304 262 14.11 1.03
120 0.153 0.196 0.303 351 298 17.83 1.03
150 0.124 0.159 0.295 398 334 22.29 1.03
185 0.0991 0.128 0.287 455 377 27.49 1.03
240 0.0754 0.098 0.279 531 434 35.66 1.37
300 0.0601 0.079 0.268 606 489 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 8.7/10 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.404 170 153 5.20 1.03
50 0.387 0.494 0.374 204 181 7.43 1.03
70 0.268 0.342 0.352 253 221 10.40 1.03
95 0.193 0.247 0.337 304 262 14.11 1.03
120 0.153 0.196 0.322 351 298 17.83 1.03
150 0.124 0.159 0.313 398 334 22.29 1.03
185 0.0991 0.128 0.304 455 377 27.49 1.03
240 0.0754 0.098 0.295 531 434 35.66 1.37
300 0.0601 0.079 0.282 606 489 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 12/20 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.425 170 153 5.20 1.03
50 0.387 0.494 0.394 204 181 7.43 1.03
70 0.268 0.342 0.370 253 221 10.40 1.03
95 0.193 0.247 0.353 304 262 14.11 1.03
120 0.153 0.196 0.338 351 298 17.83 1.03
150 0.124 0.159 0.328 398 334 22.29 1.03
185 0.0991 0.128 0.319 455 377 27.49 1.03
240 0.0754 0.098 0.308 531 434 35.66 1.37
300 0.0601 0.079 0.294 606 489 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 18/30 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.469 170 153 5.20 1.03
50 0.387 0.494 0.436 204 181 7.43 1.03
70 0.268 0.342 0.409 253 221 10.40 1.03
95 0.193 0.247 0.390 304 262 14.11 1.03
120 0.153 0.196 0.373 351 298 17.83 1.03
150 0.124 0.159 0.362 398 334 22.29 1.03
185 0.0991 0.128 0.351 455 377 27.49 1.03
240 0.0754 0.098 0.338 531 434 35.66 1.37
300 0.0601 0.079 0.322 606 489 44.57 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 3.6/6 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.393 170 153 5.20 2.85
50 0.387 0.494 0.364 204 181 7.43 2.85
70 0.268 0.342 0.343 253 221 10.40 2.85
95 0.193 0.247 0.328 304 262 14.11 2.85
120 0.153 0.196 0.314 351 298 17.83 2.85
150 0.124 0.159 0.306 398 334 22.29 4.45
185 0.0991 0.128 0.297 455 377 27.49 4.45
240 0.0754 0.098 0.289 531 434 35.66 4.45
300 0.0601 0.079 0.282 606 489 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 6/10 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.413 170 153 5.20 2.85
50 0.387 0.494 0.383 204 181 7.43 2.85
70 0.268 0.342 0.360 253 221 10.40 2.85
95 0.193 0.247 0.344 304 262 14.11 2.85
120 0.153 0.196 0.329 351 298 17.83 2.85
150 0.124 0.159 0.320 398 334 22.29 4.45
185 0.0991 0.128 0.310 455 377 27.49 4.45
240 0.0754 0.098 0.300 531 434 35.66 4.45
300 0.0601 0.079 0.287 606 489 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 8.7/15 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.435 170 153 5.20 2.85
50 0.387 0.494 0.404 204 181 7.43 2.85
70 0.268 0.342 0.379 253 221 10.40 2.85
95 0.193 0.247 0.362 304 262 14.11 2.85
120 0.153 0.196 0.346 351 298 17.83 2.85
150 0.124 0.159 0.336 398 334 22.29 4.45
185 0.0991 0.128 0.326 455 377 27.49 4.45
240 0.0754 0.098 0.315 531 434 35.66 4.45
300 0.0601 0.079 0.301 606 489 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEY 3 x (35 - 300) mm2 12/20 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.453 170 153 5.20 2.85
50 0.387 0.494 0.421 204 181 7.43 2.85
70 0.268 0.342 0.395 253 221 10.40 2.85
95 0.193 0.247 0.377 304 262 14.11 2.85
120 0.153 0.196 0.360 351 298 17.83 2.85
150 0.124 0.159 0.350 398 334 22.29 4.45
185 0.0991 0.128 0.339 455 377 27.49 4.45
240 0.0754 0.098 0.327 531 434 35.66 4.45
300 0.0601 0.079 0.312 606 489 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYBY 3 x (35 - 300) mm2 3.6/6 kV
Cu / XLPE / CWS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Inner Sheathed / DSTA / PVC Sheathed)
Application:
For installation indoors, in ground direct burried.
For power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.393 172 154 5.20 2.85
50 0.387 0.494 0.364 205 181 7.43 2.85
70 0.268 0.342 0.343 253 220 10.40 2.85
95 0.193 0.247 0.328 307 263 14.11 2.85
120 0.153 0.196 0.314 352 298 17.83 2.85
150 0.124 0.159 0.306 397 332 22.29 4.45
185 0.0991 0.128 0.297 453 374 27.49 4.45
240 0.0754 0.098 0.289 529 431 35.66 4.45
300 0.0601 0.079 0.282 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYBY 3 x (35 - 300) mm2 6/10 kV
Cu / XLPE / CWS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Inner Sheathed / DSTA / PVC Sheathed)
Application:
For installation indoors, in ground direct burried.
For power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.413 172 154 5.20 2.85
50 0.387 0.494 0.383 205 181 7.43 2.85
70 0.268 0.342 0.360 253 220 10.40 2.85
95 0.193 0.247 0.344 307 263 14.11 2.85
120 0.153 0.196 0.329 352 298 17.83 2.85
150 0.124 0.159 0.320 397 332 22.29 4.45
185 0.0991 0.128 0.310 453 374 27.49 4.45
240 0.0754 0.098 0.300 529 431 35.66 4.45
300 0.0601 0.079 0.287 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYBY 3 x (35 - 300) mm2 8.7/15 kV
Cu / XLPE / CWS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Inner Sheathed / DSTA / PVC Sheathed)
Application:
For installation indoors, in ground direct burried.
For power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.435 172 154 5.20 2.85
50 0.387 0.494 0.404 205 181 7.43 2.85
70 0.268 0.342 0.379 253 220 10.40 2.85
95 0.193 0.247 0.362 307 263 14.11 2.85
120 0.153 0.196 0.346 352 298 17.83 2.85
150 0.124 0.159 0.336 397 332 22.29 4.45
185 0.0991 0.128 0.326 453 374 27.49 4.45
240 0.0754 0.098 0.315 529 431 35.66 4.45
300 0.0601 0.079 0.301 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYBY 3 x (35 - 300) mm2 12/20 kV
Cu / XLPE / CWS / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Inner Sheathed / DSTA / PVC Sheathed)
Application:
For installation indoors, in ground direct burried.
For power station and switchgear, if there is a risk
that low mechanical damage may occur.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.453 172 154 5.20 2.85
50 0.387 0.494 0.421 205 181 7.43 2.85
70 0.268 0.342 0.395 253 220 10.40 2.85
95 0.193 0.247 0.377 307 263 14.11 2.85
120 0.153 0.196 0.360 352 298 17.83 2.85
150 0.124 0.159 0.350 397 332 22.29 4.45
185 0.0991 0.128 0.339 453 374 27.49 4.45
240 0.0754 0.098 0.327 529 431 35.66 4.45
300 0.0601 0.079 0.312 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYFGbY 3 x (35 - 300) mm2 3.6/6 kV
Cu / XLPE / CWS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.393 172 154 5.20 2.85
50 0.387 0.494 0.364 205 181 7.43 2.85
70 0.268 0.342 0.343 253 220 10.40 2.85
95 0.193 0.247 0.328 307 263 14.11 2.85
120 0.153 0.196 0.314 352 298 17.83 2.85
150 0.124 0.159 0.306 397 332 22.29 4.45
185 0.0991 0.128 0.297 453 374 27.49 4.45
240 0.0754 0.098 0.289 529 431 35.66 4.45
300 0.0601 0.079 0.282 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYFGbY 3 x (35 - 300) mm2 6/10 kV
Cu / XLPE / CWS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.413 172 154 5.20 2.85
50 0.387 0.494 0.383 205 181 7.43 2.85
70 0.268 0.342 0.360 253 220 10.40 2.85
95 0.193 0.247 0.344 307 263 14.11 2.85
120 0.153 0.196 0.329 352 298 17.83 2.85
150 0.124 0.159 0.320 397 332 22.29 4.45
185 0.0991 0.128 0.310 453 374 27.49 4.45
240 0.0754 0.098 0.300 529 431 35.66 4.45
300 0.0601 0.079 0.287 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSEYFGbY 3 x (35 - 300) mm2 8.7/15 kV
Cu / XLPE / CWS / PVC / GSFA / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
35 0.524 0.668 0.435 172 154 5.20 2.85
50 0.387 0.494 0.404 205 181 7.43 2.85
70 0.268 0.342 0.379 253 220 10.40 2.85
95 0.193 0.247 0.362 307 263 14.11 2.85
120 0.153 0.196 0.346 352 298 17.83 2.85
150 0.124 0.159 0.336 397 332 22.29 4.45
185 0.0991 0.128 0.326 453 374 27.49 4.45
240 0.0754 0.098 0.315 529 431 35.66 4.45
300 0.0601 0.079 0.301 599 482 44.57 4.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 3.6/6 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Fire Resistance Nom Overall Cable
Copper Conductor
Cross Section Diameter Weight
Oil Resistance
Conductor Screen
UV Resistance Area approx. approx.
XLPE Insulation
Flame Retardant Cat. A, B, C
Insulation Screen mm mm kg/km
Flame Retardant Non Category
Copper Tape Screen
Heat Resistance 35 18.1 625
Non-hygroscopic Tape
Anti Termite 50 19.5 805
RED PVC Outer sheath Anti Rodent 70 21.5 1,030
Low Smoke Zero Halagen
95 23.0 1,290
120 25.0 1,525
Note: 150 26.5 1,865
Conductor Shape 185 28.0 2,230
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 30.5 2,780
300 34.0 3,395
Standard Packing
400 37.0 4,390
35 - 300 sqmm supplied in wooden drum @ 1000
Application: 500 41.0 5,325
meters
For power station and switchgear as well as sta- 400 - 630 sqmm supplied in wooden drum on 630 45.5 6,705
tion because of small bending radius in confined available length
spaces indoors. As underground because of light Length Tolerance per drum 2%
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.393 0.439 198 166 238 172 5.20 1.14
50 0.387 0.494 0.374 0.420 238 196 286 203 7.43 1.14
70 0.268 0.342 0.345 0.391 296 239 356 246 10.40 1.14
95 0.193 0.247 0.329 0.375 361 285 434 293 14.11 1.14
120 0.153 0.196 0.319 0.365 417 323 500 332 17.83 1.14
150 0.124 0.159 0.312 0.358 473 361 559 366 22.29 1.14
185 0.0991 0.128 0.303 0.350 543 406 637 410 27.49 1.14
240 0.0754 0.098 0.297 0.343 641 469 745 470 35.66 1.14
300 0.0601 0.079 0.288 0.334 735 526 846 524 44.57 1.14
400 0.0470 0.063 0.281 0.327 845 590 938 572 59.43 1.14
500 0.0366 0.051 0.274 0.320 974 755 999 772 74.29 1.14
630 0.0283 0.042 0.267 0.314 1118 846 1146 864 93.60 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 6/10 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Fire Resistance Nom Overall Cable
Copper Conductor
Cross Section Diameter Weight
Oil Resistance
Conductor Screen
UV Resistance Area approx. approx.
XLPE Insulation
Flame Retardant Cat. A, B, C
Insulation Screen mm mm kg/km
Flame Retardant Non Category
Copper Tape Screen
Heat Resistance 35 20.5 695
Non-hygroscopic Tape
Anti Termite 50 22.0 885
RED PVC Outer sheath Anti Rodent 70 24.0 1,115
Low Smoke Zero Halagen
95 25.0 1,385
120 27.0 1,625
Note: 150 28.5 1,965
Conductor Shape 185 30.0 2,335
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 32.0 2,875
300 35.0 3,475
Standard Packing
400 38.0 4,450
35 - 300 sqmm supplied in wooden drum @ 1000
Application: 500 42.0 5,365
meters
For power station and switchgear as well as sta- 400 - 630 sqmm supplied in wooden drum on 630 48.0 6,740
tion because of small bending radius in confined available length
spaces indoors. As underground because of light Length Tolerance per drum 2%
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.418 0.464 198 166 238 172 5.20 1.14
50 0.387 0.494 0.389 0.435 238 196 286 203 7.43 1.14
70 0.268 0.342 0.363 0.409 296 239 356 246 10.40 1.14
95 0.193 0.247 0.350 0.396 361 285 434 293 14.11 1.14
120 0.153 0.196 0.335 0.381 417 323 500 332 17.83 1.14
150 0.124 0.159 0.326 0.373 473 361 559 366 22.29 1.14
185 0.0991 0.128 0.317 0.363 543 406 637 410 27.49 1.14
240 0.0754 0.098 0.307 0.353 641 469 745 470 35.66 1.14
300 0.0601 0.079 0.294 0.340 735 526 846 524 44.57 1.14
400 0.0470 0.063 0.286 0.332 845 590 938 572 59.43 1.14
500 0.0366 0.051 0.279 0.325 974 755 999 772 74.29 1.14
630 0.0283 0.042 0.269 0.316 1118 846 1146 864 93.60 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 8.7/15 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Fire Resistance Nom Overall Cable
Copper Conductor
Cross Section Diameter Weight
Oil Resistance
Conductor Screen
UV Resistance Area approx. approx.
XLPE Insulation
Flame Retardant Cat. A, B, C
Insulation Screen mm mm kg/km
Flame Retardant Non Category
Copper Tape Screen
Heat Resistance 35 23.0 795
Non-hygroscopic Tape
Anti Termite 50 24.0 985
RED PVC Outer sheath Anti Rodent 70 26.0 1,220
Low Smoke Zero Halagen
95 28.0 1,505
120 29.5 1,745
Note: 150 31.0 2,090
Conductor Shape 185 32.5 2,470
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 35.0 3,020
300 38.0 3,630
Standard Packing
400 40.5 4,615
35 - 300 sqmm supplied in wooden drum @ 1000
Application: 500 44.0 5,545
meters
For power station and switchgear as well as sta- 400 - 630 sqmm supplied in wooden drum on 630 48.5 6,935
tion because of small bending radius in confined available length
spaces indoors. As underground because of light Length Tolerance per drum 2%
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.438 0.484 198 166 238 172 5.20 1.14
50 0.387 0.494 0.407 0.453 238 196 286 203 7.43 1.14
70 0.268 0.342 0.383 0.429 296 239 356 246 10.40 1.14
95 0.193 0.247 0.366 0.412 361 285 434 293 14.11 1.14
120 0.153 0.196 0.351 0.397 417 323 500 332 17.83 1.14
150 0.124 0.159 0.341 0.388 473 361 559 366 22.29 1.14
185 0.0991 0.128 0.332 0.378 543 406 637 410 27.49 1.14
240 0.0754 0.098 0.321 0.367 641 469 745 470 35.66 1.14
300 0.0601 0.079 0.308 0.354 735 526 846 524 44.57 1.14
400 0.0470 0.063 0.298 0.344 845 590 938 572 59.43 1.14
500 0.0366 0.051 0.288 0.335 974 755 999 772 74.29 1.14
630 0.0283 0.042 0.279 0.325 1118 846 1146 864 93.60 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 12/20 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Fire Resistance Nom Overall Cable
Copper Conductor
Cross Section Diameter Weight
Oil Resistance
Conductor Screen
UV Resistance Area approx. approx.
XLPE Insulation
Flame Retardant Cat. A, B, C
Insulation Screen mm mm kg/km
Flame Retardant Non Category
Copper Tape Screen
Heat Resistance 35 25.0 890
Non-hygroscopic Tape
Anti Termite 50 26.5 1,085
RED PVC Outer sheath Anti Rodent 70 28.5 1,325
Low Smoke Zero Halagen
95 30.0 1,615
120 32.0 1,865
Note: 150 33.0 2,215
Conductor Shape 185 35.0 2,600
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 37.0 3,155
300 40.0 3,775
Standard Packing
400 43.0 4,775
35 - 300 sqmm supplied in wooden drum @ 1000
Application: 500 46.5 5,715
meters
For power station and switchgear as well as sta- 400 - 630 sqmm supplied in wooden drum on 630 51.0 7,125
tion because of small bending radius in confined available length
spaces indoors. As underground because of light Length Tolerance per drum 2%
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.457 0.503 198 166 238 172 5.20 1.14
50 0.387 0.494 0.425 0.371 238 196 286 203 7.43 1.14
70 0.268 0.342 0.399 0.456 296 239 356 246 10.40 1.14
95 0.193 0.247 0.382 0.428 361 285 434 293 14.11 1.14
120 0.153 0.196 0.366 0.412 417 323 500 332 17.83 1.14
150 0.124 0.159 0.355 0.402 473 361 559 366 22.29 1.14
185 0.0991 0.128 0.345 0.392 543 406 637 410 27.49 1.14
240 0.0754 0.098 0.334 0.380 641 469 745 470 35.66 1.14
300 0.0601 0.079 0.319 0.365 735 526 846 524 44.57 1.14
400 0.0470 0.063 0.309 0.355 845 590 938 572 59.43 1.14
500 0.0366 0.051 0.298 0.344 974 755 999 772 74.29 1.14
630 0.0283 0.042 0.288 0.334 1118 846 1146 864 93.60 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 18/30 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Fire Resistance Nom Overall Cable
Copper Conductor
Cross Section Diameter Weight
Oil Resistance
Conductor Screen
UV Resistance Area approx. approx.
XLPE Insulation
Flame Retardant Cat. A, B, C
Insulation Screen mm mm kg/km
Flame Retardant Non Category
Copper Tape Screen
Heat Resistance 35 31.0 1,165
Non-hygroscopic Tape
Anti Termite 50 32.0 1,375
RED PVC Outer sheath Anti Rodent 70 34.0 1,630
Low Smoke Zero Halagen
95 36.0 1,935
120 37.5 2,195
Note: 150 39.0 2,560
Conductor Shape 185 40.5 2,955
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 42.5 3,535
300 46.0 4,180
Standard Packing
400 48.5 5,205
35 - 300 sqmm supplied in wooden drum @ 1000
Application: 500 52.0 6,180
meters
For power station and switchgear as well as sta- 400 - 630 sqmm supplied in wooden drum on 630 56.5 7,625
tion because of small bending radius in confined available length
spaces indoors. As underground because of light Length Tolerance per drum 2%
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.497 0.544 198 166 238 172 5.20 1.14
50 0.387 0.494 0.463 0.510 238 196 286 203 7.43 1.14
70 0.268 0.342 0.435 0.482 296 239 356 246 10.40 1.14
95 0.193 0.247 0.416 0.462 361 285 434 293 14.11 1.14
120 0.153 0.196 0.398 0.445 417 323 500 332 17.83 1.14
150 0.124 0.159 0.387 0.433 473 361 559 366 22.29 1.14
185 0.0991 0.128 0.375 0.422 543 406 637 410 27.49 1.14
240 0.0754 0.098 0.362 0.408 641 469 745 470 35.66 1.14
300 0.0601 0.079 0.346 0.392 735 526 846 524 44.57 1.14
400 0.0470 0.063 0.334 0.380 845 590 938 572 59.43 1.14
500 0.0366 0.051 0.321 0.367 974 755 999 772 74.29 1.14
630 0.0283 0.042 0.309 0.356 1118 846 1146 864 93.60 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 3.6/6 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Copper Conductor
Fire Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen Oil Resistance
XLPE Insulation UV Resistance Area approx. approx.
Insulation Screen Flame Retardant Cat. A, B, C
Semi-Conductive WBT mm mm kg/km
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape
Non-Conductive WBT Heat Resistance 35 24.5 915
Anti Termite 50 25.5 1,095
RED PVC Outer sheath Anti Rodent 70 27.5 1,320
Low Smoke Zero Halagen
95 29.0 1,585
120 30.5 1,820
Note: 150 32.0 2,245
Conductor Shape 185 33.5 2,610
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 35.5 3,150
300 39.0 3,755
Standard Packing
400 42.0 4,835
35 - 300 sqmm supplied in wooden drum @ 1000
meters 500 46.0 5,760
Application: 400 - 630 sqmm supplied in wooden drum on 630 50.0 7,130
For power station and switchgear as well as sta- available length
tion because of small bending radius in confined Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.450 0.496 198 166 238 172 5.20 2.85
50 0.387 0.494 0.418 0.464 238 196 286 203 7.43 2.85
70 0.268 0.342 0.392 0.438 296 239 356 246 10.40 2.85
95 0.193 0.247 0.374 0.420 361 285 434 293 14.11 2.85
120 0.153 0.196 0.357 0.404 417 323 500 332 17.83 2.85
150 0.124 0.159 0.348 0.394 473 361 559 366 22.29 4.45
185 0.0991 0.128 0.337 0.383 543 406 637 410 27.49 4.45
240 0.0754 0.098 0.326 0.372 641 469 745 470 35.66 4.45
300 0.0601 0.079 0.314 0.360 735 526 846 524 44.57 4.45
400 0.0470 0.063 0.305 0.351 845 590 938 572 59.43 6.23
500 0.0366 0.051 0.295 0.342 974 755 999 772 74.29 6.23
630 0.0283 0.042 0.285 0.331 1118 846 1146 864 93.60 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 6/10 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Copper Conductor
Fire Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen Oil Resistance
XLPE Insulation UV Resistance Area approx. approx.
Insulation Screen Flame Retardant Cat. A, B, C
Semi-Conductive WBT mm mm kg/km
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape
Non-Conductive WBT Heat Resistance 35 26.0 985
Anti Termite 50 27.5 1,175
RED PVC Outer sheath Anti Rodent 70 29.5 1,405
Low Smoke Zero Halagen
95 31.0 1,675
120 32.5 1,910
Note: 150 34.0 2,335
Conductor Shape 185 35.0 2,705
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 37.0 3,240
300 40.0 3,835
Standard Packing
400 43.0 4,890
35 - 300 sqmm supplied in wooden drum @ 1000
meters 500 46.0 5,790
Application: 400 - 630 sqmm supplied in wooden drum on 630 51.0 7,160
For power station and switchgear as well as sta- available length
tion because of small bending radius in confined Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.465 0.511 198 166 238 172 5.20 2.85
50 0.387 0.494 0.432 0.478 238 196 286 203 7.43 2.85
70 0.268 0.342 0.406 0.452 296 239 356 246 10.40 2.85
95 0.193 0.247 0.387 0.433 361 285 434 293 14.11 2.85
120 0.153 0.196 0.370 0.416 417 323 500 332 17.83 2.85
150 0.124 0.159 0.359 0.405 473 361 559 366 22.29 4.45
185 0.0991 0.128 0.348 0.394 543 406 637 410 27.49 4.45
240 0.0754 0.098 0.336 0.382 641 469 745 470 35.66 4.45
300 0.0601 0.079 0.320 0.366 735 526 846 524 44.57 4.45
400 0.0470 0.063 0.308 0.355 845 590 938 572 59.43 6.23
500 0.0366 0.051 0.297 0.343 974 755 999 772 74.29 6.23
630 0.0283 0.042 0.286 0.333 1118 846 1146 864 93.60 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 8.7/15 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Copper Conductor
Fire Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen Oil Resistance
XLPE Insulation UV Resistance Area approx. approx.
Insulation Screen Flame Retardant Cat. A, B, C
Semi-Conductive WBT mm mm kg/km
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape
Non-Conductive WBT Heat Resistance 35 28.5 1,085
Anti Termite 50 30.0 1,280
RED PVC Outer sheath Anti Rodent 70 32.0 1,510
Low Smoke Zero Halagen
95 33.0 1,790
120 35.0 2,030
Note: 150 39.0 2,460
Conductor Shape 185 38.0 2,835
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 39.5 3,375
300 42.5 3,980
Standard Packing
400 45.0 5,045
35 - 300 sqmm supplied in wooden drum @ 1000
meters 500 48.5 5,955
Application: 400 - 630 sqmm supplied in wooden drum on 630 53.0 7,365
For power station and switchgear as well as sta- available length
tion because of small bending radius in confined Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.483 0.528 198 166 238 172 5.20 2.85
50 0.387 0.494 0.448 0.495 238 196 286 203 7.43 2.85
70 0.268 0.342 0.421 0.468 296 239 356 246 10.40 2.85
95 0.193 0.247 0.402 0.448 361 285 434 293 14.11 2.85
120 0.153 0.196 0.384 0.430 417 323 500 332 17.83 2.85
150 0.124 0.159 0.388 0.435 473 361 559 366 22.29 4.45
185 0.0991 0.128 0.361 0.407 543 406 637 410 27.49 4.45
240 0.0754 0.098 0.348 0.394 641 469 745 470 35.66 4.45
300 0.0601 0.079 0.331 0.378 735 526 846 524 44.57 4.45
400 0.0470 0.063 0.319 0.366 845 590 938 572 59.43 6.23
500 0.0366 0.051 0.307 0.353 974 755 999 772 74.29 6.23
630 0.0283 0.042 0.297 0.343 1118 846 1146 864 93.60 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XSY 1 x (35 - 630) mm2 12/20 kV
Cu / XLPE / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Copper Conductor
Fire Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen Oil Resistance
XLPE Insulation UV Resistance Area approx. approx.
Insulation Screen Flame Retardant Cat. A, B, C
Semi-Conductive WBT mm mm kg/km
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape
Non-Conductive WBT Heat Resistance 35 31.0 1,180
Anti Termite 50 32.0 1,375
RED PVC Outer sheath Anti Rodent 70 34.0 1,615
Low Smoke Zero Halagen
95 35.5 1,900
120 37.0 2,145
Note: 150 38.0 2,580
Conductor Shape 185 40.0 2,955
35 - 630 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 42.0 3,505
300 44.5 4,115
Standard Packing
400 47.0 5,190
35 - 300 sqmm supplied in wooden drum @ 1000
meters 500 51.0 6,110
Application: 400 - 630 sqmm supplied in wooden drum on 630 55.0 7,535
For power station and switchgear as well as sta- available length
tion because of small bending radius in confined Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.497 0.543 198 166 238 172 5.20 2.85
50 0.387 0.494 0.462 0.509 238 196 286 203 7.43 2.85
70 0.268 0.342 0.434 0.480 296 239 356 246 10.40 2.85
95 0.193 0.247 0.414 0.460 361 285 434 293 14.11 2.85
120 0.153 0.196 0.396 0.442 417 323 500 332 17.83 2.85
150 0.124 0.159 0.384 0.430 473 361 559 366 22.29 4.45
185 0.0991 0.128 0.372 0.418 543 406 637 410 27.49 4.45
240 0.0754 0.098 0.358 0.404 641 469 745 470 35.66 4.45
300 0.0601 0.079 0.341 0.387 735 526 846 524 44.57 4.45
400 0.0470 0.063 0.328 0.375 845 590 938 572 59.43 6.23
500 0.0366 0.051 0.315 0.362 974 755 999 772 74.29 6.23
630 0.0283 0.042 0.304 0.351 1118 846 1146 864 93.60 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEBY 3 x (50 - 400) mm2 3.6/6 kV
AL / XLPE / CTS / PVC / DSTA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.337 159 140 4.91 1.03
70 0.443 0.568 0.310 196 171 6.87 1.03
95 0.320 0.411 0.298 238 204 9.32 1.03
120 0.253 0.325 0.288 274 232 11.77 1.03
150 0.206 0.265 0.279 309 259 14.72 1.03
185 0.164 0.212 0.272 354 293 18.15 1.03
240 0.125 0.162 0.266 415 338 23.55 1.37
300 0.100 0.130 0.259 472 380 29.44 1.37
400 0.0778 0.102 0.255 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEBY 3 x (50 - 400) mm2 6/10 kV
AL / XLPE / CTS / PVC / DSTA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.359 159 140 4.91 1.03
70 0.443 0.568 0.330 196 171 6.87 1.03
95 0.320 0.411 0.316 238 204 9.32 1.03
120 0.253 0.325 0.305 274 232 11.77 1.03
150 0.206 0.265 0.295 309 259 14.72 1.03
185 0.164 0.212 0.287 354 293 18.15 1.03
240 0.125 0.162 0.279 415 338 23.55 1.37
300 0.100 0.130 0.268 472 380 29.44 1.37
400 0.0778 0.102 0.260 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEBY 3 x (50 - 400) mm2 8.7/15 kV
AL / XLPE / CTS / PVC / DSTA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.383 159 140 4.91 1.03
70 0.443 0.568 0.352 196 171 6.87 1.03
95 0.320 0.411 0.337 238 204 9.32 1.03
120 0.253 0.325 0.324 274 232 11.77 1.03
150 0.206 0.265 0.313 309 259 14.72 1.03
185 0.164 0.212 0.304 354 293 18.15 1.03
240 0.125 0.162 0.295 415 338 23.55 1.37
300 0.100 0.130 0.281 472 380 29.44 1.37
400 0.0778 0.102 0.273 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEBY 3 x (50 - 400) mm2 12/20 kV
AL / XLPE / CTS / PVC / DSTA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.403 159 140 4.91 1.03
70 0.443 0.568 0.370 196 171 6.87 1.03
95 0.320 0.411 0.353 238 204 9.32 1.03
120 0.253 0.325 0.340 274 232 11.77 1.03
150 0.206 0.265 0.328 309 259 14.72 1.03
185 0.164 0.212 0.319 354 293 18.15 1.03
240 0.125 0.162 0.308 415 338 23.55 1.37
300 0.100 0.130 0.294 472 380 29.44 1.37
400 0.0778 0.102 0.285 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEBY 3 x (50 - 400) mm2 18/30 kV
AL / XLPE / CTS / PVC / DSTA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.445 159 140 4.91 1.03
70 0.443 0.568 0.409 196 171 6.87 1.03
95 0.320 0.411 0.390 238 204 9.32 1.03
120 0.253 0.325 0.376 274 232 11.77 1.03
150 0.206 0.265 0.362 309 259 14.72 1.03
185 0.164 0.212 0.351 354 293 18.15 1.03
240 0.125 0.162 0.338 415 338 23.55 1.37
300 0.100 0.130 0.322 472 380 29.44 1.37
400 0.0778 0.102 0.310 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEFGbY 3 x (50 - 400) mm2 3.6/6 kV
AL / XLPE / CTS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.337 159 140 4.91 1.03
70 0.443 0.568 0.310 196 171 6.87 1.03
95 0.320 0.411 0.298 238 204 9.32 1.03
120 0.253 0.325 0.288 274 232 11.77 1.03
150 0.206 0.265 0.279 309 259 14.72 1.03
185 0.164 0.212 0.272 354 293 18.15 1.03
240 0.125 0.162 0.266 415 338 23.55 1.37
300 0.100 0.130 0.259 472 380 29.44 1.37
400 0.0778 0.102 0.255 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEFGbY 3 x (50 - 400) mm2 6/10 kV
AL / XLPE / CTS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.359 159 140 4.91 1.03
70 0.443 0.568 0.330 196 171 6.87 1.03
95 0.320 0.411 0.316 238 204 9.32 1.03
120 0.253 0.325 0.305 274 232 11.77 1.03
150 0.206 0.265 0.295 309 259 14.72 1.03
185 0.164 0.212 0.287 354 293 18.15 1.03
240 0.125 0.162 0.279 415 338 23.55 1.37
300 0.100 0.130 0.268 472 380 29.44 1.37
400 0.0778 0.102 0.260 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEFGbY 3 x (50 - 400) mm2 8.7/15 kV
AL / XLPE / CTS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.383 159 140 4.91 1.03
70 0.443 0.568 0.352 196 171 6.87 1.03
95 0.320 0.411 0.337 238 204 9.32 1.03
120 0.253 0.325 0.324 274 232 11.77 1.03
150 0.206 0.265 0.313 309 259 14.72 1.03
185 0.164 0.212 0.304 354 293 18.15 1.03
240 0.125 0.162 0.295 415 338 23.55 1.37
300 0.100 0.130 0.281 472 380 29.44 1.37
400 0.0778 0.102 0.273 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEFGbY 3 x (50 - 400) mm2 12/20 kV
AL / XLPE / CTS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.403 159 140 4.91 1.03
70 0.443 0.568 0.370 196 171 6.87 1.03
95 0.320 0.411 0.353 238 204 9.32 1.03
120 0.253 0.325 0.340 274 232 11.77 1.03
150 0.206 0.265 0.328 309 259 14.72 1.03
185 0.164 0.212 0.319 354 293 18.15 1.03
240 0.125 0.162 0.308 415 338 23.55 1.37
300 0.100 0.130 0.294 472 380 29.44 1.37
400 0.0778 0.102 0.285 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEFGbY 3 x (50 - 400) mm2 18/30 kV
AL / XLPE / CTS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen,
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.445 159 140 4.91 1.03
70 0.443 0.568 0.409 196 171 6.87 1.03
95 0.320 0.411 0.390 238 204 9.32 1.03
120 0.253 0.325 0.376 274 232 11.77 1.03
150 0.206 0.265 0.362 309 259 14.72 1.03
185 0.164 0.212 0.351 354 293 18.15 1.03
240 0.125 0.162 0.338 415 338 23.55 1.37
300 0.100 0.130 0.322 472 380 29.44 1.37
400 0.0778 0.102 0.310 545 432 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 3.6/6 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.337 158 140 4.91 1.03
70 0.443 0.568 0.310 196 171 6.87 1.03
95 0.320 0.411 0.298 236 203 9.32 1.03
120 0.253 0.325 0.288 273 232 11.77 1.03
150 0.206 0.265 0.279 309 260 14.72 1.03
185 0.164 0.212 0.272 355 294 18.15 1.03
240 0.125 0.162 0.266 415 340 23.55 1.37
300 0.100 0.130 0.259 475 384 29.44 1.37
400 0.0778 0.102 0.255 552 438 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 6/10 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.359 158 140 4.91 1.03
70 0.443 0.568 0.330 196 171 6.87 1.03
95 0.320 0.411 0.316 236 203 9.32 1.03
120 0.253 0.325 0.305 273 232 11.77 1.03
150 0.206 0.265 0.295 309 260 14.72 1.03
185 0.164 0.212 0.287 355 294 18.15 1.03
240 0.125 0.162 0.279 415 340 23.55 1.37
300 0.100 0.130 0.268 475 384 29.44 1.37
400 0.0778 0.102 0.260 552 438 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 8.7/15 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.383 158 140 4.91 1.03
70 0.443 0.568 0.352 196 171 6.87 1.03
95 0.320 0.411 0.337 236 203 9.32 1.03
120 0.253 0.325 0.324 273 232 11.77 1.03
150 0.206 0.265 0.313 309 260 14.72 1.03
185 0.164 0.212 0.304 355 294 18.15 1.03
240 0.125 0.162 0.295 415 340 23.55 1.37
300 0.100 0.130 0.281 475 384 29.44 1.37
400 0.0778 0.102 0.273 552 438 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 12/20 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.403 158 140 4.91 1.03
70 0.443 0.568 0.370 196 171 6.87 1.03
95 0.320 0.411 0.353 236 203 9.32 1.03
120 0.253 0.325 0.340 273 232 11.77 1.03
150 0.206 0.265 0.328 309 260 14.72 1.03
185 0.164 0.212 0.319 355 294 18.15 1.03
240 0.125 0.162 0.308 415 340 23.55 1.37
300 0.100 0.130 0.294 475 384 29.44 1.37
400 0.0778 0.102 0.285 552 438 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 18/30 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.445 158 140 4.91 1.03
70 0.443 0.568 0.409 196 171 6.87 1.03
95 0.320 0.411 0.390 236 203 9.32 1.03
120 0.253 0.325 0.376 273 232 11.77 1.03
150 0.206 0.265 0.362 309 260 14.72 1.03
185 0.164 0.212 0.351 355 294 18.15 1.03
240 0.125 0.162 0.338 415 340 23.55 1.37
300 0.100 0.130 0.322 475 384 29.44 1.37
400 0.0778 0.102 0.310 552 438 39.25 1.37
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 3.6/6 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.373 158 140 4.91 2.85
70 0.443 0.568 0.343 196 171 6.87 2.85
95 0.320 0.411 0.328 236 203 9.32 2.85
120 0.253 0.325 0.317 273 232 11.77 2.85
150 0.206 0.265 0.306 309 260 14.72 2.85
185 0.164 0.212 0.297 355 294 18.15 4.45
240 0.125 0.162 0.289 415 340 23.55 4.45
300 0.100 0.130 0.280 475 384 29.44 4.45
400 0.0778 0.102 0.274 552 438 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 6/10 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.392 158 140 4.91 2.85
70 0.443 0.568 0.360 196 171 6.87 2.85
95 0.320 0.411 0.344 236 203 9.32 2.85
120 0.253 0.325 0.331 273 232 11.77 2.85
150 0.206 0.265 0.320 309 260 14.72 2.85
185 0.164 0.212 0.310 355 294 18.15 4.45
240 0.125 0.162 0.300 415 340 23.55 4.45
300 0.100 0.130 0.289 475 384 29.44 4.45
400 0.0778 0.102 0.278 552 438 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 8.7/15 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.413 158 140 4.91 2.85
70 0.443 0.568 0.379 196 171 6.87 2.85
95 0.320 0.411 0.362 236 203 9.32 2.85
120 0.253 0.325 0.348 273 232 11.77 2.85
150 0.206 0.265 0.336 309 260 14.72 2.85
185 0.164 0.212 0.326 355 294 18.15 4.45
240 0.125 0.162 0.315 415 340 23.55 4.45
300 0.100 0.130 0.301 475 384 29.44 4.45
400 0.0778 0.102 0.291 552 438 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEY 3 x (50 - 400) mm2 12/20 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.429 159 140 4.91 2.85
70 0.443 0.568 0.395 196 171 6.87 2.85
95 0.320 0.411 0.377 238 204 9.32 2.85
120 0.253 0.325 0.363 274 232 11.77 2.85
150 0.206 0.265 0.350 309 259 14.72 2.85
185 0.164 0.212 0.339 354 293 18.15 4.45
240 0.125 0.162 0.327 415 338 23.55 4.45
300 0.100 0.130 0.312 472 380 29.44 4.45
400 0.0778 0.102 0.301 545 432 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEYFGbY 3 x (50 - 400) mm2 3.6/6 kV
AL / XLPE / CWS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.373 159 140 4.91 2.85
70 0.443 0.568 0.343 196 171 6.87 2.85
95 0.320 0.411 0.328 238 204 9.32 2.85
120 0.253 0.325 0.317 274 232 11.77 2.85
150 0.206 0.265 0.306 309 259 14.72 2.85
185 0.164 0.212 0.297 354 293 18.15 4.45
240 0.125 0.162 0.289 415 338 23.55 4.45
300 0.100 0.130 0.280 472 380 29.44 4.45
400 0.0778 0.102 0.274 545 432 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEYFGbY 3 x (50 - 400) mm2 6/10 kV
AL / XLPE / CWS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.392 159 140 4.91 2.85
70 0.443 0.568 0.360 196 171 6.87 2.85
95 0.320 0.411 0.344 238 204 9.32 2.85
120 0.253 0.325 0.331 274 232 11.77 2.85
150 0.206 0.265 0.320 309 259 14.72 2.85
185 0.164 0.212 0.310 354 293 18.15 4.45
240 0.125 0.162 0.300 415 338 23.55 4.45
300 0.100 0.130 0.289 472 380 29.44 4.45
400 0.0778 0.102 0.278 545 432 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEYFGbY 3 x (50 - 400) mm2 8.7/15 kV
AL / XLPE / CWS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.413 159 140 4.91 2.85
70 0.443 0.568 0.379 196 171 6.87 2.85
95 0.320 0.411 0.362 238 204 9.32 2.85
120 0.253 0.325 0.348 274 232 11.77 2.85
150 0.206 0.265 0.336 309 259 14.72 2.85
185 0.164 0.212 0.326 354 293 18.15 4.45
240 0.125 0.162 0.315 415 338 23.55 4.45
300 0.100 0.130 0.301 472 380 29.44 4.45
400 0.0778 0.102 0.291 545 432 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSEYFGbY 3 x (50 - 400) mm2 12/20 kV
AL / XLPE / CWS / PVC / GSFA / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen,
Application:
For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling stress-
es may occur during installation or operation.
Electrical Data
Conductor Inductance Current - Carrying
Short Circuit Current
Capacity at
Nom DC AC at 1 second
at 30 C *
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max.
(mH/km)
mm (/km) (/km) (A) (A) (kA) (kA)
50 0.641 0.822 0.429 159 140 4.91 2.85
70 0.443 0.568 0.395 196 171 6.87 2.85
95 0.320 0.411 0.377 238 204 9.32 2.85
120 0.253 0.325 0.363 274 232 11.77 2.85
150 0.206 0.265 0.350 309 259 14.72 2.85
185 0.164 0.212 0.339 354 293 18.15 4.45
240 0.125 0.162 0.327 415 338 23.55 4.45
300 0.100 0.130 0.312 472 380 29.44 4.45
400 0.0778 0.102 0.301 545 432 39.25 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 3.6/6 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Aluminium Conductor
Special Features on Request:
Oil Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen UV Resistance
XLPE Insulation Flame Retardant Cat. A, B, C Area approx. approx.
Insulation Screen Flame Retardant Non Category
Copper Tape Screen mm mm kg/km
Heat Resistance
Non-hygroscopic Tape
Anti Termite 50 19.0 485
RED PVC Outer sheath Anti Rodent 70 21.5 590
Low Smoke Zero Halagen 95 23.0 705
120 25.0 820
Note:
150 26.0 935
Conductor Shape
185 28.0 1,085
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 30.0 1,280
300 34.0 1,585
Standard Packing
400 37.0 1,940
Application: 50 - 300 sqmm supplied in wooden drum @ 1000
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.374 0.420 184 152 222 157 4.91 1.14
70 0.443 0.568 0.315 0.391 230 186 278 192 6.87 1.14
95 0.320 0.411 0.331 0.377 280 221 338 229 9.32 1.14
120 0.253 0.325 0.320 0.366 324 252 391 260 11.77 1.14
150 0.206 0.265 0.310 0.356 368 281 440 288 14.72 1.14
185 0.164 0.211 0.302 0.348 424 317 504 324 18.15 1.14
240 0.125 0.161 0.294 0.341 502 367 593 373 23.55 1.14
300 0.100 0.130 0.286 0.332 577 414 677 419 29.44 1.14
400 0.0778 0.102 0.280 0.327 673 470 769 451 39.25 1.14
500 0.0605 0.080 0.274 0.321 774 603 796 618 49.06 1.14
630 0.0469 0.080 0.267 0.313 914 690 939 706 61.82 1.14
800 0.0367 0.050 0.262 0.308 1019 795 994 764 78.50 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 6/10 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Aluminium Conductor
Special Features on Request:
Oil Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen UV Resistance
XLPE Insulation Flame Retardant Cat. A, B, C Area approx. approx.
Insulation Screen Flame Retardant Non Category
Copper Tape Screen mm mm kg/km
Heat Resistance
Non-hygroscopic Tape
Anti Termite 50 22.0 565
RED PVC Outer sheath Anti Rodent 70 23.5 675
Low Smoke Zero Halagen 95 25.5 790
120 27.0 915
Note:
150 28.5 1,035
Conductor Shape
185 30.0 1,185
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 32.0 1,380
300 35.0 1,665
Standard Packing
400 38.0 1,995
Application: 50 - 300 sqmm supplied in wooden drum @ 1000
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.394 0.440 184 152 222 157 4.91 1.14
70 0.443 0.568 0.363 0.409 230 186 278 192 6.87 1.14
95 0.320 0.411 0.348 0.394 280 221 338 229 9.32 1.14
120 0.253 0.325 0.336 0.382 324 252 391 260 11.77 1.14
150 0.206 0.265 0.324 0.371 368 281 440 288 14.72 1.14
185 0.164 0.211 0.316 0.362 424 317 504 324 18.15 1.14
240 0.125 0.161 0.306 0.352 502 367 593 373 23.55 1.14
300 0.100 0.130 0.294 0.340 577 414 677 419 29.44 1.14
400 0.0778 0.102 0.285 0.332 673 470 769 451 39.25 1.14
500 0.0605 0.080 0.277 0.323 774 603 796 618 49.06 1.14
630 0.0469 0.080 0.269 0.315 914 690 939 706 61.82 1.14
800 0.0367 0.050 0.263 0.310 1019 795 994 764 78.50 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 8.7/15 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Special Features on Request:
Aluminium Conductor
Oil Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen UV Resistance
XLPE Insulation Flame Retardant Cat. A, B, C Area approx. approx.
Insulation Screen
Flame Retardant Non Category
Copper Tape Screen mm mm kg/km
Non-hygroscopic Tape
Heat Resistance
Anti Termite 50 24.0 665
RED PVC Outer sheath
Anti Rodent 70 26.0 785
Low Smoke Zero Halagen 95 28.0 905
120 29.5 1,035
Note:
150 31.0 1,165
Conductor Shape
185 32.5 1,320
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 35.0 1,520
300 37.5 1,820
Standard Packing
400 40.5 2,165
Application: 50 - 300 sqmm supplied in wooden drum @ 1000
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.416 0.462 184 152 222 157 4.91 1.14
70 0.443 0.568 0.383 0.429 230 186 278 192 6.87 1.14
95 0.320 0.411 0.366 0.412 280 221 338 229 9.32 1.14
120 0.253 0.325 0.350 0.397 324 252 391 260 11.77 1.14
150 0.206 0.265 0.341 0.388 368 281 440 288 14.72 1.14
185 0.164 0.211 0.332 0.378 424 317 504 324 18.15 1.14
240 0.125 0.161 0.321 0.367 502 367 593 373 23.55 1.14
300 0.100 0.130 0.308 0.354 577 414 677 419 29.44 1.14
400 0.0778 0.102 0.298 0.344 673 470 769 451 39.25 1.14
500 0.0605 0.080 0.288 0.334 774 603 796 618 49.06 1.14
630 0.0469 0.080 0.279 0.325 914 690 939 706 61.82 1.14
800 0.0367 0.050 0.273 0.320 1019 795 994 764 78.50 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 12/20 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Aluminium Conductor
Special Features on Request:
Oil Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen UV Resistance
XLPE Insulation Flame Retardant Cat. A, B, C Area approx. approx.
Insulation Screen Flame Retardant Non Category
Copper Tape Screen mm mm kg/km
Heat Resistance
Non-hygroscopic Tape
Anti Termite 50 26.5 765
RED PVC Outer sheath Anti Rodent 70 28.5 890
Low Smoke Zero Halagen 95 30.0 1,020
120 32.0 1,155
Note:
150 33.0 1,285
Conductor Shape
185 34.5 1,445
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 37.0 1,655
300 40.0 1,965
Standard Packing
400 43.0 2,320
Application: 50 - 300 sqmm supplied in wooden drum @ 1000
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.433 0.480 184 152 222 157 4.91 1.14
70 0.443 0.568 0.400 0.446 230 186 278 192 6.87 1.14
95 0.320 0.411 0.382 0.428 280 221 338 229 9.32 1.14
120 0.253 0.325 0.368 0.414 324 252 391 260 11.77 1.14
150 0.206 0.265 0.355 0.402 368 281 440 288 14.72 1.14
185 0.164 0.211 0.345 0.392 424 317 504 324 18.15 1.14
240 0.125 0.161 0.334 0.380 502 367 593 373 23.55 1.14
300 0.100 0.130 0.319 0.365 577 414 677 419 29.44 1.14
400 0.0778 0.102 0.309 0.355 673 470 769 451 39.25 1.14
500 0.0605 0.080 0.298 0.344 774 603 796 618 49.06 1.14
630 0.0469 0.080 0.288 0.334 914 690 939 706 61.82 1.14
800 0.0367 0.050 0.282 0.328 1019 795 994 764 78.50 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 18/30 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Construction Data
Aluminium Conductor
Special Features on Request:
Oil Resistance Nom Overall Cable
Cross Section Diameter Weight
Conductor Screen UV Resistance
XLPE Insulation Flame Retardant Cat. A, B, C Area approx. approx.
Insulation Screen Flame Retardant Non Category
Copper Tape Screen mm mm kg/km
Heat Resistance
Non-hygroscopic Tape
Anti Termite 50 32.0 1,050
RED PVC Outer sheath Anti Rodent 70 34.0 1,195
Low Smoke Zero Halagen 95 36.0 1,335
120 37.5 1,485
Note:
150 39.0 1,630
Conductor Shape
185 40.5 1,805
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 42.5 2,035
300 45.5 2,370
Standard Packing
400 48.5 2,750
Application: 50 - 300 sqmm supplied in wooden drum @ 1000
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.472 0.518 184 152 222 157 4.91 1.14
70 0.443 0.568 0.436 0.482 230 186 278 192 6.87 1.14
95 0.320 0.411 0.416 0.462 280 221 338 229 9.32 1.14
120 0.253 0.325 0.401 0.447 324 252 391 260 11.77 1.14
150 0.206 0.265 0.387 0.433 368 281 440 288 14.72 1.14
185 0.164 0.211 0.375 0.422 424 317 504 324 18.15 1.14
240 0.125 0.161 0.362 0.408 502 367 593 373 23.55 1.14
300 0.100 0.130 0.345 0.392 577 414 677 419 29.44 1.14
400 0.0778 0.102 0.334 0.380 673 470 769 451 39.25 1.14
500 0.0605 0.080 0.321 0.367 774 603 796 618 49.06 1.14
630 0.0469 0.080 0.309 0.356 914 690 939 706 61.82 1.14
800 0.0367 0.050 0.302 0.348 1019 795 994 764 78.50 1.14
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 3.6/6 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Aluminium Conductor Special Features on Request:
Oil Resistance Nom Overall Cable
Conductor Screen Cross Section Diameter Weight
XLPE Insulation
UV Resistance
Insulation Screen Flame Retardant Cat. A, B, C Area approx. approx.
Semi-Conductive WBT
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape mm mm kg/km
Non-Conductive WBT Heat Resistance
Anti Termite 50 25.5 775
RED PVC Outer sheath
Anti Rodent 70 27.5 885
Low Smoke Zero Halagen 95 29.0 995
120 30.5 1,115
Note:
150 32.0 1,315
Conductor Shape
185 33.5 1,455
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 35.5 1,650
300 39.0 1,945
Standard Packing
50 - 300 sqmm supplied in wooden drum @ 1000
400 42.0 2,385
Application: meters 500 46.0 2,765
For power station and switchgear as well as sta- 400 - 800 sqmm supplied in wooden drum on
630 50.0 3,275
available length
tion because of small bending radius in confined 800 53.0 3,875
Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.427 0.473 184 152 222 157 4.91 2.85
70 0.443 0.568 0.373 0.439 230 186 278 192 6.87 2.85
95 0.320 0.411 0.374 0.421 280 221 338 229 9.32 2.85
120 0.253 0.325 0.360 0.407 324 252 391 260 11.77 2.85
150 0.206 0.265 0.348 0.394 368 281 440 288 14.72 4.45
185 0.164 0.211 0.337 0.383 424 317 504 324 18.15 4.45
240 0.125 0.161 0.327 0.373 502 367 593 373 23.55 4.45
300 0.100 0.130 0.314 0.360 577 414 677 419 29.44 4.45
400 0.0778 0.102 0.305 0.351 673 470 769 451 39.25 6.23
500 0.0605 0.080 0.295 0.342 774 603 796 618 49.06 6.23
630 0.0469 0.080 0.285 0.331 914 690 939 706 61.82 6.23
800 0.0367 0.050 0.278 0.325 1019 795 994 764 78.50 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 6/10 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Aluminium Conductor Special Features on Request:
Oil Resistance Nom Overall Cable
Conductor Screen Cross Section Diameter Weight
XLPE Insulation
UV Resistance
Insulation Screen Flame Retardant Cat. A, B, C Area approx. approx.
Semi-Conductive WBT
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape mm mm kg/km
Non-Conductive WBT Heat Resistance
Anti Termite 50 27.5 855
RED PVC Outer sheath
Anti Rodent 70 29.5 965
Low Smoke Zero Halagen 95 31.0 1,080
120 32.5 1,205
Note:
150 34.0 1,405
Conductor Shape
185 35.0 1,555
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 37.0 1,745
300 40.0 2,020
Standard Packing
50 - 300 sqmm supplied in wooden drum @ 1000
400 43.0 2,435
Application: meters 500 46.0 2,795
For power station and switchgear as well as sta- 400 - 800 sqmm supplied in wooden drum on
630 50.0 3,305
available length
tion because of small bending radius in confined 800 54.0 3,905
Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.441 0.488 184 152 222 157 4.91 2.85
70 0.443 0.568 0.406 0.452 230 186 278 192 6.87 2.85
95 0.320 0.411 0.387 0.433 280 221 338 229 9.32 2.85
120 0.253 0.325 0.373 0.419 324 252 391 260 11.77 2.85
150 0.206 0.265 0.359 0.405 368 281 440 288 14.72 4.45
185 0.164 0.211 0.348 0.394 424 317 504 324 18.15 4.45
240 0.125 0.161 0.336 0.382 502 367 593 373 23.55 4.45
300 0.100 0.130 0.321 0.368 577 414 677 419 29.44 4.45
400 0.0778 0.102 0.309 0.355 673 470 769 451 39.25 6.23
500 0.0605 0.080 0.297 0.343 774 603 796 618 49.06 6.23
630 0.0469 0.080 0.287 0.333 914 690 939 706 61.82 6.23
800 0.0367 0.050 0.280 0.327 1019 795 994 764 78.50 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 8.7/15 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Aluminium Conductor Special Features on Request:
Oil Resistance Nom Overall Cable
Conductor Screen Cross Section Diameter Weight
XLPE Insulation
UV Resistance
Insulation Screen Flame Retardant Cat. A, B, C Area approx. approx.
Semi-Conductive WBT
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape mm mm kg/km
Non-Conductive WBT Heat Resistance
Anti Termite 50 30.0 955
RED PVC Outer sheath
Anti Rodent 70 31.5 1,075
Low Smoke Zero Halagen 95 33.0 1,195
120 35.0 1,320
Note:
150 36.0 1,530
Conductor Shape
185 37.5 1,685
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 39.5 1,875
300 42.5 2,165
Standard Packing
50 - 300 sqmm supplied in wooden drum @ 1000
400 45.0 2,590
Application: meters 500 48.5 2,960
For power station and switchgear as well as sta- 400 - 800 sqmm supplied in wooden drum on
630 52.5 3,485
available length
tion because of small bending radius in confined 800 56.0 4,095
Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.458 0.504 184 152 222 157 4.91 2.85
70 0.443 0.568 0.421 0.467 230 186 278 192 6.87 2.85
95 0.320 0.411 0.402 0.448 280 221 338 229 9.32 2.85
120 0.253 0.325 0.387 0.433 324 252 391 260 11.77 2.85
150 0.206 0.265 0.372 0.418 368 281 440 288 14.72 4.45
185 0.164 0.211 0.361 0.407 424 317 504 324 18.15 4.45
240 0.125 0.161 0.348 0.394 502 367 593 373 23.55 4.45
300 0.100 0.130 0.331 0.378 577 414 677 419 29.44 4.45
400 0.0778 0.102 0.319 0.366 673 470 769 451 39.25 6.23
500 0.0605 0.080 0.307 0.353 774 603 796 618 49.06 6.23
630 0.0469 0.080 0.296 0.342 914 690 939 706 61.82 6.23
800 0.0367 0.050 0.288 0.335 1019 795 994 764 78.50 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XSY 1 x (50 - 800) mm2 12/20 kV
AL / XLPE / CWS / PVC
(Aluminium Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Construction Data
Aluminium Conductor Special Features on Request:
Oil Resistance Nom Overall Cable
Conductor Screen Cross Section Diameter Weight
XLPE Insulation
UV Resistance
Insulation Screen Flame Retardant Cat. A, B, C Area approx. approx.
Semi-Conductive WBT
Copper Wire Screen Flame Retardant Non Category
Binder Copper Tape mm mm kg/km
Non-Conductive WBT Heat Resistance
Anti Termite 50 32.0 1,055
RED PVC Outer sheath
Anti Rodent 70 34.0 1,175
Low Smoke Zero Halagen 95 35.5 1,305
120 37.0 1,435
Note:
150 38.0 1,645
Conductor Shape
185 40.0 1,805
50 - 800 sqmm supplied in compacted circular
stranded (cm) conductor shape 240 41.5 2,010
300 44.5 2,305
Standard Packing
50 - 300 sqmm supplied in wooden drum @ 1000
400 47.0 2,735
Application: meters 500 50.5 3,115
For power station and switchgear as well as sta- 400 - 800 sqmm supplied in wooden drum on
630 55.0 3,685
available length
tion because of small bending radius in confined 800 58.0 4,305
Length Tolerance per drum 2%
spaces indoors. As underground because of light
weight where installation conditions are difficult.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short Circuit Current
at 1 second
Nom DC AC Trefoil formation Flat formation
Cross Resistance Resistance
Section at 20 C at 90 C in air in ground in air in ground Conductor Screen
Area Max. Max. Max. Max. Max. Max. Max. Max.
mm (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.471 0.518 184 152 222 157 4.91 2.85
70 0.443 0.568 0.434 0.480 230 186 278 192 6.87 2.85
95 0.320 0.411 0.414 0.460 280 221 338 229 9.32 2.85
120 0.253 0.325 0.398 0.445 324 252 391 260 11.77 2.85
150 0.206 0.265 0.384 0.430 368 281 440 288 14.72 4.45
185 0.164 0.211 0.372 0.418 424 317 504 324 18.15 4.45
240 0.125 0.161 0.358 0.404 502 367 593 373 23.55 4.45
300 0.100 0.130 0.342 0.389 577 414 677 419 29.44 4.45
400 0.0778 0.102 0.329 0.376 673 470 769 451 39.25 6.23
500 0.0605 0.080 0.315 0.362 774 603 796 618 49.06 6.23
630 0.0469 0.080 0.304 0.351 914 690 939 706 61.82 6.23
800 0.0367 0.050 0.297 0.343 1019 795 994 764 78.50 6.23
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information