Balboa M-7 Trouble Shooting-1
Balboa M-7 Trouble Shooting-1
Balboa M-7 Trouble Shooting-1
Table of Contents
Balboa Control Service Checklist
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
System Components Required . . . . . . . . . . . . . . . . . . .4
Safety Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
System Description
Topside Control Panel . . . . . . . . . . . . . . . . . . . . . . . . .5
Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
M-7 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring Checks
Wiring Check Precautions . . . . . . . . . . . . . . . . . . . . . .6
System Box Wire Gauge Check . . . . . . . . . . . . . . . . . . .6
G.F.C.I. Wiring Check . . . . . . . . . . . . . . . . . . . . . . . . .6
G.F.C.I. Line-in Wiring Check . . . . . . . . . . . . . . . . . . . .7
G.F.C.I. Line-out Wiring Check . . . . . . . . . . . . . . . . . . .7
240 V Dedicated . . . . . . . . . . . . . . . . . . . . . . . . .7
120/240 V Convertible . . . . . . . . . . . . . . . . . . . . .7
Voltage Checks
Breaker Box Voltage Check . . . . . . . . . . . . . . . . . . . . .8
G.F.C.I. Line-in Voltage Check
240 V Dedicated . . . . . . . . . . . . . . . . . . . . . . . . .8
120/240 V Convertible . . . . . . . . . . . . . . . . . . . . .8
G.F.C.I. Load Out Voltage Check . . . . . . . . . . . . . . . . . .9
240 V Dedicated . . . . . . . . . . . . . . . . . . . . . . . . .9
120/240 V Convertible . . . . . . . . . . . . . . . . . . . . .9
System Box Check (at TB1) . . . . . . . . . . . . . . . . . . . . .9
240 V Dedicated . . . . . . . . . . . . . . . . . . . . . . . . .9
120/240 V Convertible . . . . . . . . . . . . . . . . . . . . .9
Peak Load Check . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Peak Load Check for 240 V Dedicated . . . . . . . .9
Peak Load Check for 120/240 V Convertible . . . .9
Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . .10
Panel Messages
HH, OHH, HTR TEMP LIMIT . . . . . . . . . . . . . . . . . . .19
OH, OHS, SPA TEMP LIMIT . . . . . . . . . . . . . . . . . . . .19
SA, SNA, SNH, SENSOR A SERVICE RQD . . . . . . . . . . .19
SB, SNB, SNT, SENSOR B SERVICE RQD . . . . . . . . . . .19
SN, SNS, SENSOR SYNC . . . . . . . . . . . . . . . . . . . . . . .19
800.645.3201
G.F.C.I. Troubleshooting
Spa Behavior
General Information . . . . . . . . . . . . . . . . . . . . . . . . .27
Heater Startup Information . . . . . . . . . . . . . . . . . . . .27
www.balboa-instruments.com
Fuses (30 and 20A time delay plus 20, 10 and 3A)
System Transformers (120 V and 240 V
plus a 120 V Duplex)
System Sensors
System Panel(s)
System Circuit Board
Tools Required
Ammeter (50A)
Digital Multi-meter
Balboa Logic Jumper on a Stick
Balboa Six-in-one Screwdriver, Includes:
Two Phillips Head and Two Flathead Screwdrivers Along
with a 1/4" and 5/16" Nut Driver
5/ " Socket
16
1/ " Open End Wrench
4
Small Wire Cutters
Pliers & Needlenose
Pliers
Quick CheckTM Test
Kit
Precision Thermometer Digital Fever Type
Padlock (to lock electrical
disconnect during service)
Plumbers Sealant
Quick CheckTM Test Kit
Important
Due to the danger of severe electrical shock, locate all
power disconnects before servicing a spa. Precautions must
be taken whenever working with breaker boxes, G.F.C.I.s, or
service disconnects.
Always refer to the wiring diagram which is included with
each system on the inside of the system box cover. Use this
diagram for voltage measurement points, and for proper
reconnection of wires.
Important
Be sure to bring the correct circuit board, topside control
panel, components, and tools.
Safety Tips
Keep children and pets away.
Be aware of your surroundings. Standing in water while
repairing a spa puts you at serious risk.
Avoid working in cramped or crowded conditions.
800.645.3201
System Description
Highly advanced microprocessor technology has been combined with solid-state
electronic switches to produce the worlds finest, high quality
state-of-the-art digital control systems. Balboa control systems are
technologically sophisticated, yet easy to understand, use, and troubleshoot.
M-7 Sensors
Circuit Board
A typical circuit board has the following output
capabilities:
240 VAC System
Two-speed pump
240 VAC, 60 Hz, 2 HP
Single-speed pump
240 VAC, 60 Hz, 2 HP
Blower
240 VAC, 60 Hz, 2 HP
Heater
240 VAC, 60 Hz, 5.5 kW
Light
12 V, 12 W, 60 Hz, 1A or
120 V, 100 W
In addition to these outputs, the board receives input
from the two temperature sensors located within the heater
housing.
Important
Do not remove and replace the circuit board unless you
have tested all other components and proven that the circuit
board is actually causing the problem.
www.balboa-instruments.com
Wiring Checks
Safety is key when servicing any spa or spa control panel. Remember, safety
comes first for you and your customer. Please take all necessary precautions
before attempting any repairs. Wiring checks are the first step to ensure safety
and proper function before beginning service on a unit.
Important
Using non-copper wire can be dangerous, and also can
be the cause of a spas malfunction. If non-copper wire
is used at any point, we do not recommend servicing the
spa until an electrician replaces it with the proper gauge
copper wire.
Important
This service must be single phase. Any abnormal
voltage reading requires an electrician. Do not
attempt to fix these types of problems yourself. High
voltage can seriously injure or kill.
800.645.3201
Important
The National
Electrical Code states
that a service disconnect
breaker box (a G.F.C.I.
can be used for this
purpose) must be
located at least five
feet away from the
spa and should be
conveniently
located near the
equipment bay. If it is not in
plain sight, keep the disconnect padlocked when in the off
position.
Precautions
Effective January 1994, G.F.C.I.s are required
for spa installations. Prior to that, G.F.C.I.s had
been recommended for spa installations, but were
not mandatory.
If the spa you are servicing was not installed with a
G.F.C.I., strongly urge your customer to improve safety and
comply with current standards by installing one.
Note: A suitable G.F.C.I. may be acquired through your local
distributor or Balboa Direct.
Important!
Remember, high voltage is still accessible in the house
breaker box even though you have turned off the spa breaker.
www.balboa-instruments.com
From the neutral bar, locate the white load neutral, and
the green ground wire.
Be sure there are no other appliances on the spa
circuit. If there are, service must be re-wired to supply
the spa only.
Make sure all four wires exit the house breaker box via
conduit, routed to the G.F.C.I. breaker box. The black
should be connected to the G.F.C.I. line-in 1. The red
should be connected to the line-in 2. The white load
neutral connects to the neutral bar. The green ground
wire should be attached securely to the ground lug inside
the G.F.C.I. box.
Important!
This service must be single phase. Any abnormal voltage
reading requires an electrician. Do not attempt to fix
problems yourself. High voltage can seriously injure or kill.
800.645.3201
Important!
If the voltage is not within the acceptable range, call
an electrician or the local electric company to diagnose
the problem.
www.balboa-instruments.com
Wiring Schematic
SUV, Value M-7, 2000LE M-7, Prestige Systems
House Breaker Box
S
y
s
t
e
m
RED (HOT)
BLK (HOT)
B
o
x
WHT
GRN
GROUND
G.F.C.I. Breaker Box
RED (HOT)
BLK (HOT)
WHT
GRN (GROUND)
WHT
BLK (HOT)
RED (HOT)
WHT (NEUTRAL)
GRN (GROUND)
WHT
Elite System
Spa
In-SpaSystem
System Box
Box
TB1
1
10
GRN (GROUND)
WHT
RED (HOT)
BLK (HOT)
WHITE (NEUTRAL)
BLK (HOT)
RED (HOT)
GREEN (GROUND)
2
3
4
5
800.645.3201
Brown outs
Brown outs can have an effect on the spas operation in
a variety of ways. The control panel may go blank, have
scrambled messages on the LCD, or only a few features will
function.
If the system is getting the proper voltage at TB1, but still
does not operate, then test for a blown power input fuse.
If the system you are troubleshooting is a Prestige,
2000LE M-7, Value M-7, or SUV System, the power input
fuses snap directly to the circuit board.
Elite System
Measure fingers 5 and 6 of the circuit board. You should
see either 120V or 240V, depending upon the system
configuration.
If you determine that there is no voltage at fingers 5 and
6, then the system power input fuse needs to be
replaced. This fuse is located in the large fuse block
inside the system box. This configuration utilizes a 30A
time delay fuse.
Note For All Systems: In each situation, the most likely
reason for the system power input fuse to blow is a pump
problem. However, on occasion, a blower problem may also
cause this fuse to blow if a 10A blower fuse is not built in.
Once the power input fuse has been changed:
Probe the red wire and the white neutral wire. Again,
voltage must be between 108 and 132 V.
Check the voltage between the black and red
wires again. Acceptable voltage range is between 216
and 264 V.
These readings should be taken under peak load
conditions.
Important
If the voltage is not in the acceptable range, call an
electrician or the local electric company to diagnose the
problem.
11
Troubleshooting (cont.)
To Determine the Cause of a Blown Power
Input Fuse:
Perform the following sequence of tests:
12
800.645.3201
Troubleshooting (cont.)
Test the Circuit Board Protection Fuse:
SUV, Value M-7, 2000LE M-7,
and Prestige Systems
If your system has a white neutral line coming in from either
your service disconnect or GFCI installed into TB1:
Probe from the white TB1 terminal and one side of the
circuit board protection fuse. The voltage should read
120 volts.
Probe from the white TB1 terminal and the other side of
the circuit board protection fuse. The voltage should read
120 volts.
Elite System
For a class 2 transformer circuit, UL requirements specify
that a fuse must be permanently installed to protect the
circuit board.
If you have determined that the system is getting
proper voltage through the power input fuse, then you
must check to see if the circuit board protection fuse
has blown.
First, turn off the power. Next, unplug the transformer
from the circuit board, then turn the power back on and
probe from the red TB1 terminal to one side of the fuse.
The voltage should read 120 V or 240 V depending on
the system.
Probe from finger 5 to the other side of the circuit board
protection fuse. The voltage should read 120 V or 240 V
depending on the system.
If either side has 0 volts, then the fuse is blown. If so, turn
off the power and replace the circuit board. (See page 26.)
Note: Another, less likely reason for the circuit board
protection fuse to blow is that a 240 V transformer was
replaced with a 120 V transformer by mistake.
Make sure that the transformer is properly rated for the
system. The voltage reading between fingers 5 and 6 on
the circuit board will determine the proper transformer
input voltage for Deluxe and Standard models.
For a 120 V system, the transformer should have two
blue connectors.
A 240 V transformer should have one blue connector.
If you determine that the circuit board protection
fuse is not blown, this means that the transformer is
receiving voltage.
www.balboa-instruments.com
Important
Be sure to turn the power off before replacing any
component, especially a circuit board.
13
www.balboa-instruments.com
15
800.645.3201
Blower
Jets
Electronic Spa Controls
Lite Duplex
System
Temp
Light
Deluxe Panel
Bulb Replacement
www.balboa-instruments.com
Bulb Replacement
800.645.3201
Panel Messages
Panel messages are a quick clue toward
solving a variety of problems. Here are the
most common messages and what they mean:
The Panel Displays:
,
, or
, or
or
, or
or
, or
, or
, or
, or
, or
All spa models are different in shape and size and have
different thermal characteristics; therefore, Balboa
Instruments, Inc. cannot be held responsible for freeze
damage to the spas plumbing. Testing is the responsibility
of the spa manufacturer and must be done to determine
the best location for the freeze sensor.
, or
, or
, or
www.balboa-instruments.com
231F 110.5C
190F 88.0C
162F 72.0C
144F 62.5C
131F 55.0C
126F 52.5C
121F 49.5C
119F 48.5C
117F 47.5C
115F 46.0C
113F 45.0C
112F 44.5C
110F 43.5C
21
22
23
G.F.C.I. Troubleshooting
Keep in mind that a majority of G.F.C.I. tripping problems can be attributed to
incorrect wiring. G.F.C.I. troubleshooting usually finds the problem.
First, turn off the main circuit breaker, then remove both
heater straps or wires from the system heater output, not
the heater itself.
After restoring the power, try to reset the G.F.C.I. again. If
it no longer trips after the system calls for heat, then
replace the heater.
If the G.F.C.I. still trips, look for pinched or shorted wires
at the transformer. Make sure that the screws that attach
the transformer to the system box have not pinched or
damaged the insulation of the transformer wires.
If the transformer wires are undamaged, check for any
other pinched wires. Refer to the wiring diagram to verify
the correct wiring of the control system.
If everything looks to be in perfect working order, then
the G.F.C.I. may be defective.
24
Ground-Fault Circuit
Interrupter/Circuit
Breaker (GFCI)
800.645.3201
25
Important!
Do not remove and replace the circuit board
unless the fault has positively been determined to be
the circuit board.
26
Important
Do not remove and replace the circuit board unless you
have tested all other components and proven that the circuit
board is actually causing the problem.
800.645.3201
Spa Behavior
See manufacturer's owners manual or reference card for
general information on operating the spa, including
programming filters and other settings that are changed from
the topside control panel.
In Priming Mode, the Mode button toggles the ozone
on/off (with a 15-second timeout). This can be useful if you
want to verify ozone generator operation without waiting for
a filter cycle. This feature is not available on smaller panels
where Mode is a multi-button sequence, since such a
sequence exits Priming Mode.
www.balboa-instruments.com
27
Value M-7
S#
Mode of Operation
On
Off
S10
30/50 Amp
30A
50A
S9
N/A
N/A
N/A
S8
Deg C/F
C
F
S7
N/A
N/A
N/A
S6
50/60 HZ
50HZ 60HZ
S5
N/A
N/A
N/A
S4
N/A (Must be off)
N/A
N/A
S3
Panel Option
Mini
DigDup
S2
N/A
N/A
N/A
S1
Test Mode
On
Off
Jumper J43 is persistent memory reset. Reset
persistent memory to default by putting J43 on 2 pins
during power-up (until Pr is displayed). Must be
on 1 pin otherwise for persistent memory to work.
2000LE M-7
S#
Mode of Operation
On
Off
S10
30/50 Amp
30A
50A
S9
1 or 2 Pumps
1 Pump 2 Pumps
S8
Deg C/F
C
F
S7
Pump 1spd/2spd
1spd
2spd
S6
50/60 HZ
50HZ 60HZ
S5
Pump1 1spd/2spd in Circ 1spd
2spd
S4
N/A (Must be off)
N/A
N/A
S3
Circ/Non-Circ
Circ
Non-Circ
S2
F.O. / Spa Light
F.O.
Spa Light
S1
Test Mode
On
Off
Jumper J43 is persistent memory reset. Reset persistent
memory to default by putting J43 on 2 pins during
power-up (until Pr is displayed). Must be on 1 pin
otherwise for persistent memory to work.
28
Prestige
SW1 BANK
S#
Mode of Operation
On
S12
Battery Reset
Reset
S11
Pump 3 Enable
On
S10
Pump3 1spd/2spd
1spd
S9
Pump2 1spd/2spd
1spd
S8
Enable Ozone Disp*
On
S7
Pump1 1spd/2spd in Circ 1spd
S6
Circ System
Yes
S5
Deg C/F
C
S4
Spa Light
On/Off
S3
Amperage Select
S2
Amperage Select
S1
Test Mode
On
Off
No
Off
2spd
2spd
Off
2spd
No
F
Dim
Off
S4
S3
S2
S1
Off
N/A
3kw
(equal or
less than)
60HZ
30 min
No
No
S1-3
On
On
Off
Off
Important
Dip Switches must be pushed entirely to one side to
register on or off.
800.645.3201
Logic
Jumper
Important!
The illustrations at left indicate how the logic jumpers are used. If a
jumper is installed on two pins, it is completing a circuit across the
two pins. If it is installed on one pin, the circuit between the two
pins is open. Sometimes a logic jumper will be used on a group of
three pins and depending on which two pins have been connected
by the jumper, feature A or B will be enabled.
Open
Shorted
Feature A Enabled
www.balboa-instruments.com
Feature B Enabled
29
Function of Jumper
Position*
J-6
J-7
J-9
J-10
J-16
Enables O3 message
J-24
Disables ORP
J-25
J-36
J-41
Disables pump 2
(ORP disabled)
(60hz, F operation selected)
(Memory storage allowed)
(Pump 2 enabled)
* The Jumper symbols shown here are oriented to correspond to their actual
positions on the printed circuit board.
= Open Jumper
J-36
= Shorted Jumper
J-7
Portion of PC board
for Elite showing
location of jumpers.
J-16
J-25
J-10
J-6
J-41
J-8
J-24
30
800.645.3201
120V
Pump 2 load
(no blower fuse
required)
28
3a
5
18
17
3b
19
15
16
20
22
14
21
4
23
J43
26
13
7
7
26
24
25a
27
11
25b
12a
12b
10
A/C Input
120/240 VAC optional connectors for conversion of
pumps, ozone and blower
Onboard load fuses
a. F5 25A
b. F6 25A
Circuit Board Protection Fuse (F4)
Onboard blower fuse (F7)
Onboard transformer
Control panel input, duplex or mini panel
Blower or Pump 2 Relay
Blower or Pump 2 Output
10-position dip switch, modes of operation (see chart)
Aux freeze protection circuit (J22, optional)
a. Sensor A connection
b. Sensor B connection
U4 main processor
Circ Pump Output (if applicable)
www.balboa-instruments.com
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
21a
20
17
13
15
21b
11a
3a
16
14
10
11b
18
3b
2
8
1
12
24b
25a
23a
22
23b
A/C Input
120/240 VAC optional connectors for conversion of
pumps, ozone and blower
Onboard load fuses
a. F5 25A
b. F6 25A
Circuit Board Protection Fuse (F4)
Spa and fiber optic light fuse 3A 250V (F1)
Onboard blower fuse (F7)
Onboard transformer
Control panel input, duplex or mini panel
10-position dip switch, modes of operation (see chart)
Aux freeze protection circuit (J22, optional)
a. Sensor A connection
b. Sensor B connection
U4 main processor
Pump 1 low relay (K1)
Pump 1 low output (J29)
J43
15.
16.
17.
18.
19.
20.
21.
21.
22.
23.
24.
25.
27b
5
14
25
13
15
17
3a
18
27a
26
23
11a
24
16
11b
3b
21
22
1
12
8
19
30b
20
4
28
30a
29a
10
29b
J43
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
27.
28.
29.
30.
31.
12
13
34
50
46
42
10
53
44
56
38
40
35
45
41
52
49
51
47
26a
20a
54
19
26b
43
20b
57
28
32
27
33
15
14
31
J24
31
30
22
36
24
29
24
21
4a
18
4b
48
24
6a
25
9a
25
9b
34
11
37
17
23
16
1
52
6b
55
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
55.
56.
57.
800.645.3201
8a 8b
9
14
27
21
19
21
38
23
17
28
12
39
13
24
10
32
38
26
33
16
6
11
34
25 25 15 15
2 18 29 31 20 30
22
www.balboa-instruments.com