CT Spec Revision 2015
CT Spec Revision 2015
CT Spec Revision 2015
TI/SPC/PSI/CT/0515(05/2015) Page 1 of 27
GOVERNMENT OF INDIA
MINISTRY OF RAILWAYS
TECHNICAL SPECIFICATION
FOR
CURRENT TRANSFORMERS
for
ISSUED BY
SPECI FICATION : T E C H N I C A L S P E C I F I C A T I O N F O R
CURRENT TRANSFORMER FOR RAILWAY AC
TRACTION SUBSTATIONS.
INDEX
1.0 Scope 4
9.0 Painting 10
10.0 Testing 10
12.0 Spares 16
15.0 Warranty 16
APPENDIXES
APPENDIX- A General Arrangement at the Traction 18
Transformer at Traction Sub-station
ANNEXURES
ANNEXURE- A Drawing & Details of Terminal Connectors 23
area
1.0 SCOPE
1.1 This specification applies to outdoor electrically exposed type Current
Transformer for a nominal system voltage of 220 kV or 132 kV or
110 kV or 66 kV for use in unattended Railway Traction Sub-station
in any part of India together with associated. Electrical/Electronic
measuring/indicating instrument and protective devices. It
supersedes Specification No. ETI/PSI/117(07/88),
ETI/PSI/102(08/87), ETI/PSI/40(08/83), ETI/PSI/22(09/82) and
ETI/PSI/55(09/79).
1 . 2 The Current Transformer shall be complete with all parts, fittings and
accessories including mounting frame work of steel, necessary for its
efficient operation. All such parts, fittings and accessories shall be
deemed to be within the scope of this Specification, whether
specifically mentioned herein or not. The Current Transformer shall
be of proven design.
in in Instrument Transformers.
16 RDSOs Spec No. Steel and stainless steel fasteners.
ETI/OHE/18(04/84)
with correction Slip
No.6 (09/87)
17 RDSOs Spec No. Specification for hollow porcelain insulator
ETI/PSI/70(11/84) and bushings.
5.1(b) For ABT Metering: The rating and other particulars of the
Current Transformer shall be as follows:-
i)Type: Single phase, oil filled natural
air cooled, One core
for ABT Metering.
ii) No. of windings: Primary Two
Secondary - One
iii) System voltage:
9.0 PAINTING
9.1 All the steel surfaces which are in contact with insulating oil
shall be painted with heat resistant oil insoluble insulating warmish. All
steel surfaces exposed to weather shall be given on primer coat of zinc
chromate and two coats of gray paint to shade No. 631 of IS: 5. One coat
of additional paint shall be given at site by the manufacturer.
9.2 Fasteners.
All fasteners of 12 mm diameter and less exposed to atmosphere
shall be stainless steel and those above 12 mm diameter shall be preferably
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 11 of 27
APPENDIX A
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 18 of 27
APPENDIX B
SECTOR
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 20 of 27
APPENDIX-C
SCHEDULE OF GUARANTEED PERFORMANCE, TECHNICAL AND
OTHER PARTICULARS.
S. Description Unit of
No. measurement
1. Name of the manufacturer
2. Country of origin
3. Standard governing specification
4. Manufacturers type designation
5. (a) Nominal system voltage kV
(b) Highest system voltage kV
6. (a) Rated primary current Amp
(b) Rated secondary current Amp
(c) Rated transformation ratio
7 Rated burden VA
8 Accuracy class
9 Rated accuracy limit factor
10 Current error at rated primary current Percent
11 Phase displacement at rated primary Minutes
current
12 Complete error at rated accuracy limit percent
primary current
13 Rated short-time current and duration
(a) Thermal (Ith) kA (RMS)for one
sec.
kA (peak)
(b) Dynamic (Idyn)
14 Temperaturerise of the windings
(by resistance method) over an ambient
temperature of 45 0C 0
C
(a) At rated current
(b) At 100% overload for 5 minutes 0
C
15. Partial discharge level pC
16. Particulars windings
a) Primary winding
i) Type
ii) No. of turns
iii) Current density at rated Amp/mm2
current
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 21 of 27
a. Protected mm
b. Total mm
vii) Weight of porcelain housing Kgs.
/bushing
19 Overall dimensions:
i) Length mm
ii) Width mm
iii) Height mm
20 Weights:
(i) Total weight of copper used
a) Primary winding Kgs.
b) Secondary winding Kgs.
(ii) Weight of core Kgs.
(iii)(a) Quantity of insulating oil Liter
b) Weight of insulating oil Kgs.
iv) Total weight Kgs.
21 Particulars of terminal connector:
(i) Name of manufacturer
(ii) Rated current Amp.
(iii) Temperature rise above an
ambient temperature of 45 0C
a) At rated current
b) At 150 percent of rated current for
15 minutes.
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 23 of 27
ANNEXURE- A
Details of Terminal Connector:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 24 of 27
ANNEXURE- B
Format of Title Drawing:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 25 of 27
ANNEXURE- C
1.0 SCOPE
This part of specification cover design, manufacture, testing,
inspection, packing and supply of 145 kV class outdoor,
Current Transformer with CT ratio of 1200-800-400/5A to the
Specification given below to be used in Mumbai area on 110
kV side at Traction Sub-station with 30 MVA Transformers and
required to be operated in parallel with adjacent Traction Sub-
stations.
2.0 RATING AND OTHER PARTICULARS:
i) Type Single phase, oil filled natural
air cooled outdoor.
ii) No. of cores 4
iii) System voltage
a) Nominal system 132
voltage , kV
b) Highest system
145
voltage, kV
iv) Rated
primary/secondary
currents
a) Primary current,
Amp 1200
b) Secondary 5
current, Amp
v) CT ratio 1200-800-400/5A
vi) Rated frequency 50 Hz,+/-3%
vii) Class of insulation A
viii) a) Short time 40
current rating
(thermal) for 3
second, kA
b) Short circuit 40
withstand current
(3 sec.), kA
c) Short time
current rating 100
(dynamic), kA
(peak)
ix) Rated insulation level
a) One minute 50 275
Hz withstand
voltage/induced
over-voltage, kV
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 26 of 27
(rms)
b) Impulse 650
withstand
voltage, positive
and negative
polarity (1.2/50
microseconds
wave), kV (peak)
x) Minimum creepage 4495
distance of insulator
(31 mm/kV), mm
xi) Temperature rise 50 0C over an ambient temp.
Maximum temperature 50 0C
rise of windings
immersed in oil
xii) Rated Overload 150% of full load for 15
minutes
xiii) Rated Burden & Class Core-1 Core- Core-2&4
of Accuracy of different 3
cores
Protection R met Protection
Burden in VA 40 40 -
Accuracy Class 5P20 0.2 PS
Instrument Security - <5 -
factor
Knee point voltage - - >750V
Iex (max) at Vk/2 - - <100 mA
Rct (max) - - <1.0 Ohm
at max.
tap.
2.1
a) multi ratio specified shall be obtained by taps on
secondary side.
b) The values specified above for metering & protection
core shall be met for the lowest tap. (except) Rct and
knee point voltage for PS core which is at the highest
tap).
c) P1 and P2 markings to be permanently riveted.
d) CT shall be of dead tank design.
e) Power factor terminal (test tap) shall be provided inside the
secondary terminal box.
f) The disposition of various CT cores and detailed drawings
along with SOGP shall be furnished for RDSOs approval
before manufacture is taken up.
3.0 Construction:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015) Page 27 of 27