Basf Masterflow 678 Tds

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Technical Data Guide

Related Documents

MasterFlow 678 Installation Guide

03 63 00
Epoxy
Grouting

MasterFlow 678

Deep-pour multiple-use epoxy grout


Formerly masterflow 678 dp plus
Packaging
MasterFlow 678 is packaged in
convenient premeasured units.
1 Unit consists of the following:
16.0 lb (7.257 kg) pail Part A
8.0 lb (3.629 kg) bottle Part B
4 x 54 lb (24.5 kg) bags Part C
Yield
1.8 ft3 (0.05 m3)
Storage
2 years (for both resin and hardener)
when properly stored
Shelf Life
Store in unopened containers at
60 to 80F (16 to 27C) in clean,
dry conditions
VOC Content
0 g/L less water and exempt solvents

Master Builders Solutions by BASF


www.master-builders-solutions.basf.us

Description

MasterFlow 678 is a low-exotherm, three-component epoxy grout for use where deep sections of
epoxy grout must be placed with low heat generation.

PRODUCT HIGHLIGHTS
Long working time helping to facilitate

proper placement
Excellent creep resistance, even at high

HOW TO Apply
Do not install this product without
reading and referencing the companion
MasterFlow 678 Installation Guide.

temperatures increasing product performance


over a wider temperature range
Low exotherm resulting in minimal heat generation Mixing
Positive expansion to help fill minor gaps and
1. Aggregate must be completely dry.
voids in forming
2. Precondition all components to 70 F (21 C) for
Superior adhesion for positive bonding
24 hours before using.
characteristics to concrete and steel
3. Pour the hardener (Part B) into a pail of grout
Can be placed in lifts of up to 18" thick without
resin (Part A) and stir by hand, using a spatula
or paint stirring paddle, until well mixed to a
reinforcement making it ideal for deep pours
uniform amber color.
4. Pour the mixed liquids into a horizontal shaft
mortar mixer or a Kol type mixer without delay.
Applications
Deep-pour baseplate grouting
5. Add the grout aggregate, one bag at a time, and
Grouting of pump bases
mix only until aggregate is completely wetted
Setting of baseplates
out to avoid air entrapment. Caution: Always
Grouting of compressors and drive motors
add aggregate to the mixer after the premixed
Grouting of anchors, bars and dowels
liquids have been poured in.
Rebuilding deteriorated curbs, bases and columns 6. Pour the grout into a wheelbarrow or buckets
Repair of spalled concrete
for transporting to pour-site. Remove it from the
wheelbarrow within 15 minutes.
7. After the pour is complete, remove uncured
epoxy from the mixer, wheelbarrow and tools
with soap and water or a citrus degreaser.
Cured material must be removed mechanically

Technical Data Guide


MasterFlow 649

Technical Data
Composition
MasterFlow 678 is a low-exotherm
three-component epoxy.
Property

VALUE

Resin/hardener ratio,
by weight

2 to 1

Density, lbs/ft3 (kg/m3)

125 (2,000)

Working time, min,


at 70 F (21 C)

90

Test Data
Property

Results Test Method

Initial set, hrs

Vicat, ASTM C 953

Final set, hrs

7.5

Vicat, ASTM C 953

Expansion

Passes

ASTM C 827

Effective Bearing Area (EBA)

>95%

ASTM C 1339

Compressive strength, psi (MPa)


1 day
7 days
28 days

70 F (21 C)
6,400 (44)
11,000 (76)
12,000 (83)

ASTM C 579, modified

Adhesion to concrete, psi (MPa)

2,500 (17)

Michigan DOT

Adhesion to steel, psi (MPa)

4,000 (28)

Michigan DOT

Coefficient of thermal expansion,


in/in/ F

20.0 x 10

ASTM C 531

Tensile strength, psi (MPa)

1,900 (13)

ASTM C 307

Flexural strength, psi (MPa)

3,900 (27)

ASTM C 580

Creep, in/in/ F

1 day
28 days

@ 90 F (32 C)
@140 F (60 C) ASTM 1181
1,200 psi (8.2 MPa) 600 psi (4.1 MPa)
2.9 x 10-3
2.9 x 10-3
2.9 x 10-3
3.5 x 10-3

Peak exotherm, F ( C)
1,000 g, adiabatic conditions

93 (34)

140 F (60 C)

10,000 (70)
8,500 (59)

-6

Test results are averages obtained under laboratory conditions. Expect reasonable variations.
Unless otherwise noted, test samples were cured 7 days at 73 F (23 C) and 50% relative humidity.

Master Builders Solutions by BASF


www.master-builders-solutions.basf.us

For Best Performance


Do not add solvent, water, or any other material

to the grout.
Do not alter the resin or hardener proportions.
Contact your local representative for a pre-job

conference to plan the installation.


For guidelines on specific anchor-bolt

applications, contact Technical Service.


Substrate temperature must be greater than

50 F (10 C).
Cold material will exhibit decreased flowability

and reduced strength development.


Minimum placement thickness is 1" (25 mm).

Consult your BASF representative before placing


lifts more than 6" (152 mm) in depth.
Chamfering the concrete edge helps reduce
thermal cracking. Following proper installation
procedures also reduces the potential for cracking.
For professional use only; not for sale to or use
by the general public.
Make certain the most current versions of
product data sheet and SDS are being used;
visit www.master-builders-solutions.BASF.us to
verify the most current versions.
Proper application is the responsibility of the
user. Field visits by BASF personnel are for the
purpose of making technical recommendations
only and not for supervising or providing quality
control on the jobsite.

Technical Data Guide


MasterFlow 649

Health, Safety and Environmental

LIMITED WARRANTY NOTICE

Read, understand and follow all Safety Data Sheets


and product label information for this product
prior to use. The SDS can be obtained by visiting
www.master-builders-solutions.basf.us,
e-mailing your request to [email protected]
or calling 1(800)433-9517. Use only as directed.
For medical emergencies only,
call ChemTrec 1(800) 424-9300.

BASF warrants this product to be free from


manufacturing defects and to meet the technical
properties on the current Technical Data Guide,
if used as directed within shelf life. Satisfactory
results depend not only on quality products but
also upon many factors beyond our control. BASF
MAKES NO OTHER WARRANTY OR GUARANTEE,
EXPRESS OR IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE WITH RESPECT TO ITS
PRODUCTS. The sole and exclusive remedy of
Purchaser for any claim concerning this product,
including but not limited to, claims alleging
breach of warranty, negligence, strict liability
or otherwise, is the replacement of product or
refund of the purchase price, at the sole option of
BASF. Any claims concerning this product must
be received in writing within one (1) year from the
date of shipment and any claims not presented
within that period are waived by Purchaser. BASF
WILL NOT BE RESPONSIBLE FOR ANY SPECIAL,
INCIDENTAL, CONSEQUENTIAL (INCLUDING LOST
PROFITS) OR PUNITIVE DAMAGES OF ANY KIND.
Purchaser must determine the suitability of the
products for the intended use and assumes
all risks and liabilities in connection therewith.
This information and all further technical advice
are based on BASFs present knowledge and
experience. However, BASF assumes no liability
for providing such information and advice
including the extent to which such information
and advice may relate to existing third party
intellectual property rights, especially patent
rights, nor shall any legal relationship be created
by or arise from the provision of such information
and advice. BASF reserves the right to make any
changes according to technological progress
or further developments. The Purchaser of the
Product(s) must test the product(s) for suitability
for the intended application and purpose
before proceeding with a full application of the
product(s). Performance of the product described
herein should be verified by testing and carried
out by qualified experts.

BASF Corporation
Construction Systems

889 Valley Park Drive, Shakopee, MN 55379


www.master-builders-solutions.basf.us

2013 BASF Corporation Form No.1019404 rev 09/13

Customer Service 1(800) 433.9517


Technical Service 1(800) 243.6739