System Charging Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32
At a glance
Powered by AI
The key takeaways are that the document discusses procedures for properly charging refrigerant systems, including capillary tube and expansion valve systems, as well as checking the performance in cooling and heating modes.

The different types of metering devices discussed are capillary tubes, thermostatic expansion valves (TXVs), and fixed orifice expansion valves (FCCVs).

To check cooling performance, the document says to allow pressures to stabilize and measure indoor wet bulb temperature, outdoor dry bulb temperature and pressures (both head and suction). Then locate the intersection of temperatures on the performance chart to check pressures are within specified ranges.

System Charging

Heating and Cooling Capillary Tube Systems Thermostatic Expansion Valve Systems Charging by Weight
American Standard Inc. 2001

Preface
The purpose of this publication is to provide service technicians with the general knowledge necessary to properly charge a Heat Pump system or an Air Conditioning system. This manual outlines, in detail, recommended charging procedures to be followed on all capillary tube and expansion valve systems. Before any of the procedures outlined in this manual can be initiated the service technician must have all the necessary tools as listed under equipment on page 4. In addition to tools proper airflow must be verified prior to any attempt to charge a system. The system should be checked to confirm that all air filters are clean, that the blower assembly and coil are free of dirt and that the duct system is adequate. If proper airflow is not available all associated problems must be corrected prior to attempting any charging procedure. Cooling performance can be checked when outdoor temperature is above 75. Heating performance can be checked when the outdoor temperature is below 60.

Section 608, paragraph C of the Clean Air Act of 1990 states:


Effective July 1, 1992, it shall be unlawful for any person, in the course of maintaining, servicing, repairing, or disposing of an air conditioning system, to knowingly vent or release any CFC or HCFC refrigerant. Minimal releases (air purges of refrigerant hoses) associated with good faith attempts to recapture or recycle are exempt from the ban on venting. The Clean Air Act has provisions for significant fines and/or imprisonment for noncompliance. These fines could range from $5,000 to $25,000 per day.

Note: This publication is general in nature and is intended for INSTRUCTIONAL PURPOSES ONLY. It is not to be used for equipment selection, application, installation, or specific service procedures.

Table Of Contents
Refrigerant System Charging .................................................................................................................................... Service Tools Equipment ...................................................................................................................................... Metering Devices ....................................................................................................................................................... Cooling Systems ........................................................................................................................................................ Heat Pump Systems .................................................................................................................................................. Equipment Pressure Taps (General) ......................................................................................................................... Charging Capillary Tube/FCCV Cooling Mode Only .............................................................................................. Example Slide Rule Calculation ................................................................................................................................ Performance Cooling Mode .................................................................................................................................... 2 2 3 4 5 6 7 8 9

Charging and Performance Cooling Mode ............................................................................................................ 10 Charging By Subcooling Cooling Mode ................................................................................................................. 11 Performance Heating Mode .................................................................................................................................... 12 Charging Heating Mode .......................................................................................................................................... 13 Charging By Weight ................................................................................................................................................... 15 Calibrating Pressure Gauges ..................................................................................................................................... 16 Refrigerant 410A Background ............................................................................................................................................................ 17 Characteristics ........................................................................................................................................................ 17 Refrigerant Safety ...................................................................................................................................................... 18 Application Notes ...................................................................................................................................................... 19 System Charging Using R410A ................................................................................................................................ 20 R-410A Temperature and Pressure Chart ................................................................................................................. 21 Subcooling Table ....................................................................................................................................................... 22 R-410A Split Cooling Units Only ............................................................................................................................... 24 R-410A Split Heat Pump Units Only ......................................................................................................................... 25 R-410A Charging and Performance Cooling Mode ............................................................................................... 26 R-410A Charging Heating Mode R-410A ............................................................................................................. 27

IMPORTANT
These procedures should be followed at initial start-up and at anytime the power has been removed for 12 hours or more. To prevent compressor damage which may result from the presence of LIQUID refrigerant in the crankcase: 1. Make certain the room thermostat is in off position. (The compressor is not to operate.) 2. Apply power by closing the system disconnect switch. This energizes the compressor heater which evaporates the liquid refrigerant in the crankcase. Allow 30 minutes for each pound of refrigerant in the system as noted on the unit nameplate. 3. After proper elapsed time the thermostat may be set to operate the compressor. 4. Except as required for safety while servicing DO NOT OPEN SYSTEM DISCONNECT SWITCH.

Refrigerant System Charging


Refrigerant charging is one of the most important and probably least understood service procedures practiced in the air conditioning industry. Improperly charged systems lead to inefficient operation and premature equipment failure. The graph below illustrates a typical package cooling system charge being varied from 50% undercharge to 37.5% overcharge. Airflow and temperatures were held constant at ARI standard conditions as the charge was varied. Note the change in capacity, power input and EER as each pound of refrigerant was added above 50% undercharge.

Refrigerant Charge
BTUH
COOLING CAPACITY

Correct Charge
Optimum capacity Highest possible EER Longest equipment life
KW

POWER INPUT

BTU/WATT-HR

Undercharge
Capacity decreases Power input decreases but not in proportion to capacity EER goes down

EER

DISCHARGE PRESSURE

Equipment life is shortened

PSIG

Overcharge
SUCTION PRESSURE

Capacity decreases as more charge is added beyond the optimized capacity Power input increases EER decreases Equipment life is shortened

Temperature-F

EVAP. SUCT. SUPERHEAT

EER

BTU Output Power Input BTU Output

LIQUID SUBCOOLING

COP =
75 6# 87.5 7# 100% 8# 112.5 9# 125 10# 137.5% 11#

BTU Input

50% 4#

62.5 5#

Note:
1. The package cooling system used to develop the above information utilized a TXV refrigerant metering device. 2. Field conditions different from ARI conditions (95 db outdoor air, 80 db-67 wb return air) will yield results that vary from the graphs in this example.

Service Tools Equipment


The Service Tools needed to PROPERLY charge a refrigeration system includes: 1. Manifold Gauges 2. Electronic Temperature Analyzer (Temperature measurements should be made with a good quality electronic temperature tester such as a Robinair 12860, Annie A-8, Electro-medic M-99, or equivalent.) 3. Sling Psychrometer 4. Refrigerant- 22 (Mono-chlorodiflouromethane) 5. Approved refrigerant recovery system and holding tank.

Metering Devices
We use various types of refrigerant metering devices in air conditioning and heat pump systems. The cooling units we will discuss are equipped with Flow Control Check Valves (FCCV), see diagram below left, Capillary Tubes, Bleed-Type Thermostatic Expansion Valves (TXV-B) and Non-Bleed Thermostatic Expansion Valves (TXV-NB), see diagram below right. Current heat pump units which we will cover are equipped with Bleed and Non-Bleed TXV in outdoor sections with everything but Capillary Tubes on indoor coils. The CCBA and CUBA coils have a fixed flow control device for coolingonly applications. The FCCV Flow Control is used on TXA-C and TXC-C universal convertible coils. This metering device is applied to these coils for cooling and heat pump applications with 10 and 11 SEER products respectively. Package products may either use a FCCV or Capillary Tube metering devices. (FCCV coils are not an approved combination with a 5 ton 12 SEER or any 14 SEER outdoor units. These units can easily be overcharged with this type of metering device because the large volume of refrigerant in the system may not show an increase in head pressure. Only TVX coils should be used.) Care should be taken that the proper size FCCV is matched to the outdoor unit to insure that the correct volume of refrigerant is flowing through the system (approx. 3 lbs/ton/minute). The orifice size of the FCCV is marked on the side of the metering device. TXA-C and TXC-C coils are shipped with the orifice size that matches the most commonly used outdoor unit with that particular coil combination. That size is indicated on the tag on the coil connection end. Correct orifice size is dependent on the outdoor unit model. The proper orifice for the indoor unit is in a small bag attached to the outdoor unit. (Orifices shipped with indoor coils may or may not be correct for the outdoor unit, so the installer must verify size at the time of installation.) Refer to Service Facts which also shows the proper size and type of metering device for the application. TXC-E high efficiency coils are equipped with BleedType TXVs for refrigerant control. The diaphragm on the TXV opens or closes the valve orifice to maintain a preset superheat and control refrigerant flow as load conditions on the evaporator change. When the compressor shuts off, refrigerant is able to bleed between the high pressure side upstream of the TXV and the low pressure downstream of the TXV; the system will equalize within 3-5 minutes. Also, these coils have a larger internal volume in order to support additional charge and provide for higher efficiencies. These coils are designed to be matched with 12 SEER outdoor units for higher SEER requirements. These coils can also be mated to 10 and 11 SEER units. The TXC-S variable speed coils are equipped with Non-Bleed TXVs (TXV-NB). These coils do not equalize or bleed through the valve orifice which helps to prevent refrigerant from migrating back to the compressor after system shutdown. These coils should only be applied to outdoor products that are equipped with quick start components because of the pressure differential during system start up. Scroll compressor unit does not require a quick start component. Variable speed coils are mated with 12 and 14 SEER products for high efficiency. Because todays high efficiency systems require additional refrigerant volume to produce the needed capacity and efficiency, it is important that systems be installed with the proper size indoor coils equipped with the necessary metering device. Failure to do so could cause a decrease in reliability, capacity and efficiency.

AccutronTM Flow Control Check Valve (FCCV)


ACCUTRON COMPONENTS
TM

Typical Thermostatic Expansion Valve

ADAPTER

POWER ELEMENT SEAT PIN

FLOW CONTROL CHECK VALVE (FCCV) ORIFICE BODY SEALING CAP

SUPERHEAT SPRING
FIELD SUPPLIED LIQUID LINE

THERMOSTATIC BULB

Cooling Systems
The diagram below illustrates the proper Manifold Gauge and Temperature Analyzer connections for charging a split cooling system.

Split System
1. Attach center hose from manifold to drum of refrigerant. Purge center hose with a minimum amount of refrigerant. Use the guidelines for deminimus release of refrigerant. 2. Purge with a minimum amount of refrigerant and attach suction (compound) gauge hose to the suction line (larger refrigerant line) pressure tap. This pressure tap is located on the suction line service valve. 3. Purge with a minimum amount of refrigerant and attach the high pressure gauge hose to the liquid line (smaller refrigerant line) pressure tap. This pressure tap is located on the liquid line service valve. 4. Attach temperature probe securely to the suction line near the service valve (if charging a cooling system with capillary tubes or checking TXV superheat). Insulate the probe with suction line insulation to prevent the element from being influenced by the surrounding air. Allow adequate time for system temperatures to stabilize before recording the temperature.

Cooling Package System


1. Attach center hose from manifold to drum of refrigerant. Purge center hose with a minimum amount of refrigerant. Use the guidelines for deminimus release of refrigerant. 2. Purge with a minimum amount of refrigerant and attach suction (compound) gauge hose to the suction line (larger refrigerant line) pressure tap. This pressure tap may be located on the inside of the cabinet. For example: on the Voyager and Impack lines. 3. Purge with a minimum amount of refrigerant and attach high pressure gauge hose to the liquid line (smaller refrigerant line) pressure tap. This pressure tap is located inside the cabinet. 4. Attach temperature probe securely to the suction line approximately 6" away from compressor, if charging a cooling system with capillary tubes or checking TXV superheat. Insulate the probe with suction line insulation to prevent the element from being influenced by the surrounding air. Allow adequate time for system temperatures to stabilize before recording the temperature.

On either style of system, if refrigerant must be removed to achieve charge balance, an approved refrigerant recovery system and an approved storage tank must be used.

Heat Pump Systems


The diagram below illustrates the proper Manifold Gauge and Temperature Analyzer connections for charging a split heat pump system in the cooling or heating mode.

Heat Pump Split System


1. Attach center hose from manifold to drum of refrigerant. Purge with a minimum amount of refrigerant. Use the guidelines for deminimus release of refrigerant. 2. Purge with a minimum amount of refrigerant and attach suction (compound) gauge hose to low side charging port. This charging port (pressure tap) on older models protrudes from the corner service valve panel of the heat pump and is piped directly to the suction line at the compressor. On current models this pressure tap is inside the cabinet. 3. Purge with a minimum amount of refrigerant and attach the high pressure gauge hose to the high side charging port. The high and low sides charging ports (pressure taps) on older models protrude from the corner service valve panel of the heat pump and are piped directly to the discharge and suction lines at the compressor. Use this tap to obtain head pressure when charging heat pumps in the heating or cooling mode. DO NOT use the pressure tap on the liquid line (small) service valve for charging or performance measurements. On current models, this pressure tap is inside the cabinet. 4. Attach the temperature probe securely to the suction line near the service valve if charging a system with indoor capillary tubes by the super heat method or a heat pump with capillary tubes by the hot gas method. Insulate the probe with suction line insulation to prevent the element from being influenced by the surrounding air. Allow adequate time for recording the temperature.

Heat Pump Package System


1. Attach center hose from manifold to drum of refrigerant.. Purge center hose with a minimum amount of refrigerant. Use the guidelines for deminimus release of refrigerant. 2. Purge with a minimum amount of refrigerant and attach suction (compound) gauge hose to low side charging port. This charging port (pressure tap) is inside the cabinet of the heat pump and is piped directly to the suction line at the Compressor. 3. Purge with a minimum amount of refrigerant and attach the high pressure gauge hose to the high side charging port. The high side charging port (pressure tap) is inside the cabinet of the heat pump and is piped directly to the discharge line at the compressor. Use this tap to obtain head pressure when charging heat pumps in the heating or cooling mode. 4. Attach the temperature probe securely to the suction line approximately 6" away from compressor, if charging a system with indoor capillary tubes by the superheat method or a heat pump with capillary tubes by the hot gas method. Insulate the probe with suction line insulation to prevent the element from being influenced by the surrounding air. Allow adequate time for recording the temperature.

On either style of system, if refrigerant must be removed to achieve charge balance, an approved refrigerant recovery system and an approved storage tank must be used.

Equipment Pressure Taps (General)


Pressure taps may be located on the equipment cabinet, on the refrigerant lines, or on refrigerant line service valves. Some equipment may have pressure taps at more than one location. See the charging charts located on the equipment for selecting proper pressure taps. Inaccurate pressure readings will occur if the wrong taps are used. Pressure taps located on or inside the equipment cabinet must be used on heat pumps. Inaccurate readings and damage to pressure gauges will result if the wrong taps are used. Three phase 7.5 ton and larger split system models have pressure taps located on service valves which are closed when the valves are fully open in their operating position (backseated). After connecting gauges to pressure taps, the service valves are turned one turn in a clockwise direction to open the pressure taps. Do not exceed one turn. When pressure measurements have been completed, return the valves to their fully backseated position. Replace and tighten valve caps securely to prevent leaks. Cover caps on pressure taps should always be replaced and tightened after making pressure measurements to prevent leaks. Do not overtighten caps on Schrader type pressure taps. The tap may be damaged preventing future use.

Manifold Gauge Removal


Caution must be used when removing hoses from a refrigerant system. When attaching and removing manifold gauges access valve actuators manufactured by Robinair, Watsco, J.B. Industries, Imperial Eastman and Delco may be used to prevent loss of refrigerant charge. Liquid refrigerant when released can cause severe burns and permanent eye damage. Always wear safety glasses, face mask and protective clothing when handling refrigerants.

Charging Capillary Tube/FCCV Cooling Mode Only R-22


Current Superheat Method
1. Measure indoor dry bulb temperature. (Return air at air handler). 2. Measure outdoor dry bulb temperature. (Measure at outdoor unit).
SUPERHEAT F

50 45 40 35 30 25 20 15

SPLIT SYSTEM
INDOOR DRY BULB TEMPERATURE F INDOOR WET BULB*

From Dwg. No. 21C141108 Rev. 0

95/79 90/75 85/71


1 80/67

3. Measure suction pressure at suction pressure tap. 4. Measure suction temperature before the suction service valve on a split system or 6" away from the compressor on a package system. 5. You may determine the actual system superheat in degrees by referring to a temperature pressure chart or the low side manifold gauge and the measured suction line temperature. 6. *Find the intersection when the outdoor temperature and indoor temperature meet and read degrees superheat. If unit superheat is more than 5 above chart value, add R-22 until within 5. If unit superheat is more than 5 below chart value, remove R-22 until within 5, using an approved recovery system. 7. If superheat is below the 5 limit line, DO NOT ADD R-22.

75/63 70/58

10 5

DO NOT ADD CHARGE IF LIMIT LINE POINT FALLS BELOW THIS LINE

55

60

65

70

75

80

85

90

95

100 105 110 115

OUTDOOR TEMPERATURE F

50 45

PACKAGE SYSTEM
95/79 90/75

From Dwg. No. 21B123511 Rev. 0

40 85/71 35 80/67
SUPERHEAT F

30 25 20 15 10 5

75/63 70/58
INDOOR WET BULB* INDOOR DRY BULB TEMPERATURE F

6 6
DO NOT ADD CHARGE IF LIMIT LINE POINT FALLS BELOW THIS LINE

55

60

65

70

75

80

85

90

95

100 105 110 115

OUTDOOR TEMPERATURE F

Charts based on 400 CFM/ton indoor airflow and 50% relative humidity, use only on systems that cool with an FCCV or capillary tube.
*If Relative Humidity is above 70% or below 20% use indoor Wet Bulb Temperature.

Example Slide Rule Calculation R-22


1. INDOOR TEMPERATURE
DRY BULB
70 75 80 85 90 95 58 63 67 71 75 79

3a. REQUIRED SUPERHEAT AIR CONDITIONING CHARGING CALCULATOR


5 10 15 20 25 30

WET* BULB

(COOLING CAPILLARY TUBE and FIXED ORIFICE FLOW CONTROL)

3b.

INSTRUCTIONS:
50 51 52 54 55 56 57 59 60 62 63 64 66 69 71 75 78 81 84 87 91 94 41 42 43 44 45 46 47 48 49 50 51 52 53 55 57 59 61 63 65 67 69 71
Select the unit type (SPLIT or PACKAGE). Remove and reverse the slide if needed.

1. Set Indicator at INDOOR


TEMPERATURE -F.

2.
OUTDOOR TEMP. -F

2. Read REQUIRED SUPERHEAT


opposite OUTDOOR TEMP. -F (dash(-)means 5 required).

55 60 65 70 75 80 85 90 95 100 105 110 115

29 27 24 22 19 17 15 12 10 7

3a. Reset Arrow at REQUIRED 3b. Opposite measured SUCTION


SUPERHEAT. PRESSURE is the correct SUCTION LINE TEMPERATURE when system is properly charged. NOTE: If SUCTION LINE TEMP. -F is not within 5F of suction line reading; 1. Add charge to decrease line temperature requirements. 2. Remove charge to increase line temperature. 3. After adjusting R-22, repeat Steps 3a and 3b (if required).

REQUIRED SUPERHEAT

SUCTION PRESSURE

SUCTION LINE TEMP. -F

S P L I T

1995 American Standard Inc.

* If humidity is above 70% or below 20% use wet bulb temperature.

1. INDOOR TEMPERATURE
DRY BULB
70 75 80 85 90 95 58 63 67 71 75 79

3a. REQUIRED SUPERHEAT AIR CONDITIONING CHARGING CALCULATOR


5 10 15 20 25 30

WET* BULB

(COOLING CAPILLARY TUBE and FIXED ORIFICE FLOW CONTROL)

3b.

INSTRUCTIONS:
50 51 52 54 55 56 57 59 60 62 63 64 66 69 71 75 78 81 84 87 91 94 41 42 43 44 45 46 47 48 49 50 51 52 53 55 57 59 61 63 65 67 69 71
Select the unit type (SPLIT or PACKAGE). Remove and reverse the slide if needed.

1. Set Indicator at INDOOR


TEMPERATURE -F.

2.
OUTDOOR TEMP. -F

2. Read REQUIRED SUPERHEAT

Example

55 60 65 70 75 80 85 90 95 100 105 110 115

29 27 24 22 19 17 15 12 10 7

REQUIRED SUPERHEAT

SUCTION PRESSURE

SUCTION LINE TEMP. -F

opposite OUTDOOR TEMP. -F (dash(-)means 5 required). 3a. Reset Arrow at REQUIRED SUPERHEAT. 3b. Opposite measured SUCTION PRESSURE is the correct SUCTION LINE TEMPERATURE when system is properly charged. NOTE: If SUCTION LINE TEMP. -F is not within 5F of suction line reading; 1. Add charge to decrease line temperature requirements. 2. Remove charge to increase line temperature. 3. After adjusting R-22, repeat Steps 3a and 3b (if required).

S If Indoor Temperature (1) is ................ 80 P L and Outdoor Temperature is ............... 95 I T

Required Superheat (2) is ................... 10

1995 American Standard Inc.

* If humidity is above 70% or below 20% use wet bulb temperature.

1. INDOOR TEMPERATURE
DRY BULB
70 75 80 85 90 95 58 63 67 71 75 79

3a. REQUIRED SUPERHEAT AIR CONDITIONING CHARGING CALCULATOR


5 10 15 20 25 30

WET* BULB

(COOLING CAPILLARY TUBE and FIXED ORIFICE FLOW CONTROL)

If REQUIRED SUPERHEAT (2) is 10, Set Arrow on 10 (3a)

3b.

INSTRUCTIONS:
50 51 52 54 55 56 57 59 60 62 63 64 66 69 71 75 78 81 84 87 91 94 36 37 38 39 40 41 42 43 44 45 46 47 48 50 52 54 56 58 60 62 64 66
Select the unit type (SPLIT or PACKAGE). Remove and reverse the slide if needed.

1. Set Indicator at INDOOR


TEMPERATURE -F.

2.

2. Read REQUIRED SUPERHEAT


opposite OUTDOOR TEMP. -F (dash(-)means 5 required).

OUTDOOR TEMP. -F

If SUCTION PRESSURE is 63 psig (3b), SUCTION TEMPERATURE Should be 46F


REQUIRED SUPERHEAT

55 60 65 70 75 80 85 90 95 100 105 110 115

29 27 24 22 19 17 15 12 10 7

3a. Reset Arrow at REQUIRED 3b. Opposite measured SUCTION


SUPERHEAT. PRESSURE is the correct SUCTION LINE TEMPERATURE when system is properly charged. NOTE: If SUCTION LINE TEMP. -F is not within 5F of suction line reading; 1. Add charge to decrease line temperature requirements. 2. Remove charge to increase line temperature. 3. After adjusting R-22, repeat Steps 3a and 3b (if required).

SUCTION PRESSURE

SUCTION LINE TEMP. -F

S P L I T

1995 American Standard Inc.

* If humidity is above 70% or below 20% use wet bulb temperature.

Performance Cooling Mode R-22


Current Method Split System with a TWV036A Air Handler Cooling System with FCCV or Capillary Tubes Indoor Air Flow 1200 CFM

PERFORMANCE CURVES ARE NOT UNIVERSAL


Indoor Unit Alternates See Correction Table
400 350
LIQUID PRESSURE (PSIG)
71F

CORRECTION TABLE
INDOOR ENTERING 59F WET BULB F

Indoor Unit

CFM

Corr. S

Press. H

300 250 200 150 100


40 60 80

COOLING WITH CAPILLARY


BXA036A200A BXA736M2HPA BXA736D200A BXF036A200A BXA042A200A BXF048A200A BWH736A100A BWV036A100E BWV736A100E BWV042A100C 1200 1200 1200 1200 1350 1350 1200 1200 1200 1350 3 3 0 2 0 3 0 0 0 3 6 6 0 4 0 6 0 0 0 6

100

120

100 95 90
SUCTION PRESSURE (PSIG)
71F

85
59F

INDOOR ENTERING WET BULB F

COOLING WITH FCCV


TWV036A140A* 1200 0 0

80

2
75 70 65 60 55 50

Cooling performance can be checked when the outdoor temperature is above 75F. To check cooling performance, allow pressures to stabilize and measure indoor wet bulb temperature, outdoor temperature and pressures (both head and suction). Locate outdoor dry bulb and indoor wet bulb temperature. Find the intersection of the outdoor dry bulb temperature and indoor wet bulb temperature. Read head (or liquid) and suction pressure value in the left hand column of the chart. Actual Head Pressure should be 10 PSIG of chart. Suction Pressure should be 3 PSIG of chart.

40

60

80

100

120

OUTDOOR TEMPERATURE (F)

*Note: Interconnecting Lines: Gas - 7/8" O.D.: Liquid - 5/16" O.D. These graphs are for checking unit performance only. They are not to be used for system charging. To charge systems with indoor capillary tube, see superheat graphs or capillary tube slide rule calculation on pages 7 and 8.

Example:
Outdoor Dry Bulb Temperature = 90F Indoor Wet Bulb Temperature = 67F

Answer:
Suction Pressure @ 1200 CFM = 75 PSIG Head Pressure @ 1200 CFM = 225 PSIG

Charging and Performance Cooling Mode R-22


Current Method Split System with a TXC730P3HPA Coil Cooling System with Thermal Expansion Valve. Indoor Airflow 1060 CFM

PERFORMANCE CURVES ARE NOT UNIVERSAL


Indoor Unit Alternates See Correction Table CORRECTION TABLE
400 350
LIQUID PRESSURE (PSIG)

Indoor Unit
2
71F INDOOR ENTERING 59F WET BULB F

CFM

Corr. S

Press. H

300 250

4
200 150 100
40 100 95 90 60 80

TWH036A140A TWH736A140A TWH042A140A TWH742A140A TWH048A140A

1200 1200 1350 1350 1350 1125 1200 1200 1350 1350 1060 1060 1200

0 0 3 2 5 5 2 0 0 2 0 0 3

0 0 6 4 10 10 4 0 0 4 0 0 6

COOLING WITH TXV


1
100 120

SUCTION PRESSURE (PSIG)

BXA730P3HPA BXA736P3HPA BXF736P3HPA BXA742P3HPA BXF748P3HPA TXC730P3HPA TXC730P6HPB* TXC736P3HPA


INDOOR ENTERING WET BULB F

85 80 75 70 65 60 55

71F

2
67F

Cooling performance can be checked when the outdoor temperature is above 75. To check cooling performance, allow pressures to stabilize and measure indoor wet bulb temperature, outdoor dry bulb temperature and pressures (both head and suction). Locate outdoor dry bulb and indoor wet bulb temperature. Find the intersection of the outdoor dry bulb temperature and indoor wet bulb temperature. Read head (or liquid) and suction pressure value in the left hand column of the chart. Actual Head Pressure should be 10 PSIG of chart. Suction Pressure should be 3 PSIG of chart.

63F 59F

1
50 40 60 80 100 120

OUTDOOR TEMPERATURE (F)

Example:
Outdoor Dry Bulb Temperature = 85F Indoor Wet Bulb Temperature = 67F
*Note: Interconnecting Lines: Gas - 7/8" O.D.: Liquid - 5/16" O.D.

Answer:
Suction Pressure @1060 CFM = 74 PSIG Head Pressure @ 1060 CFM = 210 PSIG

10

Charging By Subcooling Cooling Mode R-22


For charging outdoor units at above 65F outdoor temperature in cooling mode and with indoor TXV.
420 370 320 REMOVE REFRIGERANT 270 220 ADD REFRIGERANT 170 120 70 80 90 100 110 120 130

TXV REFRIGERANT CHARGING CURVE

LIQUID PRESSURE (PSIG)

LIQUID TEMPERATURE (F)

CHARGING CURVE SELECTION CHART


65 60 55

REFRIGERANT LINE LIFT (FEET)

50 45 40 35 30 25 20 15 10 5

UPPER CURVE

MIDDLE CURVE LOWER CURVE

0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85

TOTAL REFRIGERANT LINE LENGTH (FEET)

1. Measure Liquid Line Temperature and Refrigerant Pressure at service valves. 2. Determine total refrigerant pipe length and height (lift) if indoor section is above the condenser. Plot the intersection of the two points on the Curve Selection Chart to determine which curve to use. 3. Plot the pressure and temperature on the TXV Charging Curve. 4. If the lines cross above the curve, remove refrigerant; if below curve, add refrigerant. 5. Whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before additional measurements can be made. 6. When system is correctly charged, refer to System Performance Curves to verify charge and performance. 7. Exception Model 6H0024A100A will have 30 subcooling in cooling. Its system performance charts are with 30 subcooling.

11

Performance Heating Mode R-22


Heat Pump with Capillary Tubes or FCCV
These charts are located in the outdoor section along with the charging charts. If the unit has a capillary tube outdoors these charts should NOT be used for charging but only to ensure you are in the ball park on the charge and that the system is working properly. Once this has been established you should use the charging chart on the outdoor unit. A typical chart is shown on the next page to fine tune the charge for maximum efficiency. 3. To check either HEAD or SUCTION PRESSURE enter the chart on the bottom scale marked OUTDOOR TEMPERATURE. 4. Draw a vertical line up to the INDOOR TEMPERATURE and read SUCTION PRESSURE or HEAD PRESSURE horizontally to the left in the appropriate airflow column. 5. The HEAD PRESSURE reading on the gauge should be equal to, or within 5 PSIG BELOW the chart reading. 6. The SUCTION PRESSURE reading on the gauge should be within 3 PSIG of the chart reading.

To use the chart:


1. Read indoor and outdoor temperatures at the air handler and outdoor unit respectively. 2. Measure head and suction pressures at the outside pressure tap.

INDOOR CFM 1100


400

1200
400

1300
400

350

350

350

INDOOR ENTERING DRY BULB F 80

HEAD PRESSURE (PSIG)

300

300

300

70 60

This is a Typical Chart and is Not Universal for All Heat Pumps.

250

250

250

200

200

200

150

150

150

100

100

100 -20 -10 0 10 20 30 40 50 60

OUTDOOR TEMPERATURE (F)

80 70

80 70 60 50 40 30 20 10 0

80 70 60 50 40 30 20 10 0 -20 -10 0 10 20 30 40 50 60

SUCTION PRESSURE (PSIG)

60 50 40 30 20 10 0

80 70 60

INDOOR ENTERING DRY BULB F

OUTDOOR TEMPERATURE (F)

12

Charging Heating Mode R-22


Heat Pump with Capillary Tubes or FCCV
1. Unit must be in the Heating Mode with stabilized running conditions and coil must be free of ice. 2. Measure suction pressure and discharge pressure and check against pressure curve performance in the outdoor unit. If pressures are within tolerance proceed with the following steps. If pressures are not within tolerance see preceding page. 3. Measure outdoor dry bulb temperature at the outdoor unit. 4. Measure indoor dry bulb temperature at the air handler. 5. Measure Hot Gas temperature near outdoor unit. 6. Using the Charging Chart on the outdoor unit find the intersection where the outdoor temperature and the indoor temperature meet. Read hot gas temperature for this intersection. If measured hot gas temperature is more than 2 above chart value, add R-22 until within 2 degrees. If measured hot gas temperature is more than 2 below chart value, remove R-22 until within 2, using an approved recovery system.

This is a Typical Chart and is Not Universal for All Heat Pumps.
220
INDOOR DRY BULB TEMPERATURE F

COMPRESSOR DISCHARGE GAS TEMPERATURE F

200

80F 70F 60F

180

160

140

120

10

20

30

40

50

60

O.D. TEMPERATURE F

continued

13

Charging Heating Mode R-22


Current Method Split Heat Pump with a TWV030A Air Handler Heat Pump with TXV Outdoor Unit Indoor Airflow 1000 CFM

continued

PERFORMANCE CURVES ARE NOT UNIVERSAL


Indoor Unit Alternates See Correction Table CORRECTION TABLE
400 350
HEAD PRESSURE (PSIG)

Indoor Unit

CFM

Corr. S

Press. H

300 250 200 150

80F

70F 60F

INDOOR ENTERING DRY BULB F.

1
100
0 20 40 60 80

100
90 80 70
SUCTION PRESSURE

2
80F 60F
INDOOR ENTERING DRY BULB F

60

3
50 40 30 20 10

TXA036A4HPA TXA736A4HPA TXC042A4HPA TXA042A4HPA TXA742A4HPA TWV025A140A TWV725A140A TWV730A140A TWV036A140A TWV736A140A TWV042A140A TWV742A140A TWH024A140A TWH742A140A TWH030A140A TWH730A140A TWH036A140A TWH736A140A TWH042A140A TWH742A140A

1125 1125 1125 1125 1125 900 900 1000 1125 1125 1125 1125 900 900 1000 1000 1125 1125 1125 1125

-1 -1 -1 -1 -1 1 1 0 -1 -1 -1 -1 1 1 0 0 -1 -1 -1 -1

-15 -15 -20 -20 -20 15 15 0 -15 -15 -20 -20 15 15 0 0 -15 -15 -20 -20

Heating performance can be checked when the outdoor temperature is below 60F. To check heating performance, allow pressures to stabilize and measure indoor dry bulb temperature, outdoor temperature and pressures (both head and suction). Locate outdoor and indoor dry bulb temperature, find the intersection of the outdoor temperature and indoor temperature and read head or suction pressure value in the left hand column of the chart. Actual Head Pressure should be: Equal to or less than 5 PSIG of chart. Suction Pressure should be 3 PSIG of chart.

1
0 0 20 40 60 80

OUTDOOR TEMPERATURE (F)

14

Charging By Weight
When a refrigerant system is opened, as in compressor replacement, the service technician may want to recharge the system by weight. The units are shipped with the minimum operating charge. The minimum charge is the charge required for 25 feet of line for units produced prior to 8/98. For units produced after this date, the shipped charge is the total system charge when installed with 15 feet of refrigerant lines and the smallest indoor coil, by internal volume, that the unit is listed within the ARI Directory. The smallest indoor coil may not be the tested combination. This minimum operating charge is shipped in the unit so at start up time no refrigerant recovery will be necessary. Indoor coils are shipped with a 10 PSIG nitrogen holding charge.

Package Systems
The charge stamped on the units nameplate is the total charge. With an accurate scale the weight method of charging is a rapid and accurate method of charging.

Split Systems
Charging by weight using units nameplate information only is not an approved method. Prior to 8/98, the refrigerant charge stamped on the outdoor unit nameplate was the total system charge when installed with 25 feet of refrigerant lines and with the indoor coil or air handler that the outdoor unit was rated with. The Department of Energy, test procedures require the manufacturer to test and rate their outdoor unit with their highest sales volume indoor coil or air handler. This rated combination is listed in the Air Conditioning and Refrigeration Institute Directory, ARI. In the ARI Directory this tested combination is noted by a sign. Unless you have this tested combination installed, which is listed in the ARI Directory only, the charge stamped on the outdoor unit nameplate is of little use. Further, this nameplate stamping is not the charge always shipped in the outdoor unit.

Evacuation
When the refrigerant lines installation is completed and leak checked they and the indoor coil must be dehydrated. Proper dehydration is achieved when these components are evacuated to a minimum of 500 microns.

15

Calibrating Pressure Gauges


To check pressure gauges, connect the low pressure gauge to a cylinder of CFC-12 and the high pressure gauge to a cylinder of HCFC-22. Make sure the cylinders have been left standing in a stable environment, away from radiant heat sources, for several hours. This guarantees that the temperature inside the cylinder is the same as the temperature outside the cylinder. Measure the temperature of the air around the cylinders. Now compare the pressure indicated on the gauges to the Temperature-Pressure Chart. Use the adjustment screw on the gauges to calibrate them to this pressure. EXAMPLE: The air temperature is 75F. The low pressure gauge (connected to the cylinder of CFC-12) should be adjusted to indicate 77 PSIG. The high pressure gauge (connected to HCFC-22) should indicate 132.25 PSIG or as close as we can read it. We dont need a pressure/temperature chart to make this check. Most manifold gauges used for refrigeration and air conditioning have this chart built into the scales, right on the gauge. Figure 1 is a copy of the scales on a typical set of refrigeration gauges. Notice the inside scales labeled HCFC-22, CFC-12 and CFC-502. The values on these scales are the saturation temperatures for the pressures indicated. If the low pressure gauge is connected to a cylinder of CFC-12, and the air temperature is 75F, adjust the needle to indicate a temperature of 75F on the CFC-12 (middle) scale. The pressure reading is about 77 PSIG. Finally, after calibrating the high pressure gauge to HCFC-22, calibrate it also to CFC-12. This gives us two reference points for more accuracy. Due to the rough handling these test instruments go through day after day, it is important to develop a habit of routine maintenance and calibration. These instruments are our eyes and ears. How can we quickly and accurately service equipment if we cant trust the measurements we make?

80

40
50

80
90
50

50

50

40

CFC-12 CFC-502

60

60

10

80

20

30

250

12

0
Figure 1

in Hg p.s.i.

Troubleshooting Chart-What To Check


. EF LD . RO EF NT D CO RM F. T TE DE OS T AY FR OS EL ING DE EFR T R AK E D OS LE IV FR VE CT DE VAL EFE ING K LD K EC OI LEA NS CH V C OV TIO SO S RIC OW ST FL RE IR AT . A HE R. CI I.D R N F. S. PE E RE RE SU OP K N UC TIO ST A V UL W TX IRC FLO C IR S RE A LE R D. B AI O. SA AD D. S. EN O O. RE ND P. L E O VA RG NC E E HA E NO IV RC RG SS VE A CE . O CH OR EX REF DER ESS R UN PR O F. M SS RE CO PRE SE NT M FU IE CO GE IL O FIC K TA EF UC OL R C IN ST V TO TAT W C S LO NTA MO ER CO HER RM T FO NG NS IRI RA W TS L T GE AC RO LTA NT AY NT VO CO EL CO W OR RT R OR LO ACT TA CIT S PA OR NT CA IT CO T AC L AR AP IO ST N C SOR G RU RES IRIN Y P M E W PL CO AG UP LT R S DE VO WE MO GH PO ECK HI CH TO T HA W

Refrigerant Circuit Head Pressure Too High Head Pressure Too Low Suction Pressure Too High Suction Pressure Too Low Liquid Refrigerant Floodback(TXV) Liquid Refrigerant Floodback Cap Tube ID Coil Frosting Compressor Runs Inadequate or No Cooling/Heating Electrical Compressor & OD Fan Will Not Start Compressor Will Not Start But OD Fan Runs OD Fan Will Not Start Compressor Hums But Will Not Start Compressor Cycles On IOL ID Blower Will Not Start Defrost Unit Will Not Initiate Defrost Defrost Terminates On Time Unit Icing Up

C H C H C H C H C H C H C H C H C H C H C H C H C H C H C H C H C H P - Primary Causes S - Secondary Causes P P P P P S P P S P P P P P P P P S P P S P P P P P S P S P P S P S P P S S S S S S S S S S S S S S S S S S S S S P S S P S S S P P

P P S P S P S P P S P P P P P S P S P

S P S S

S P S S S S S S S S S S S S P S P S S S S P P S S S P S S S P S S

11 0
P P P P P S P S SS S S P S S S S P S P S S P

30

HCFC-22

10

S S S

P P P S PP S P S PP S

S S

100
PP P P P P

P P S S

60

90

C - Cooling H - Heating

16

70
S P

70

30
40

60
60
30

20

20

50
50
10

10
40
0

40

30
10

30
20

20
20

0 04 03 10 2

10
0

30

10

10

20

40

Refrigerant 410A
Background
The traditional refrigerants, which have been used in central air conditioning systems for the past fifty years, have been declared to be a threat to the environment. This is due to the presence of Chlorine in their chemical make-up. As a consequence, the air conditioning industry has been required to search for a suitable replacement for the most popular of the current refrigerants, Refrigerant 22. Since there are concerns of efficiency and service use, as well as the environmental issues, the job has not been easy. To locate a replacement and qualify it for use in the products we manufacture has taken years of work. The refrigerant chosen at this time is Refrigerant 410A. Continuing study will be conducted into other alternates. together and may separate when released from pressure. It is said to be near AZEOTROPIC in its construction. This word means that it is a mixture, not a compound. It is manufactured by combining Refrigerant 32 and Refrigerant 125. Both of these refrigerants are made of Hydrogen, Fluorine, and Carbon and are referred to as HFCs. The most important reason for using an alternate refrigerant is that it does not contain any Chlorine. Under Federal law, no release of refrigerant is allowed beyond the minimum required to do service to the products. This DE MINIMUS or least possible loss must be closely observed during service to avoid being subject to possible fines and worse. Even the alternative refrigerants cannot be released to atmosphere. The EPA (Environmental Protection Agency) requires they must be collected and handled as the existing refrigerants are handled. The issue here is not Ozone Depletion but the contribution to Global Warming and the waste of a valuable resource. The alternative refrigerant R-410A is not a drop-in replacement for R-22. Since they use different oils, different drier construction materials and different expansion devices, they require the greatest caution in replacement situations. At this time, R410A is intended for use in new equipment. The service tools that are used for the alternative refrigerant are not the same as the tools used for the current refrigerants and this will be explained in this manual. Please read and heed the warnings included in the material in this manual and the manufactures literature included with the products containing this alternative refrigerant.

Refrigerant Characteristics
The refrigerants developed in the nineteen twenties, using chlorine, such as Refrigerant 22, were uniform in their chemical make-up. Such refrigerants are called compounds. Each molecule of the refrigerant is like every other molecule. There is no way in the field to separate the elements of a compound once it has been made. Only the most sophisticated laboratory equipment can break the building blocks of the refrigerant apart. They contained Hydrogen, Chlorine, Fluorine, and Carbon. These refrigerants were called HCFCs. The alternative refrigerants are different in the materials used to make them. They are also different in the manner in which they are made. Refrigerants like Refrigerant 410A are mixtures of chemicals. This means its components are not as tightly bonded

17

Refrigerant Safety
The alternative refrigerant, R-410A, like R-22 is a safe product. The same precautions must be observed when using either one. However, the technician must be aware of several differences in the handling of R-410A. When the cylinders containing Refrigerant 410A are sitting upright, the valve will release liquid refrigerant. As you can see in Figure 1, there is a dip tube in the tank reaching to near the bottom of the cylinder. To charge with vapor, turn the cylinder upside down as shown in Figure 2. For cylinders made after 299, turn the cylinder upside down as shown in Figure 1A for liquid and upright for vapor as shown in Figure 2A. Refrigerant cylinders containing Refrigerant 410A are ROSE colored for identification. Refrigerant cylinders should never be stored at 125F or higher temperatures. Never charge any refrigerant cylinder to greater than 80% of its capacity. This was true for Refrigerant 22 and is also true for Refrigerant 410A. Refrigerant 410A boils at -62.9F. when released to atmosphere. This is twenty degrees colder than Refrigerant 22. The danger of frostbite is much greater on exposed skin. Wear gloves and protect your eyes with safety glasses at all times. This refrigerant, like Refrigerant 22, is low in toxicity but it can still be harmful to humans as it displaces oxygen. Since it is heavier than air, it will form puddles in low places. Use adequate ventilation near equipment that is leaking. Refrigerant 410A is classified as non-flammable. Like Refrigerant 22, when mixed with air under pressure it can ignite. Make sure the system is without pressure before using a torch for a repair. Recovery cylinders used with Refrigerant 410A are not the same cylinders used for Refrigerant 22. Refrigerant 410A recovery cylinders are constructed and tested to higher pressures, 400 PSIG (Pounds to the Square Inch Gauge). Since the vapor pressure of Refrigerant 410A is from 50% to 70% higher than Refrigerant 22 at the same temperature, service hoses, manifolds and gauges are all constructed to withstand higher pressures. See Figure 3 for the gauge faces. The oils used with the alternative refrigerant are also different. The oil used with the HCFC refrigerants such as 22 was mineral oil based. The oil used

Figure 1

Figure 2

Figure 1A
Invert cylinder if it has NO Dip Tube for charging. NO Dip Tube on cylinders manufactured after Feb. 1999.

Figure 2A
NO Dip Tube on cylinders manufactured after Feb. 1999.

18

Refrigerant Safety
with Refrigerant 410A is a synthetic oil called POLYOLESTER, abbreviated POE. This oil requires special handling. Since it is hygroscopic in nature, (it picks up moisture from the air), it must be kept sealed until used. Liquid line driers must be changed whenever the system is opened for service. A good vacuum cannot adequately remove the moisture from the synthetic oil as it did from a mineral oil based lubricant. The only system additive that may be used is AcidAway. This additive has ONLY been approved for Refrigerant 22, when used in accordance with the manufacturers instructions. All other additives are discouraged and are not recommended. The last caution will seem unusual to the technician. Synthetic oil will attack many materials used in roofing. When service is required on equipment mounted on a roof, the surrounding roof must be protected from oil spray or spills. A plastic covering or tarp must be spread around the work area. This caution must be taken seriously! Wiping up spilled oil will not stop it from causing long term damage to roofing materials.

Figure 3

Application Notes
Replacement of a unit using Refrigerant 22 with a unit using Refrigerant 410A requires that both the indoor and outdoor units be replaced. If the existing line sets are the correct size and the oil from the replaced unit did not contain any acid, the existing line set may be used. The technician should make every effort to eliminate any low spots in the lines forming traps. Blow through the lines with dry nitrogen to reduce the amount of oil remaining in the lines. Then the lines may be used. Line set lengths and lift restrictions will be similar to those found in R22 systems. This table is shown for training only, and must be used only for that purpose. For line sizing, use Pub. No. 32-3009 latest edition.

5 Ton R22 7/8 1 1/8 1 3/8 3/4 7/8* 1 1/8 3/8

4 Ton 7/8 1 1/8 3/4 7/8* 1 1/8 3/8

3.5 Ton 3/4 7/8 1 1/8 3/4* 7/8 3/8

3 Ton 3/4 7/8 5/8 3/4* 7/8 3/8

2.5 Ton 5/8 3/4 7/8 5/8* 3/4 7/8 5/16

2 Ton 5/8 3/4 7/8 5/8* 3/4 7/8 5/16

1.5 Ton 5/8 3/4 1/2* 5/8 3/4 1/4

1 Ton 1/2 5/8 1/2* 5/8 1/4

R410A Liquid Line


*Rated tube size

19

System Charging Using R-410A


Charging systems with refrigerants which are classified as AZEOTROPIC, such as R-410A, require special technique. The blended refrigerants may tend to separate when charging is done with only the vapor. This may lead to FRACTIONATION, when the refrigerants in the blend do not boil off at the exact same temperature. Fortunately, R-410A has a wellmatched pair of refrigerants. The difference in boiling points is less than a degree. This means that for our purposes the refrigerant does not require you to calculate the temperature difference known as GLIDE. For all our work, the refrigerant will have a single boiling point for each pressure. The use of liquid in charging is not new. We have charged the high side of the system with liquid for many years. Charging the low side with liquid will require the use of a special charging metering device. A Chargefaster (CH200) by Watsco or its equivalent must be used. This device allows the refrigerant to be taken from the cylinder as liquid but puts it into the system as a vapor. Remember the refrigerant cylinder will dispense liquid when it is upright because of the cylinder dip tube on cylinders manufactured before Feb. 1999. The cylinder must be inverted if manufactured after Feb. 1999 to obtain liquid for charging. To dispense vapor directly, the cylinder must be in the upright position. The subcooling method of charging will be used in the cooling cycle when an expansion value (TXV) is installed in the system. In this method of charge adjustment, an accurate reading of the temperature of one of the refrigerant lines is required. The standard service thermometer is not accurate or fast enough to properly react. An electronic temperature tester, such as an Annie A-8 or equivalent, should be used. The sensing element must be tightly connected to the tubing and insulated from the ambient air. The charts for charge adjustment will be found in the equipment and the service literature for the product. While charging the system, allow sufficient time for the system to react to the adjustment before adding or removing charge.

20

R-410A Temperature and Pressure Chart

TEMP

R410

TEMP

R410

TEMP

R410

-60 -55 -50 -45 -40 -35 -30 -25 -20 -15 -10 -5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

1.2 3.4 5.8 8.6 11.6 14.9 18.5 22.5 26.9 31.7 36.8 42.5 48.6 49.9 51.2 52.5 53.8 55.2 56.6 58.0 59.4 60.9 62.3 63.8 65.4 66.9 68.5 70.0

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43

71.7 73.3 75.0 76.6 78.3 80.1 81.8 83.6 85.4 87.3 89.1 91.0 92.9 94.9 96.8 98.8 100.8 102.9 105.0 107.1 109.2 111.4 113.6 115.8 118.0 120.3 122.6 125.0
Figure 4

44 45 46 47 48 49 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155

127.3 129.7 132.2 134.6 137.1 139.6 142.2 155.5 169.6 184.6 200.6 217.4 235.3 254.1 274.1 295.1 317.2 340.5 365.0 390.7 417.7 445.9 475.6 506.5 539.0 572.8 608.1 645.0
Pub No. 34-3400-01

21

Subcooling Charging Table

REQUIRED LIQUID LINE TEMPERATURE


LIQUID PRESSURE AT SERVICE VALVE (PSIG) REQUIRED SUBCOOLING TEMPERATURE (F) 8 10 12 14 16 18

189 195 202 208 215 222 229 236 243 251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474 486 499 511

58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128

56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126
Figure 5

54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124

52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122

50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120

48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118

22

410A Refrigerant
In the cooling cycle the Subcooling chart shown in Figure 5 will help you to make the decisions when charging units equipped with thermostatic expansion valves (TXV). Since the valve controls the superheat, subcooling must be used to determine the correct charge level. It is recommended that charging be done in the liquid phase. When adding liquid refrigerant into the low side of the system, a charge-metering device is recommended (WATSCO CH200, or equivalent). Allow ample time when adding refrigerant for the system to balance out, to avoid having to recover refrigerant. Existing Halide leak detectors do not work with R-410A. Existing acid test kits do not work with R-410A. (New kits are being developed.) Existing driers do not work with R-410A. Note that although R-410A does not deplete the ozone layer, all refrigerants must be recovered. R-410A systems use POE oil, which is not compatible with the oils used in R-22 systems. If existing refrigerant lines are to be used with an R-410A system (assuming that the line sizes are acceptable), they must be thoroughly blown out with dry nitrogen to remove the old oil. Blow vertical sections from top to bottom. POE oils absorb moisture very quickly. Keep container tightly closed, whenever possible, and expose the system to the atmosphere as little as possible. POE oils can also damage a roof, if spilled. Vacuum pumps can not remove all of the moisture from POE oils. Change the liquid line drier anytime the system is opened to the atmosphere. Suction line driers are to be left in the system for no more than 72 hours. Use only liquid and suction line driers approved for R-410A. Since all current R-410A systems are expansion valve systems, the refrigerant charge is to be checked by the subcooling method, See Charts 6 and 7 in the cooling cycle. In heating use the heating discharge pressure curves. Maximum liquid line pressure drop with R-410A systems is 50 PSI (10 subcooling). Recommended suction line pressure drop (2F) is 4.8 PSI (Round up to 5.0). At this time, only matched systems are permitted with R-410A. Both indoor and outdoor units must be changed in a unit replacement. R-410A boils at -62.9 at atmospheric pressure, so beware of frostbite! Line set lengths and lift restrictions will be similar to those found in R22 systems, as long as the rise is limited to 60 feet and the length is 200 feet or less. Tables on the following pages show the line sizes.

23

R410A Split Cooling Units Only


TXV REFRIGERANT CHARGING CURVE

600

For charging outdoor units with R410A refrigerant at above 65F outdoor temperature in cooling mode and with indoor TXV.

LIQUID PRESSURE (PSIG.)

550 500 450 400 350 300 250 200 70 80 90 100 110 120 130
ADD REFRIGERANT REMOVE REFRIGERANT

LIQUID TEMPERATURE (F.)


1. Measure Liquid Line Temperature and Refrigerant Pressure at service valves. 2. Determine total refrigerant pipe length and height (lift) if indoor section is above the condenser. Plot the intersection of the two points on the Curve Selection Chart to determine which curve to use. 3. Plot the pressure and temperature on the TXV Charging Curve. 4. If the lines cross above the curve remove refrigerant, if below curve add refrigerant. 5. Whenever charge is removed or added, the system must be operated for a minimum 20 minutes to stabilize before additional measurements can be made. 6. When system is correctly charged refer to System Performance Curves to verify charge and performance.
Chart 6

CHARGING CURVE SELECTION CHART


R E F R I G E R A N T L I N E L I F T ( F E E T )

60 50 40 30 25 20 15 10 0

UPPER CURVE MIDDLE CURVE LOWER CURVE

10

20

25

30

40

60 80

TOTAL REFRIGERNT LINE LENGTH (FEET)

ERPD 4292A DISTR T-1 A150999P05 REV.0

24

R410A Split Heat Pump Units Only


TXV REFRIGERANT CHARGING CURVE

600

For charging outdoor units with R410A refrigerant at above 65F outdoor temperature in cooling mode and with indoor TXV.

LIQUID PRESSURE (PSIG.)

550 500 450 400 350 300 250 200 70 80 90 100 110 120 130
ADD REFRIGERANT REMOVE REFRIGERANT

LIQUID TEMPERATURE (F.)


1. Measure Liquid Line Temperature and Refrigerant Pressure at service valves. 2. Determine total refrigerant pipe length and height (lift) if indoor section is above the condenser. Plot the intersection of the two points on the Curve Selection Chart to determine which curve to use. 3. Plot the pressure and temperature on the TXV Charging Curve. 4. If the lines cross above the curve remove refrigerant, if below curve add refrigerant. 5. Whenever charge is removed or added, the system must be operated for a minimum 20 minutes to stabilize before additional measurements can be made. 6. When system is correctly charged refer to System Performance Curves to verify charge and performance.
Chart 7

CHARGING CURVE SELECTION CHART


R E F R I G E R A N T L I N E L I F T ( F E E T )

60 50 40 30 25 20 15 10 0

UPPER CURVE MIDDLE CURVE LOWER CURVE

10

20

25

30

40

60 80

TOTAL REFRIGERNT LINE LENGTH (FEET)

ERPD 4309B DISTR T-1 A150999P06 REV.0

25

R-410A Charging and Performance Cooling Mode


Current Method Split System with a RWE040E13 Coil Cooling System with Thermal Expansion Valve. Indoor Airflow 1160 CFM

PERFORMANCE CURVES ARE NOT UNIVERSAL


Indoor Unit Alternates See Correction Table

600 550

PRESSURE CURVE CORRECTION PSIG


Alternate Indoor Units With Thermal Expansion Valve
2
71F INDOOR ENTERING 59F WET BULB F

LIQUID PRESSURE (PSIG)

500 450 400 350 300 250 200


40 170 165 160 155 50 60 70 80

Indoor Unit

CFM

Cooling Suction Head Pressure Pressure

Heating Suction Head Pressure Pressure

RWE040E13* RWE037E13
4 3

1160 1060

0 -7

0 -2

0 1

0 53

*Base Indoor Unit(s) Curves on 21X151830 Rev.0

Cooling performance can be checked when the outdoor temperature is above 65.
1
90 100 110 120

OUTDOOR TEMPERATURE (F)

To check cooling performance, allow pressures to stabilize and measure indoor wet bulb temperature, outdoor dry bulb temperature and pressures (both head and suction). Locate outdoor dry bulb and indoor wet bulb temperature. Find the intersection of the outdoor dry bulb temperature and indoor wet bulb temperature. Read head (or liquid) and suction pressure value in the left hand column of the chart. Actual Head Pressure should be 20 PSIG of chart.
INDOOR ENTERING WET BULB F

71F

150
SUCTION PRESSURE (PSIG)

145
67F

140 135 130 125 120 115 110 105

Suction Pressure should be 5 PSIG of chart.

Example:
Outdoor Dry Bulb Temperature = 85F Indoor Wet Bulb Temperature = 67F

63F

Answer:
59F

Suction Pressure @1160 CFM = 137 PSIG Head Pressure @ 1160 CFM = 340 PSIG

1
100 40 50 60 70 80 90 100 110 120

*Note: Interconnecting Lines: Gas - 3/4" O.D. Liquid - 3/8" O.D.


From Dwg. No. 21X151830 Rev. 0

OUTDOOR TEMPERATURE (F)

26

R-410A Charging Heating Mode


Current Method Split Heat Pump with a RWE040E13 Air Handler Heat Pump with TXV Outdoor Unit Indoor Airflow 1160 CFM

PERFORMANCE CURVES ARE NOT UNIVERSAL


Indoor Unit Alternates See Correction Table

450
80F

PRESSURE CURVE CORRECTION PSIG


Alternate Indoor Units With Thermal Expansion Valve
INDOOR ENTERING DRY BULB F.

400
HEAD PRESSURE (PSIG)
70F

350
60F

Indoor Unit

CFM

Cooling Suction Head Pressure Pressure

Heating Suction Head Pressure Pressure

300 250 200 150


0 10 20 30 40 50 60 70 80

RWE040E13* RWE037E13

1160 1060

0 -7

0 -2

0 1

0 53

*Base Indoor Unit(s) Curves on 21X151830 Rev.0

Heating performance can be checked when the outdoor temperature is below 60F. To check heating performance, allow pressures to stabilize and measure indoor dry bulb temperature, outdoor temperature and pressures (both head and suction). Locate outdoor and indoor dry bulb temperature, find the intersection of the outdoor temperature and indoor temperature and read head or suction pressure value in the left hand column of the chart. Actual Head Pressure should be: Equal to or less than 10 PSIG of chart. Suction Pressure should be 5 PSIG of chart.

OUTDOOR TEMPERATURE (F)


140 130 120
110
SUCTION PRESSURE

80F 60F

INDOOR ENTERING DRY BULB F

100 90 80 70 60 50 40 30 20 0 10 20 30 40 50 60 70 80

OUTDOOR TEMPERATURE (F)

*Note: Interconnecting Lines: Gas - 3/4" O.D. Liquid - 3/8" O.D.


From Dwg. No. 21X151830 Rev. 0

27

Notes

28

Notes

29

Pub. No. 34-4100-06

P.I. (L)

You might also like